हिंदी

INVT Solar Pump A-LS: Weak-Light Alarm (Not a Fault)

Quick answer

A-LS on an INVT Goodrive100-PV solar pump inverter is the weak-light pre-alarm. It is an alarm, not a fault: the sunlight is weak or the solar panel setup is not enough, so the inverter stops the pump and sleeps. INVT says the device runs again automatically when the light is sufficient. By default it reports A-LS after 100 seconds of running at its lowest output (at once if the panel voltage is below 70 V) and tries to run again after the 300-second weak-light wake-up delay (P15.24).

Why it shows in the evening

In weak light, the inverter stops the pump when output stays at its lowest for the weak-light delay, then sleeps until light returns.

Why the pump waits after the sun comes out

After A-LS, the inverter waits the weak-light wake-up delay (P15.24, default 300 seconds) before it clears the alarm and runs again. So allow about 5 minutes. Ask the installer before changing these settings.

A-LS in strong sun?

If A-LS shows in strong midday sun, ask the installer to check whether the panel configuration is enough for the pump, as INVT advises. If P15.32 is set to 0, the inverter switches to grid input in weak light instead of sleeping, on systems wired for it.

Common causes

  • Weak sunlight
  • The solar panel setup is too small for the pump
  • PV voltage below 70 V (reported at once)

Fix it step by step

  1. Wait. INVT says the device runs again automatically when the light is enough.
  2. Allow about 5 minutes: after A-LS is reported, the inverter clears the alarm after the weak-light wake-up delay (P15.24, default 300 seconds) and runs again.
  3. If A-LS shows in strong midday sun, ask the installer to check whether the panel configuration is enough for the pump, as INVT advises.

Still showing A-LS?

  • The timings are settings: weak-light delay P15.23 (default 100 s) and wake-up delay P15.24 (default 300 s). Ask the installer before changing them.

हिंदी में

INVT सोलर पंप में A-LS का मतलब है धूप कम है। यह खराबी नहीं, अलार्म है। पंप रुककर सो जाता है और धूप आने पर खुद चल जाता है।

  1. इंतज़ार करें। धूप आने पर पंप खुद चलेगा।
  2. A-LS आने के बाद पंप लगभग 5 मिनट (डिफ़ॉल्ट देरी) बाद फिर से चलने की कोशिश करता है।
  3. दोपहर की तेज़ धूप में भी A-LS आए तो इंस्टॉलर से पैनल चेक कराएं।

Sources

Last checked:

↑