INVT Solar Pump OL1 / OL2 Fault: Motor or Inverter Overload

Quick answer

OL1 on an INVT Goodrive100-PV solar pump inverter is motor overload and OL2 is inverter overload. For OL1, INVT lists grid voltage too low, a wrongly set motor rated current, or a stalled motor or a violently changing load. For OL2, INVT lists acceleration too fast, resetting a motor that is still turning, grid voltage too low, a load that is too heavy, or a motor power that is too small.

OL1 or OL2: motor or inverter overload

Both stop the pump. In the fault record, OL1 is fault type 11 and OL2 is fault type 12.

Do not keep restarting

INVT's advice for OL2 is to avoid restarting right after a stop. Do not keep resetting and restarting the pump.

What the installer checks

For OL1: the grid voltage, the motor rated current against the pump nameplate, the load and the torque boost. For OL2: the grid voltage, the ACC time, and whether the inverter and motor are the right size; INVT says to select an inverter with larger power or a proper motor.

Safety: Only a qualified electrician should open the inverter or touch the panel, pump or motor wiring. INVT's manual says to disconnect every supply (solar panel DC input and any grid AC input) and wait at least the time marked on the inverter (5 minutes for most models) or until the DC bus voltage is below 36 V before any wiring or inspection. High voltage is present inside while it runs.

Common causes

  • OL1: grid voltage too low
  • OL1: motor rated current set wrong
  • OL1: motor stalled or load jumps violently
  • OL2: acceleration too fast
  • OL2: a rotating motor was reset
  • OL2: grid voltage too low
  • OL2: load too heavy
  • OL2: motor power too small

Fix it step by step

  1. Do not keep resetting and restarting the pump. INVT's advice for OL2 is to avoid restarting right after a stop.
  2. OL1: ask the installer to check the grid voltage, reset the motor rated current to the pump nameplate, and check the load and adjust torque boost, as INVT advises.
  3. OL2: ask the installer to check the grid voltage, increase the ACC time, and check whether the inverter and motor are the right size; INVT says to select an inverter with larger power or a proper motor.

Still showing OL1?

  • OL3 is electronic overload: the overload pre-alarm threshold was reached. Check the load and the threshold.

हिंदी में

INVT सोलर पंप में OL1 मतलब मोटर ओवरलोड, OL2 मतलब इन्वर्टर ओवरलोड।

  1. बार-बार रीसेट करके चालू न करें। रुकने के तुरंत बाद दोबारा चालू न करें।
  2. OL1: इंस्टॉलर ग्रिड वोल्टेज चेक करे, मोटर का करंट नेमप्लेट से सेट करे और लोड चेक करे।
  3. OL2: इंस्टॉलर ग्रिड वोल्टेज, ACC टाइम और इन्वर्टर का साइज़ चेक करे।

Questions people ask

OL1 or OL2: which is worse?

Both stop the pump. OL1 is motor overload (grid voltage, motor current setting, stalled or jumping load); OL2 is inverter overload (fast acceleration, restarting a turning motor, low grid voltage, heavy load, or the inverter or motor not the right size).

How are OL1 and OL2 stored in the fault record?

As numbers in P07.27 (current fault) and P07.28 onward (previous faults): OL1 is fault type 11 and OL2 is fault type 12.