Delta VFD GFF Fault: Ground Fault on Motor Output

Quick answer

GFF on a Delta AC drive means ground fault. On the MS300, Delta says the drive detected a short circuit to ground on the output terminals (U/V/W), so it shut off the output and the motor coasted. Causes: burnt or aged motor insulation, a broken cable, high stray capacitance on long motor cables, interference, or a hardware failure. VFD-M calls it ground fault or fuse failure. This is electrical work for an electrician.

Safety: Only a qualified electrician should work on the drive or motor wiring. Delta's MS300 manual says to switch off the AC input power before any wiring, not to touch internal parts until the POWER LED is off, and to measure the DC bus voltage and wait until it is below 25 VDC, because hazardous voltage can stay in the capacitors after power-off. The VFD-EL-W and VFD-M manuals also say to make sure the RUN command is OFF before you press RESET.

Common causes

  • Burnt motor or aged motor insulation
  • Short circuit because of a broken cable
  • Larger stray capacitance of the cable and terminal
  • Malfunction caused by interference
  • Hardware failure in the drive

Fix it step by step

  1. Switch off and wait until the DC bus voltage is below 25 VDC.
  2. Have an electrician check the motor insulation with a megger and replace the motor if insulation is poor.
  3. Check the motor cable for damage and replace it if needed.
  4. If the motor cable is longer than 100 m, Delta suggests lowering the carrier frequency.
  5. Cycle the power after checking. If GFF still shows, Delta says return the drive to the factory for repair.

Still showing GFF?

  • On MS300, b4GFF (fault ID 141) means a ground fault was found before run.
  • VFD-EL-W has no ground fault code in its fault table.

हिंदी में

Delta VFD में GFF का मतलब है ग्राउंड (अर्थ) फ़ॉल्ट: मोटर की तरफ़ (U/V/W) कहीं तार अर्थ से छू रहा है।

  1. बिजली बंद करें और 25 VDC से कम होने तक रुकें।
  2. इलेक्ट्रीशियन से मोटर इंसुलेशन megger से और केबल चेक कराएं।
  3. केबल 100 m से लंबी हो तो carrier frequency कम करें।
  4. फिर भी GFF आए तो ड्राइव रिपेयर के लिए भेजें।

Questions people ask

Can a long motor cable cause GFF?

Delta lists larger stray capacitance of the cable as a cause, and says to lower the carrier frequency if the motor cable is over 100 m.