Delta VFD ocA Fault: Over-current During Acceleration

Quick answer

ocA on a Delta AC drive means over-current during acceleration. On the MS300, Delta says output current went above three times the rated current while the motor was speeding up, so the drive shut off its output at once and the motor coasted. The first corrective actions Delta lists are a longer acceleration time (or S-curve), auto-acceleration (Pr.01-44) and over-current stall prevention (Pr.06-03). Delta also lists short circuits in the motor cable, poor motor insulation and too large a load.

Safety: Only a qualified electrician should work on the drive or motor wiring. Delta's MS300 manual says to switch off the AC input power before any wiring, not to touch internal parts until the POWER LED is off, and to measure the DC bus voltage and wait until it is below 25 VDC, because hazardous voltage can stay in the capacitors after power-off. The VFD-EL-W and VFD-M manuals also say to make sure the RUN command is OFF before you press RESET.

Common causes

  • Acceleration time is too short
  • Short circuit at the motor output because of poor cable insulation
  • Burnt or aged motor insulation
  • Load is too large, or changes suddenly
  • Motor is larger than the drive
  • A contactor on the drive output (U/V/W) switching while the drive is running
  • V/F curve or torque compensation set too high
  • Motor cable too long
  • Hardware failure (short circuit or ground fault at the drive output)

Fix it step by step

  1. Note the code and check the series on the nameplate.
  2. Increase the acceleration time (MS300: Pr.01-12 and related; VFD-EL-W: Acceleration Time). Delta also suggests a longer S-curve, auto-acceleration (Pr.01-44) and over-current stall prevention (Pr.06-03) on MS300.
  3. Have an electrician check the motor cable for short circuits and the motor insulation with a megger, with the power off.
  4. Check the motor rated current is not higher than the drive rated current, and that the load is within the drive rating.
  5. Wait 5 seconds after the fault is cleared, make sure RUN is OFF, then press RESET.

Still showing ocA?

  • Delta's MS300 manual says that if the short-circuit check finds a short at the drive output terminals, return the drive to the factory for repair.
  • VFD-EL-W lists ocA as fault ID 9; VFD-M lists it as OCA (Pr.73 record 10).
  • The 300% trip level is from the MS300 manual. The VFD-M error code list (p.4-69) describes ocA, ocd and ocn as output current exceeding 2 times the rated current.

हिंदी में

Delta VFD में ocA का मतलब है मोटर तेज़ होते समय (acceleration) करंट बहुत ज़्यादा हो गया। MS300 में यह रेटेड करंट के 3 गुना पर ट्रिप होता है।

  1. Acceleration time बढ़ाएं।
  2. बिजली बंद करके इलेक्ट्रीशियन से मोटर केबल और मोटर इंसुलेशन (megger) चेक कराएं।
  3. लोड और मोटर ड्राइव की क्षमता से ज़्यादा न हों।
  4. RUN बंद करके RESET दबाएं।

Questions people ask

What is the difference between ocA, ocd and ocn?

All three are over-current faults. ocA happens while accelerating, ocd while decelerating, and ocn at constant speed.

Can ocA come from a bad motor?

Yes. Delta lists burnt or aged motor insulation and short circuits in the motor cable as causes.