Quick answer
oH1 on a Delta AC drive means overheating. On the MS300 it is IGBT overheating: the IGBT temperature went over the protection level and the drive stopped. On VFD-EL-W it means the heat sink temperature is too high. Delta's causes: high ambient or cabinet temperature, blocked ventilation, an obstructed heat sink or a cooling fan that is not running, too little space around the drive, too heavy a load, or running at 100% or more of rated output for a long time.
Safety: Only a qualified electrician should work on the drive or motor wiring. Delta's MS300 manual says to switch off the AC input power before any wiring, not to touch internal parts until the POWER LED is off, and to measure the DC bus voltage and wait until it is below 25 VDC, because hazardous voltage can stay in the capacitors after power-off. The VFD-EL-W and VFD-M manuals also say to make sure the RUN command is OFF before you press RESET.
Common causes
- Ambient or control cabinet temperature too high
- Ventilation holes of the cabinet blocked
- Heat sink obstructed, or cooling fan not running
- Not enough space around the drive
- Load too large for the drive
- Running at 100% or more of rated output for a long time
Fix it step by step
0 of 5 done
- Check the ambient temperature and that the cabinet ventilation holes are not blocked.
- Leave enough space around the drive, and move it away from heat sources such as brake resistors.
- Reduce the load or the carrier frequency, or use a larger drive, as Delta suggests.
- If the heat sink is obstructed or the cooling fan is not running, have an electrician remove the obstruction or replace the cooling fan, as Delta says.
- On MS300, reset once the IGBT temperature is 10°C below the oH1 level.
Still showing oH1?
- Delta also suggests adding a cooling fan or air conditioner for the cabinet.
- VFD-M shows overheating as oH (Pr.73 record 03); its manual says to check that the heat sink fins are clean and the drive has room to breathe.
हिंदी में
Delta VFD में oH1 का मतलब है ड्राइव (IGBT / हीट सिंक) बहुत गरम हो गई।
- पैनल के वेंटिलेशन छेद खुले रखें और कमरे का तापमान देखें।
- ड्राइव के चारों ओर जगह छोड़ें, ब्रेक रेज़िस्टर जैसी गरम चीज़ों से दूर रखें।
- लोड कम करें या बड़ी ड्राइव लगाएं।
- हीट सिंक की सफ़ाई या कूलिंग फ़ैन बदलना इलेक्ट्रीशियन से कराएं।
Questions people ask
Is oH1 a motor overheat?
No. oH1 is the drive's own IGBT or heat sink. Motor overheating has other codes (oH3 / PTC on MS300, PTC1 on VFD-EL-W).
Did this fix your problem? क्या इससे मदद मिली?
What went wrong?
Thanks. This helps us fix our guides. धन्यवाद!
Sources
- Delta MS300 Series User Manual (2026-04): Chapter 14 Fault Codes, pp.547–581
- Delta VFD-EL-W Series User Manual (2024-09): 6-1 Fault Code Information, pp.6-3 to 6-7
- Delta VFD-M User Manual (Aug 2015): Pr.73 fault record list pp.4-52 to 4-53, error code list p.4-69, Chapter 6 Fault Code Information
Last checked: