Delta VFD Fault Codes: MS300, VFD-EL-W and VFD-M Full List
This list comes from the fault code chapters of three Delta user manuals from Delta's download center: MS300 (2026), VFD-EL-W (2024) and VFD-M (2015). Delta uses similar short codes across its drives, but the exact set and wording differ by series: MS300 splits over-voltage and low-voltage into separate codes for acceleration, deceleration, constant speed and stop (ovA, ovd, ovn, ovS, LvA, Lvd, Lvn, LvS), while VFD-EL-W shows a single ov or Lv. Check the series name on the drive's nameplate, then read the rows for that series.
Safety: Only a qualified electrician should work on the drive or motor wiring. Delta's MS300 manual says to switch off the AC input power before any wiring, not to touch internal parts until the POWER LED is off, and to measure the DC bus voltage and wait until it is below 25 VDC, because hazardous voltage can stay in the capacitors after power-off. The VFD-EL-W and VFD-M manuals also say to make sure the RUN command is OFF before you press RESET.
How to see the code
- Read the code on the drive keypad display.
- Check the series on the nameplate (for example MS300, VFD-EL-W, VFD-M).
- Match the code in the rows for that series. MS300 and VFD-EL-W also give a fault ID number, which you see in the fault record parameters.
- Fix the cause first, then reset. Delta says to make sure the RUN command or signal is OFF before RESET.
Delta VFD / drive error code list
| Code | Model type | Meaning | What to do |
|---|---|---|---|
| ocA (fault ID 1) | MS300 | Over-current during acceleration · full fix | ocA on a Delta AC drive means over-current during acceleration. On the MS300, Delta says output current went above three times the rated current while the motor was speeding up, so the drive shut off its output at once and the motor coasted. The first corrective actions Delta lists are a longer acceleration time (or S-curve), auto-acceleration (Pr.01-44) and over-current stall prevention (Pr.06-03). Delta also lists short circuits in the motor cable, poor motor insulation and too large a load. |
| ocd (fault ID 2) | MS300 | Over-current during deceleration | — |
| ocn (fault ID 3) | MS300 | Over-current during steady operation · full fix | ocn on a Delta AC drive means over-current while running at constant speed. On the MS300, Delta says output current went above three times the rated current, so the drive shut off its output at once and the motor coasted. Delta's causes include a short circuit in the motor cable, a locked motor shaft, poor motor insulation, a sudden change in load, and a motor larger than the drive. VFD-EL-W calls it over-current during constant speed operation and VFD-M calls it OCn. |
| GFF (fault ID 4) | MS300 | Ground fault · full fix | GFF on a Delta AC drive means ground fault. On the MS300, Delta says the drive detected a short circuit to ground on the output terminals (U/V/W), so it shut off the output and the motor coasted. Causes: burnt or aged motor insulation, a broken cable, high stray capacitance on long motor cables, interference, or a hardware failure. VFD-M calls it ground fault or fuse failure. This is electrical work for an electrician. |
| ocS (fault ID 6) | MS300 | Over-current at stop | — |
| ovA (fault ID 7) | MS300 | Over-voltage during acceleration | — |
| ovd (fault ID 8) | MS300 | Over-voltage during deceleration · full fix | ovd on a Delta MS300 drive means DC bus over-voltage during deceleration. Delta says it trips at 410 VDC on 230V models, 820 VDC on 460V models and 1116 VDC on 575V models. The first cause Delta lists is a deceleration time that is too short, so the motor sends too much energy back into the drive. Delta's fixes: increase the deceleration time, connect a brake resistor or braking unit, use S-curve, over-voltage stall prevention (Pr.06-01) or auto-deceleration (Pr.01-44). VFD-EL-W and VFD-M use one ov code for any DC bus over-voltage, not only during deceleration. |
| ovn (fault ID 9) | MS300 | Over-voltage at constant speed | — |
| ovS (fault ID 10) | MS300 | Over-voltage at stop | — |
| LvA (fault ID 11) | MS300 | Low-voltage during acceleration | — |
| Lvd (fault ID 12) | MS300 | Low-voltage during deceleration | — |
| Lvn (fault ID 13) | MS300 | Low-voltage at constant speed | — |
| LvS (fault ID 14) | MS300 | Low-voltage at stop | — |
| OrP (fault ID 15) | MS300 | Phase loss protection | — |
| oH1 (fault ID 16) | MS300 | IGBT overheating · full fix | oH1 on a Delta AC drive means overheating. On the MS300 it is IGBT overheating: the IGBT temperature went over the protection level and the drive stopped. On VFD-EL-W it means the heat sink temperature is too high. Delta's causes: high ambient or cabinet temperature, blocked ventilation, an obstructed heat sink or a cooling fan that is not running, too little space around the drive, too heavy a load, or running at 100% or more of rated output for a long time. |
| tH1o (fault ID 18) | MS300 | IGBT temperature detection failure | — |
| oL (fault ID 21) | MS300 | Over load · full fix | oL on a Delta AC drive means overload: the drive detected excessive output current for too long. On VFD-EL-W Delta says the drive can withstand 150% of rated current for at most 60 seconds. On MS300 (normal duty) the drive can sustain 120% of rated output current for 1 minute or 150% for 3 seconds; on heavy duty, 150% for 1 minute or 200% for 3 seconds. Delta's fixes: reduce the load, increase acceleration / deceleration time, correct the V/F curve, or use a larger drive. |
| EoL1 (fault ID 22) | MS300 | Electronic thermal relay 1 protection | — |
| EoL2 (fault ID 23) | MS300 | Electric thermal relay 2 protection | — |
| oH3 (fault ID 24) | MS300 | Motor overheating (PTC / PT100) | — |
| ot1 (fault ID 26) | MS300 | Over torque 1 | — |
| ot2 (fault ID 27) | MS300 | Over torque 2 | — |
| uC (fault ID 28) | MS300 | Under current | — |
| cF2 (fault ID 31) | MS300 | EEPROM read error | — |
| cd1 (fault ID 33) | MS300 | U-phase error | — |
| cd2 (fault ID 34) | MS300 | V-phase error | — |
| cd3 (fault ID 35) | MS300 | W-phase error | — |
| Hd0 (fault ID 36) | MS300 | cc hardware failure | — |
| Hd1 (fault ID 37) | MS300 | oc hardware error | — |
| AUE (fault ID 40) | MS300 | Auto-tuning error | — |
| AFE (fault ID 41) | MS300 | PID loss ACI | — |
| PGF2 (fault ID 43) | MS300 | PG feedback loss | — |
| PGF3 (fault ID 44) | MS300 | PG feedback stall | — |
| PGF4 (fault ID 45) | MS300 | PG slip error | — |
| ACE (fault ID 48) | MS300 | ACI loss | — |
| EF (fault ID 49) | MS300 | External fault | — |
| EF1 (fault ID 50) | MS300 | Emergency stop | — |
| bb (fault ID 51) | MS300 | External base block | — |
| Pcod (fault ID 52) | MS300 | Password is locked | — |
| CE1 (fault ID 54) | MS300 | Illegal command | — |
| CE2 (fault ID 55) | MS300 | Illegal data address | — |
| CE3 (fault ID 56) | MS300 | Illegal data value | — |
| CE4 (fault ID 57) | MS300 | Data is written to read-only address | — |
| CE10 (fault ID 58) | MS300 | Modbus transmission time-out | — |
| ydc (fault ID 61) | MS300 | Y-connection / Δ-connection switch fault | — |
| dEb (fault ID 62) | MS300 | Deceleration energy backup fault | — |
| oSL (fault ID 63) | MS300 | Over slip error | — |
| SdRv (fault ID 68) | MS300 | Reverse direction of the speed feedback | — |
| SdOr (fault ID 69) | MS300 | Over speed rotation feedback | — |
| SdDe (fault ID 70) | MS300 | Large deviation of speed feedback | — |
| STL1 (fault ID 72) | MS300 | STO loss 1 | — |
| STO (fault ID 76) | MS300 | STO | — |
| STL2 (fault ID 77) | MS300 | STO loss 2 | — |
| STL3 (fault ID 78) | MS300 | STO loss 3 | — |
| Aoc (fault ID 79) | MS300 | U-phase over-current before run | — |
| boc (fault ID 80) | MS300 | V-phase over-current before run | — |
| coc (fault ID 81) | MS300 | W-phase over-current before run | — |
| OPHL (fault ID 82) | MS300 | Output phase loss U phase | — |
| OPHL (fault ID 83) | MS300 | Output phase loss V phase | — |
| OPHL (fault ID 84) | MS300 | Output phase loss W phase | — |
| oL3 (fault ID 87) | MS300 | Overload protection at low frequency | — |
| RoPd (fault ID 89) | MS300 | Rotor position detection error | — |
| CGdE (fault ID 101) | MS300 | CANopen guarding fault | — |
| CHbE (fault ID 102) | MS300 | CANopen heartbeat fault | — |
| CbFE (fault ID 104) | MS300 | CANopen bus off fault | — |
| CIdE (fault ID 105) | MS300 | CANopen index error | — |
| CAdE (fault ID 106) | MS300 | CANopen station address error | — |
| CFrE (fault ID 107) | MS300 | CANopen memory error | — |
| CP20 (fault ID 121) | MS300 | Internal communication error | — |
| CP22 (fault ID 123) | MS300 | Internal communication error | — |
| CP30 (fault ID 124) | MS300 | Internal communication error | — |
| CP32 (fault ID 126) | MS300 | Internal communication error | — |
| CP33 (fault ID 127) | MS300 | Internal communication error | — |
| ot3 (fault ID 128) | MS300 | Over-torque 3 | — |
| ot4 (fault ID 129) | MS300 | Over-torque 4 | — |
| EoL3 (fault ID 134) | MS300 | Internal communication error | — |
| EoL4 (fault ID 135) | MS300 | Internal communication error | — |
| Hd6 (fault ID 140) | MS300 | oc hardware error | — |
| b4GFF (fault ID 141) | MS300 | GFF occurs before run | — |
| AuE1 (fault ID 142) | MS300 | Auto-tune error 1 | — |
| AuE2 (fault ID 143) | MS300 | Auto-tune error 2 | — |
| AuE3 (fault ID 144) | MS300 | Auto-tune error 3 | — |
| AuE5 (fault ID 149) | MS300 | Auto-tune error 5 | — |
| oc (fault ID 1) | VFD-EL-W | Over-current: abnormal increase in current | — |
| ov (fault ID 2) | VFD-EL-W | Over-voltage: DC bus voltage exceeds its maximum allowable value | — |
| oH1 (fault ID 3) | VFD-EL-W | Overheating: heat sink temperature too high · full fix | oH1 on a Delta AC drive means overheating. On the MS300 it is IGBT overheating: the IGBT temperature went over the protection level and the drive stopped. On VFD-EL-W it means the heat sink temperature is too high. Delta's causes: high ambient or cabinet temperature, blocked ventilation, an obstructed heat sink or a cooling fan that is not running, too little space around the drive, too heavy a load, or running at 100% or more of rated output for a long time. |
| Lv (fault ID 4) | VFD-EL-W | Low voltage: DC bus voltage below its minimum value · full fix | Lv on a Delta AC drive means low voltage: the drive detected that the DC bus voltage fell below its minimum value. VFD-EL-W and VFD-M show Lv. The MS300 shows LvA (during acceleration), Lvd (deceleration), Lvn (constant speed) or LvS (at stop), each when the DC bus is lower than Pr.06-00. Delta's causes are a power cut, supply voltage changes, a wrong drive model for the supply, starting a large motor on the same supply, or (MS300) a missing short circuit plate or DC reactor between +1 and +2. |
| oL (fault ID 5) | VFD-EL-W | Overload: excessive drive output current (150% for 60 s max) · full fix | oL on a Delta AC drive means overload: the drive detected excessive output current for too long. On VFD-EL-W Delta says the drive can withstand 150% of rated current for at most 60 seconds. On MS300 (normal duty) the drive can sustain 120% of rated output current for 1 minute or 150% for 3 seconds; on heavy duty, 150% for 1 minute or 200% for 3 seconds. Delta's fixes: reduce the load, increase acceleration / deceleration time, correct the V/F curve, or use a larger drive. |
| oL1 (fault ID 6) | VFD-EL-W | Overload 1: internal electronic overload trip | — |
| oL2 (fault ID 7) | VFD-EL-W | Overload 2: motor overload | — |
| EF (fault ID 8) | VFD-EL-W | External fault (MI terminal set to external fault, or address 2002H bit0 = 1) | — |
| ocA (fault ID 9) | VFD-EL-W | Over-current during acceleration · full fix | ocA on a Delta AC drive means over-current during acceleration. On the MS300, Delta says output current went above three times the rated current while the motor was speeding up, so the drive shut off its output at once and the motor coasted. The first corrective actions Delta lists are a longer acceleration time (or S-curve), auto-acceleration (Pr.01-44) and over-current stall prevention (Pr.06-03). Delta also lists short circuits in the motor cable, poor motor insulation and too large a load. |
| ocd (fault ID 10) | VFD-EL-W | Over-current during deceleration | — |
| ocn (fault ID 11) | VFD-EL-W | Over-current during constant speed operation · full fix | ocn on a Delta AC drive means over-current while running at constant speed. On the MS300, Delta says output current went above three times the rated current, so the drive shut off its output at once and the motor coasted. Delta's causes include a short circuit in the motor cable, a locked motor shaft, poor motor insulation, a sudden change in load, and a motor larger than the drive. VFD-EL-W calls it over-current during constant speed operation and VFD-M calls it OCn. |
| PHL (fault ID 14) | VFD-EL-W | Phase loss: check the input power is three-phase | — |
| cFA (fault ID 16) | VFD-EL-W | Auto acceleration / deceleration failure | — |
| codE (fault ID 17) | VFD-EL-W | Software protection failure: password locked | — |
| cF1.0 (fault ID 18) | VFD-EL-W | Internal EEPROM cannot be programmed (return to factory) | — |
| cF2.0 (fault ID 19) | VFD-EL-W | Internal EEPROM cannot be read | — |
| HPF1 (fault ID 20) | VFD-EL-W | CC (current clamp); return the unit to the factory | — |
| HPF2 (fault ID 21) | VFD-EL-W | OV hardware fault (return to factory) | — |
| HPF4 (fault ID 23) | VFD-EL-W | OC hardware fault (return to factory) | — |
| cF3.0 (fault ID 24) | VFD-EL-W | Wiring detection fault: U-phase error (return to factory) | — |
| cF3.1 (fault ID 25) | VFD-EL-W | Wiring detection fault: V-phase error (return to factory) | — |
| cF3.2 (fault ID 26) | VFD-EL-W | Wiring detection fault: W-phase error (return to factory) | — |
| cF3.3 (fault ID 27) | VFD-EL-W | Wiring detection fault: DC bus wiring detection error (return to factory) | — |
| cF3.4 (fault ID 28) | VFD-EL-W | Wiring detection fault: temperature sensor error (return to factory) | — |
| AErr (fault ID 32) | VFD-EL-W | Analog signal error: check if ACI wiring is broken | — |
| PTC1 (fault ID 34) | VFD-EL-W | Motor internal temperature too high (PTC); motor coasts to stop | — |
| FbE (fault ID 35) | VFD-EL-W | PID feedback signal fault | — |
| dEv (fault ID 36) | VFD-EL-W | Unusual PID feedback | — |
| oPHL (fault ID 37) | VFD-EL-W | Multi-motor fault protection: check motor wiring | — |
| HotP (fault ID 38) | VFD-EL-W | Thermal cutout triggered | — |
| bb | VFD-EL-W | External base block: drive stops output while B.B. input is active | — |
| cE-- | VFD-EL-W | Communication fault: check RJ45 wiring and protocol settings | — |
| oc (Pr.73 record 01) | VFD-M | Over-current | — |
| ov (Pr.73 record 02) | VFD-M | Over-voltage | — |
| oH (Pr.73 record 03) | VFD-M | Overheat | — |
| oL (Pr.73 record 04) | VFD-M | Overload · full fix | oL on a Delta AC drive means overload: the drive detected excessive output current for too long. On VFD-EL-W Delta says the drive can withstand 150% of rated current for at most 60 seconds. On MS300 (normal duty) the drive can sustain 120% of rated output current for 1 minute or 150% for 3 seconds; on heavy duty, 150% for 1 minute or 200% for 3 seconds. Delta's fixes: reduce the load, increase acceleration / deceleration time, correct the V/F curve, or use a larger drive. |
| oL1 (Pr.73 record 05) | VFD-M | Overload 1 | — |
| EF (Pr.73 record 06) | VFD-M | External fault | — |
| CF1 (Pr.73 record 07) | VFD-M | CPU failure 1 | — |
| CF3 (Pr.73 record 08) | VFD-M | CPU failure 3 | — |
| HPF (Pr.73 record 09) | VFD-M | Hardware protection failure | — |
| OCA (Pr.73 record 10) | VFD-M | Over-current during acceleration · full fix | ocA on a Delta AC drive means over-current during acceleration. On the MS300, Delta says output current went above three times the rated current while the motor was speeding up, so the drive shut off its output at once and the motor coasted. The first corrective actions Delta lists are a longer acceleration time (or S-curve), auto-acceleration (Pr.01-44) and over-current stall prevention (Pr.06-03). Delta also lists short circuits in the motor cable, poor motor insulation and too large a load. |
| OCd (Pr.73 record 11) | VFD-M | Over-current during deceleration | — |
| OCn (Pr.73 record 12) | VFD-M | Over-current during steady state operation · full fix | ocn on a Delta AC drive means over-current while running at constant speed. On the MS300, Delta says output current went above three times the rated current, so the drive shut off its output at once and the motor coasted. Delta's causes include a short circuit in the motor cable, a locked motor shaft, poor motor insulation, a sudden change in load, and a motor larger than the drive. VFD-EL-W calls it over-current during constant speed operation and VFD-M calls it OCn. |
