Quick answer
PVLV on an INVT Goodrive100-PV solar pump inverter is PV undervoltage: the voltage coming from the solar panels is too low for the inverter. INVT lists three causes: the panels in series give too little power, the weather is cloudy or rainy, or the motor's starting current is too high. INVT's fix is to add panels or test again in normal sunlight; if the motor's starting current is the problem, replace the motor.
What PVLV means
It is a fault, not the A-LS weak-light alarm, and is fault type 41 in the fault record.
Three causes, three fixes
Cloudy or rainy weather: PVLV can be normal; INVT says to test again in normal sunlight.
Too few panels in series: if it shows in full sun, INVT says to increase the number of solar panels. Have the installer check the panel count.
Motor starting current too high: if the panels are enough and it still trips at start, INVT's fix is to replace the motor.
Start-up voltage
INVT's specification table gives a start-up voltage of 200 V and a minimum working voltage of 150 V for the 220 V models (-SS2, -S2, -2), and 300 V and 250 V for the 3-phase 380 V -4 models.
Resetting PVLV
INVT's reset is the STOP/RST key, a control terminal or a communication command, after the cause is fixed. If the voltage is still low, the code stays.
Safety: Only a qualified electrician should open the inverter or touch the panel, pump or motor wiring. INVT's manual says to disconnect every supply (solar panel DC input and any grid AC input) and wait at least the time marked on the inverter (5 minutes for most models) or until the DC bus voltage is below 36 V before any wiring or inspection. High voltage is present inside while it runs.
Fix it step by step
0 of 3 done
- Check the weather. In cloud or rain, PVLV can be normal; INVT says to test again in normal sunlight.
- If it shows in full sun, the panel setup may be too small. INVT says to increase the number of solar panels. Have the installer check the panel count against the inverter.
- If the panels are enough and it still trips at start, INVT points to a motor with too high starting current: the fix is to replace the motor. This is installer or electrician work.
Still showing PVLV?
- PVLV is detected in the boost module on models that have one.
- The inverter stores faults as numbers in P07.27 (current fault) and P07.28 onward (previous faults); PVLV is fault type 41. Give this number and the code to your installer.
हिंदी में
INVT सोलर पंप में PVLV का मतलब है सोलर पैनल से आने वाला वोल्टेज कम है। कारण: पैनल कम, बादल या बारिश, या मोटर का स्टार्टिंग करंट ज़्यादा।
- बादल या बारिश में यह आ सकता है। अच्छी धूप में फिर चलाकर देखें।
- तेज़ धूप में भी आए तो इंस्टॉलर से पैनल की संख्या चेक कराएं। INVT पैनल बढ़ाने को कहता है।
- फिर भी आए तो मोटर का स्टार्टिंग करंट ज़्यादा हो सकता है। यह काम इलेक्ट्रीशियन करे।
Questions people ask
PVLV and A-LS: what is the difference?
Both relate to low sunlight. A-LS is an alarm: the pump sleeps and wakes by itself when light returns. PVLV is a fault: PV undervoltage, with too few panels, bad weather or high motor starting current as causes.
Did this fix your problem? क्या इससे मदद मिली?
What went wrong?
Thanks. This helps us fix our guides. धन्यवाद!
Sources
Last checked: