Solar Pump error codes by brand
Pick your brand to see the solar pump codes we cover, what each one means, and what you can safely check yourself. Each code links back to the brand's own manual or support page.
अपना ब्रांड चुनें और डिस्प्ले पर दिख रहे कोड का मतलब और हल देखें।
- A code is showingPick your brand below, then find your code.डिस्प्ले पर कोड दिख रहा है
- Only a light is blinkingHow to read the code on each brand.सिर्फ लाइट ब्लिंक हो रही है
Pick your brand ब्रांड चुनें
INVT solar pump codes at a glance
All INVT Goodrive100-PV solar pump inverter fault and alarm codes from INVT's own manual: PVLV, PVOV, PINV, A-LS weak light, A-LL no water, OC, OV, UV, SPO and more, with causes.
INVT GD100-PV सोलर पंप इन्वर्टर के फ़ॉल्ट कोड INVT के मैनुअल से। A- से शुरू होने वाले कोड (A-LS कम धूप, A-LL पानी नहीं, A-tF टंकी भरी, A-tL पानी खाली) अलार्म हैं: धूप या पानी आने पर पंप खुद चल जाता है। PVLV मतलब पैनल का वोल्टेज कम, PVOV मतलब ज़्यादा, PINV मतलब पैनल की तार उल्टी लगी।
| Code | Model type | Meaning |
|---|---|---|
| OUt1 | GD100-PV | Inverter unit U-phase protection |
| OUt2 | GD100-PV | Inverter unit V-phase protection |
| OUt3 | GD100-PV | Inverter unit W-phase protection |
| OV1 | GD100-PV | Overvoltage during acceleration |
| OV2 | GD100-PV | Overvoltage during deceleration |
| OV3 | GD100-PV | Overvoltage during constant speed running |
| OC1 | GD100-PV | Overcurrent during acceleration |
| OC2 | GD100-PV | Overcurrent during deceleration |
| OC3 | GD100-PV | Overcurrent during constant speed running |
| UV | GD100-PV | Bus undervoltage |
| OL1 | GD100-PV | Motor overload |
| OL2 | GD100-PV | Inverter overload |
| SPI | GD100-PV | Phase loss on the input side |
| SPO | GD100-PV | Phase loss on the output side |
| OH1 | GD100-PV | Rectifier module overheating (P07 list: boost module overheat) |
| OH2 | GD100-PV | Inverter module overheat |
| EF | GD100-PV | External fault |
| CE | GD100-PV | RS485 communication fault |
| ItE | GD100-PV | Current detection fault |
| tE | GD100-PV | Motor autotuning fault |
Shakti solar pump codes at a glance
What Shakti solar pump drive and controller fault codes mean, from Shakti's own installation manuals: 01 Low Power, 02 DC Bus Under Voltage, 05 Dry Run, 06 Over Temp, 08 Short Circuit, 11 PMSM Start Fail and the Kalpavriksha USPC codes, with what to check.
Shakti सोलर पंप ड्राइव की LCD पर नंबर और संदेश आता है, जैसे 05 DRY RUN DETECTED। Nandi, Lotus और Simha Plus में 01 से 12 तक एक ही टेबल है; Kalpavriksha USPC के नंबर अलग हैं। 01 LOW POWER खराबी नहीं, चेतावनी है: पैनल से बिजली कम आ रही है (अक्सर धूप कम होने से)।
| Code | Model type | Meaning |
|---|---|---|
| 01 | Nandi, Lotus, Simha Plus solar drives | Low power: input power is low because of weak sunlight or shadow on the panels, panels not in healthy condition, or solar power below the minimum PV power setting. Lotus and Simha Plus mark this as a warning, not a fault. |
| 02 | Nandi, Lotus, Simha Plus solar drives | DC bus under voltage: low input power (weak sunlight or shadow on panels), panels not in healthy condition, or a sudden high power draw by the motor because the pump or motor is jammed |
| 03 | Nandi, Lotus, Simha Plus solar drives | DC bus over voltage: the DC bus voltage in the drive is more than the set voltage |
| 04 | Nandi, Lotus, Simha Plus solar drives | Output over voltage: the output side voltage is high when the drive is off |
| 05 | Nandi, Lotus, Simha Plus solar drives | Dry run: no water on the suction / inlet side of the pump |
| 06 | Nandi, Lotus, Simha Plus solar drives | Over temperature: the drive is heating more than expected, or ventilation is poor |
| 07 | Nandi, Lotus, Simha Plus solar drives | Over current at output: the output current (RMS) is more than the value set in the drive's factory setup. Causes: wrong rated current set, or the connected load does not match the selected parameters. |
| 08 | Nandi, Lotus, Simha Plus solar drives | Short circuit trip: an internal or output connection is shorted, the voltage is too low, or there was a sudden load |
| 09 | Nandi, Lotus, Simha Plus solar drives | High inrush current: sudden increase in load, wrong motor selected, or a cable joint not done properly |
| 10 | Nandi, Lotus, Simha Plus solar drives | Output open circuit: one of the outputs opened while running |
| 11 | Nandi, Lotus, Simha Plus solar drives | PMSM start fail: starting torque not enough, or the pump or motor is mechanically jammed |
| 12 | Nandi, Lotus, Simha Plus solar drives | Unbalance fault: one of the three phases is missing |
| 01 | Kalpavriksha USPC, 2022 manual | Low power: input power is less than the set minimum power (weak sunlight or shadow on panels, panels not healthy, or solar power below the minimum PV power setting) |
| 02 | Kalpavriksha USPC, 2022 manual | DC bus over voltage: the DC bus voltage is more than the set voltage |
| 05 | Kalpavriksha USPC, 2022 manual | Dry run: no water on the suction / inlet side of the pump |
| 06 | Kalpavriksha USPC, 2022 manual | Wrong motor: the wrong type of motor is connected, for example an induction motor instead of PMSM, or the other way round |
| 08 | Kalpavriksha USPC, 2022 manual | High inrush current: sudden increase in load, wrong motor selected, or a cable joint not done properly |
| 09 | Kalpavriksha USPC, 2022 manual | Output open circuit: one of the outputs opened while running |
| 18 | Kalpavriksha USPC, 2022 manual | PV over voltage: the average panel (PV) voltage is above 765 V |
| 19 | Kalpavriksha USPC, 2022 manual | PV under voltage: the average panel (PV) voltage is below 150 V |
Can't see the code?
- How to check the error code on your solar pump: steps for each brand
Step-by-step solar pump guides
- INVT A-LL · Pump running dry: no water at the source
- INVT A-LS · Sunlight too weak; pump sleeping
- INVT OC1 · Current too high (start, stop or running)
- INVT OL1 · Pump motor or inverter overloaded
- INVT PVLV · Solar panel input voltage too low
- INVT PVOV · Solar panel input voltage too high
- INVT SPO · One motor phase missing or very unequal
- Shakti 05 · Pump is running without water