Quick answer
oL on a Delta AC drive means overload: the drive detected excessive output current for too long. On VFD-EL-W Delta says the drive can withstand 150% of rated current for at most 60 seconds. On MS300 (normal duty) the drive can sustain 120% of rated output current for 1 minute or 150% for 3 seconds; on heavy duty, 150% for 1 minute or 200% for 3 seconds. Delta's fixes: reduce the load, increase acceleration / deceleration time, correct the V/F curve, or use a larger drive.
Safety: Only a qualified electrician should work on the drive or motor wiring. Delta's MS300 manual says to switch off the AC input power before any wiring, not to touch internal parts until the POWER LED is off, and to measure the DC bus voltage and wait until it is below 25 VDC, because hazardous voltage can stay in the capacitors after power-off. The VFD-EL-W and VFD-M manuals also say to make sure the RUN command is OFF before you press RESET.
Common causes
- Load too large
- Acceleration / deceleration time or working cycle too short
- V/F voltage too high
- Drive capacity too small
- Overload during low-speed operation
- Torque compensation too large
- Output phase loss (broken cable or loose screws)
Fix it step by step
0 of 5 done
- Reduce the load.
- Increase the acceleration / deceleration time (MS300: Pr.01-12 to 01-19).
- Check the V/F curve settings (MS300: Pr.01-01 to 01-08) and torque compensation.
- Have an electrician check the motor cable and terminal screws for an output phase loss.
- Wait 5 seconds after the fault clears, RUN OFF, then RESET.
Still showing oL?
- Related codes differ by series. On VFD-EL-W and VFD-M, oL1 is the internal electronic overload trip and oL2 is motor overload. The MS300 has no oL1 or oL2; it uses EoL1 and EoL2 for electronic thermal relay 1 and 2 protection.
हिंदी में
Delta VFD में oL का मतलब है ड्राइव पर ओवरलोड, ज़्यादा करंट ज़्यादा देर तक।
- लोड कम करें।
- Acceleration / deceleration time बढ़ाएं।
- V/F और torque compensation सेटिंग चेक करें।
- न सुधरे तो बड़ी क्षमता की ड्राइव लगाएं।
Questions people ask
What is the difference between oL, oL1 and oL2?
On VFD-EL-W and VFD-M, oL is drive overload, oL1 is the internal electronic overload trip, and oL2 is motor overload. The oL1 and oL2 codes do not exist on MS300.
Did this fix your problem? क्या इससे मदद मिली?
What went wrong?
Thanks. This helps us fix our guides. धन्यवाद!
Sources
- Delta MS300 Series User Manual (2026-04): Chapter 14 Fault Codes, pp.547–581
- Delta VFD-EL-W Series User Manual (2024-09): 6-1 Fault Code Information, pp.6-3 to 6-7
- Delta VFD-M User Manual (Aug 2015): Pr.73 fault record list pp.4-52 to 4-53, error code list p.4-69, Chapter 6 Fault Code Information