| GFF (Pr.73 record 13) | VFD-M | Ground fault or fuse failure · full fix | GFF on a Delta AC drive means ground fault. On the MS300, Delta says the drive detected a short circuit to ground on the output terminals (U/V/W), so it shut off the output and the motor coasted. Causes: burnt or aged motor insulation, a broken cable, high stray capacitance on long motor cables, interference, or a hardware failure. VFD-M calls it ground fault or fuse failure. This is electrical work for an electrician. |
| CF2 (Pr.73 record 16) | VFD-M | CPU failure | — |
| bb (Pr.73 record 17) | VFD-M | External base block | — |
| oL2 (Pr.73 record 18) | VFD-M | Overload 2 | — |
| cFA (Pr.73 record 19) | VFD-M | Auto adjustable accel/decel failure | — |
| codE (Pr.73 record 20) | VFD-M | Software protection code | — |
| Lv (Pr.73 record 14 (not recorded)) | VFD-M | Low voltage · full fix | Lv on a Delta AC drive means low voltage: the drive detected that the DC bus voltage fell below its minimum value. VFD-EL-W and VFD-M show Lv. The MS300 shows LvA (during acceleration), Lvd (deceleration), Lvn (constant speed) or LvS (at stop), each when the DC bus is lower than Pr.06-00. Delta's causes are a power cut, supply voltage changes, a wrong drive model for the supply, starting a large motor on the same supply, or (MS300) a missing short circuit plate or DC reactor between +1 and +2. |
Good to know
- Reset on VFD-EL-W and VFD-M: press the RESET (STOP/RESET) key on the keypad, set a multi-function input terminal to RESET and switch it ON, or send a RESET command by communication.
- Most MS300 faults reset manually, and many only 5 seconds after the fault is cleared (for example ocA, ocd, ocn, GFF, oL). Over-voltage faults reset only when the DC bus voltage drops below 90% of the trip level.
- VFD-M: the three most recent faults are stored in Pr.73 to Pr.75. Delta says to wait 5 seconds after a fault has been cleared before resetting.
- Delta's manuals tell you to return the drive to the factory for hardware faults such as HPF, cF3.x, Hd0/Hd1 and cd1–cd3.
हिंदी में
Delta VFD (AC ड्राइव) के फ़ॉल्ट कोड Delta के अपने मैनुअल से: oc मतलब ज़्यादा करंट, ov मतलब DC बस वोल्टेज ज़्यादा, Lv मतलब वोल्टेज कम, oH1 मतलब ड्राइव गरम, oL मतलब ओवरलोड, GFF मतलब अर्थ (ग्राउंड) फ़ॉल्ट।
- ड्राइव की नेमप्लेट पर सीरीज़ देखें (MS300, VFD-EL-W, VFD-M)।
- कोड का मतलब नीचे उसी सीरीज़ की लाइन में देखें।
- वायरिंग या मोटर का काम सिर्फ़ इलेक्ट्रीशियन करे। बिजली बंद करने के बाद भी कैपेसिटर में खतरनाक वोल्टेज रहता है, 25 VDC से कम होने तक न छुएं।
- कारण ठीक करने के बाद RUN बंद करके RESET दबाएं।
Questions people ask
What is ocA fault in a Delta VFD?
Over-current during acceleration. On MS300, Delta says it trips when output current exceeds 3 times the rated current while accelerating. The first fix Delta lists is a longer acceleration time; it also lists motor cable short circuits, poor motor insulation and too large a load.
What is ovd in a Delta VFD?
Over-voltage during deceleration on MS300: the DC bus voltage went above the trip level (410 VDC on 230V models, 820 VDC on 460V models) while slowing down. Delta's first fixes are a longer deceleration time or a brake resistor / braking unit.
What is GFF fault in a Delta drive?
Ground fault: the drive detected a short circuit to ground on the output terminals (U/V/W). Delta says to check motor insulation with a megger and check the cable.
How do I reset a Delta VFD fault?
Fix the cause, make sure the RUN command is OFF, then press RESET on the keypad, use a terminal set to RESET, or send a RESET command by communication.
Sources
- Delta MS300 Series User Manual (2026-04): Chapter 14 Fault Codes, pp.547–581
- Delta VFD-EL-W Series User Manual (2024-09): 6-1 Fault Code Information, pp.6-3 to 6-7
- Delta VFD-M User Manual (Aug 2015): Pr.73 fault record list pp.4-52 to 4-53, error code list p.4-69, Chapter 6 Fault Code Information
- Delta Download Center (Industrial Automation)
Last checked: