Quick answer
PVOV on an INVT Goodrive100-PV solar pump inverter is PV overvoltage: the input voltage from the solar panels is too high. INVT lists two causes: too many panels connected in series, or a -4 model set as another model. The fix is to reduce the number of panels in series, or check and reset the model setting. Both are installer jobs.
What PVOV means
It is fault type 40 in the fault record.
Two causes INVT lists
Too many panels connected in series, which raises the input voltage. Or a -4 model (3-phase 380 V) set as another model in the settings. If PVOV started after new panels were added, INVT's first cause, too many panels in series, is the one the installer should check.
Voltage limits
INVT gives a maximum DC voltage of 440 V for the 220 V models (-SS2, -S2, -2) and 800 V for the -4 models. The recommended DC input range is 200–400 V and 300–750 V.
Installer job
Do not add or move panels yourself; panel strings carry high DC voltage.
Safety: Only a qualified electrician should open the inverter or touch the panel, pump or motor wiring. INVT's manual says to disconnect every supply (solar panel DC input and any grid AC input) and wait at least the time marked on the inverter (5 minutes for most models) or until the DC bus voltage is below 36 V before any wiring or inspection. High voltage is present inside while it runs.
Common causes
- Too many solar panels in series: input voltage too high
- Model -4 is set as another model
Fix it step by step
0 of 3 done
- Do not add or move panels yourself. Panel strings carry high DC voltage.
- Call the installer. INVT says to reduce the number of solar panels in series connection.
- Ask the installer to check and reset the model setting, as INVT advises for a -4 model set as another model.
Still showing PVOV?
- PVOV is fault type 40 in the fault record (P07.27 onward). It is detected in the boost module on models that have one.
- The -4 in the model name means a 3-phase 380 V model. If a -4 inverter is set as another model, INVT says to check and reset the model setting.
हिंदी में
INVT सोलर पंप में PVOV का मतलब है सोलर पैनल का वोल्टेज ज़्यादा है। सीरीज़ में पैनल ज़्यादा हैं या मॉडल सेटिंग गलत है।
- पैनल खुद न हटाएं, इनमें ऊंचा DC वोल्टेज होता है।
- इंस्टॉलर को बुलाएं, वह सीरीज़ में पैनल कम करेगा।
- मॉडल सेटिंग भी इंस्टॉलर चेक करे।
Questions people ask
Why did PVOV start after new panels were added?
INVT's first cause is too many panels in series, which raises the input voltage. The installer should reduce the series count.
What voltage is too high for the GD100-PV?
INVT's specification table gives a maximum DC voltage of 440 V for the 220 V models (-SS2, -S2, -2) and 800 V for the 3-phase 380 V -4 models. The recommended DC input range is 200–400 V and 300–750 V. The model letter is in the model name, for example GD100-2R2G-4-PV.
Did this fix your problem? क्या इससे मदद मिली?
What went wrong?
Thanks. This helps us fix our guides. धन्यवाद!
Sources
Last checked: