Delta VFD ovd Fault: Over-voltage During Deceleration

Quick answer

ovd on a Delta MS300 drive means DC bus over-voltage during deceleration. Delta says it trips at 410 VDC on 230V models, 820 VDC on 460V models and 1116 VDC on 575V models. The first cause Delta lists is a deceleration time that is too short, so the motor sends too much energy back into the drive. Delta's fixes: increase the deceleration time, connect a brake resistor or braking unit, use S-curve, over-voltage stall prevention (Pr.06-01) or auto-deceleration (Pr.01-44). VFD-EL-W and VFD-M use one ov code for any DC bus over-voltage, not only during deceleration.

Safety: Only a qualified electrician should work on the drive or motor wiring. Delta's MS300 manual says to switch off the AC input power before any wiring, not to touch internal parts until the POWER LED is off, and to measure the DC bus voltage and wait until it is below 25 VDC, because hazardous voltage can stay in the capacitors after power-off. The VFD-EL-W and VFD-M manuals also say to make sure the RUN command is OFF before you press RESET.

Common causes

  • Deceleration time too short, so the load sends back too much regenerative energy
  • Stall prevention level set lower than no-load current
  • Supply voltage too high, or voltage spikes
  • A phase-in (power factor) capacitor switching on the same supply
  • Motor ground fault
  • Wrong wiring of the brake resistor or braking unit
  • Interference

Fix it step by step

  1. Increase the deceleration time (MS300: Pr.01-13, 01-15, 01-17, 01-19).
  2. Consider S-curve, over-voltage stall prevention (Pr.06-01) or auto-deceleration (Pr.01-44), as Delta suggests.
  3. If the load is heavy or stops fast, have an electrician connect a brake resistor or braking unit as Delta specifies.
  4. Have an electrician check the supply voltage is within the drive rating.
  5. Reset once the DC bus voltage has dropped below 90% of the trip level, with RUN OFF.

Still showing ovd?

  • If phase-in capacitors on the same supply cause surges, Delta says to install an AC reactor.
  • Delta's related codes on MS300 are separate faults with their own causes: ovA (during acceleration), ovn (constant speed), ovS (at stop).

हिंदी में

Delta VFD में ovd का मतलब है मोटर धीमी होते समय DC बस वोल्टेज बहुत बढ़ गया (230V मॉडल में 410 VDC, 460V में 820 VDC)।

  1. Deceleration time बढ़ाएं।
  2. भारी लोड हो तो इलेक्ट्रीशियन से ब्रेक रेज़िस्टर या ब्रेकिंग यूनिट लगवाएं।
  3. इलेक्ट्रीशियन से सप्लाई वोल्टेज चेक कराएं।
  4. वोल्टेज कम होने पर RUN बंद करके RESET करें।

Questions people ask

Does ovd mean my supply voltage is too high?

It can. Delta lists a short deceleration time first and also lists high supply voltage, so check both.

What is ov on VFD-EL-W?

VFD-EL-W shows a single ov code (fault ID 2) for DC bus over-voltage. Delta's fixes are the same: check input voltage, increase deceleration time or add a brake resistor.