Shakti Solar Pump Error Codes: 01 Low Power, 05 Dry Run, 08 Short Circuit and More (Nandi, Lotus, Simha Plus, Kalpavriksha)

By FaultDecode · Checked against Shakti's official documents · Updated · How we check

29 Shakti codes on this page.

Shakti solar pump drives show a two-digit fault number and a message on the LCD, for example 05 DRY RUN DETECTED. On Nandi, Lotus and Simha Plus, when a fault is detected the drive cuts its output and the motor slows down and stops. The numbers are not the same on every Shakti controller: Nandi, Lotus and Simha Plus solar drives share one table (01 to 12), while the Kalpavriksha Universal Solar Pump Controller (USPC) uses a different list (for example 06 is Over Temperature on Nandi but Wrong Motor on Kalpavriksha). Check the controller's name on the controller or its label, then read the rows for it. Every row here is from Shakti's own manuals on shaktipumps.com.

Safety: A solar pump drive works with high DC voltage from the panels, and the motor side is three-phase. For short circuit, over voltage, unbalance or over temperature codes, switch off and call the installer, an electrician or Shakti customer care. Many of Shakti's fixes are parameter or wiring changes (rated current, torque boost, panels in series): leave these to the installer. Do not open the drive.

How to see the code

  1. Read the LCD on the drive: it shows a number and a message, for example 01 LOW POWER or 05 DRY RUN DETECTED.
  2. Note the controller name (Nandi, Lotus, Simha Plus or Kalpavriksha USPC), because the same number can mean different things.
  3. With remote monitoring, Shakti says the motor will not turn on and the fault status can be seen in the menu under fault report (Lotus, Simha Plus).
  4. Match the number and controller in the table below.

How to check the error code on other solar pump brands

Shakti solar pump error code list

CodeModel typeMeaningWhat to do
01 (shown as 01 LOW POWER; a warning, not a fault (Lotus, Simha Plus footnote)) Nandi, Lotus, Simha Plus solar drives Low power: input power is low because of weak sunlight or shadow on the panels, panels not in healthy condition, or solar power below the minimum PV power setting. Lotus and Simha Plus mark this as a warning, not a fault. Check whether sunlight is weak; if so, wait for proper sunlight. The Lotus and Simha Plus manuals also say to check dust on the panels and the direction of the panels. The installer can lower the minimum input power setting.
02 (shown as 02 DC BUS UNDER VOLTAGE) Nandi, Lotus, Simha Plus solar drives DC bus under voltage: low input power (weak sunlight or shadow on panels), panels not in healthy condition, or a sudden high power draw by the motor because the pump or motor is jammed Check whether sunlight is weak and wait for proper sunlight. The Lotus and Simha Plus manuals also say to check dust on the panels and their direction. If the pump or motor may be jammed, the installer should check and clean the motor pump set. The installer can also lower the minimum input power setting.
03 (shown as 03 DC BUS OVER VOLTAGE) Nandi, Lotus, Simha Plus solar drives DC bus over voltage: the DC bus voltage in the drive is more than the set voltage The installer should check the number of PV panels connected in series and make sure the voltage is below the limit in the drive's specification sheet. Contact Shakti customer care.
04 (shown as 04 OUTPUT OVER VOLTAGE) Nandi, Lotus, Simha Plus solar drives Output over voltage: the output side voltage is high when the drive is off The installer should check that the input is connected at the right place. Shakti's troubleshooting also lists hardware failure: contact customer care.
05 (shown as 05 DRY RUN DETECTED) Nandi, Lotus, Simha Plus solar drives Dry run: no water on the suction / inlet side of the pump · full fix Check that water is available at the pump inlet. For a submersible pump, wait for water to come in. For a surface pump, check the water level in the tank and do the priming properly.
06 (shown as 06 OVER TEMP PROTECTED) Nandi, Lotus, Simha Plus solar drives Over temperature: the drive is heating more than expected, or ventilation is poor Check the ventilation around the drive and how it is mounted. If it keeps coming, contact Shakti customer care. Do not open the drive.
07 (shown as 07 OVER CURRENT DETECTED) Nandi, Lotus, Simha Plus solar drives Over current at output: the output current (RMS) is more than the value set in the drive's factory setup. Causes: wrong rated current set, or the connected load does not match the selected parameters. The installer should set the right rated current and check the connected load. Contact Shakti customer care.
08 (shown as 08 SHORT CIRCUIT TRIP) Nandi, Lotus, Simha Plus solar drives Short circuit trip: an internal or output connection is shorted, the voltage is too low, or there was a sudden load Switch off. An electrician or installer should find and correct the shorted connection and check the cable insulation (Lotus and Simha Plus manuals: run the drive with the motor disconnected; if it runs, check the motor wires, cable and the motor's megger reading). Contact Shakti customer care.
09 (shown as 09 HIGH INRUSH CURRENT) Nandi, Lotus, Simha Plus solar drives High inrush current: sudden increase in load, wrong motor selected, or a cable joint not done properly The installer should select the correct motor in the menu and make a proper cable joint. Contact Shakti customer care.
10 (shown as 10 OUTPUT OPEN CIRCUIT) Nandi, Lotus, Simha Plus solar drives Output open circuit: one of the outputs opened while running Check that the motor is connected at the drive's output (installer or electrician).
11 (shown as 11 PMSM START FAIL) Nandi, Lotus, Simha Plus solar drives PMSM start fail: starting torque not enough, or the pump or motor is mechanically jammed The installer can increase the torque boost % and INIT_RAMP_TIME_PMSM parameters, and check the pump for a jam.
12 (shown as 12 UNBALANCE FAULT) Nandi, Lotus, Simha Plus solar drives Unbalance fault: one of the three phases is missing An electrician or installer should check all three phase connections. Contact Shakti customer care.
01 (shown as 01 LOW POWER) Kalpavriksha USPC, 2022 manual Low power: input power is less than the set minimum power (weak sunlight or shadow on panels, panels not healthy, or solar power below the minimum PV power setting) Check whether sunlight is weak; if so, wait for proper sunlight. The installer can lower the minimum input power setting.
02 (shown as 02 DC BUS OVERVOLTAGE) Kalpavriksha USPC, 2022 manual DC bus over voltage: the DC bus voltage is more than the set voltage The installer should check the number of PV panels in series and keep the voltage below the specification. Contact Shakti customer care.
05 (shown as 05 DRY RUN DETECTED) Kalpavriksha USPC, 2022 manual Dry run: no water on the suction / inlet side of the pump · full fix Check that water is available at the pump inlet. For a submersible pump, wait for water to come in. For a surface pump, check the tank water level and do the priming properly.
06 (shown as 06 WRONG MOTOR) Kalpavriksha USPC, 2022 manual Wrong motor: the wrong type of motor is connected, for example an induction motor instead of PMSM, or the other way round The installer should connect the correct motor and change the setting to match it.
08 (shown as 08 VFD HIGH INRUSH CURRENT) Kalpavriksha USPC, 2022 manual High inrush current: sudden increase in load, wrong motor selected, or a cable joint not done properly The installer should select the correct motor in the menu and make a proper cable joint. Contact Shakti customer care.
09 (shown as 09 OUTPUT OPEN CIRCUIT) Kalpavriksha USPC, 2022 manual Output open circuit: one of the outputs opened while running Check that the motor is connected at the output (installer or electrician).
18 (shown as 18 PV OVER VOLTAGE) Kalpavriksha USPC, 2022 manual PV over voltage: the average panel (PV) voltage is above 765 V The installer should reduce the PV string voltage.
19 (shown as 19 PV UNDER VOLTAGE) Kalpavriksha USPC, 2022 manual PV under voltage: the average panel (PV) voltage is below 150 V Wait for enough sunshine. If it happens in good sun, the installer should increase the PV string voltage.
20 (shown as 20 USPC OVER TEMP) Kalpavriksha USPC, 2022 manual Controller over temperature: the controller is heating more than expected, or ventilation is poor Check the ventilation and mounting. If it keeps coming, contact Shakti customer care. Do not open the controller.
24 (shown as 24 PEAK TORQUE OVERLOAD) Kalpavriksha USPC, 2022 manual Peak torque overload: the load torque is above 150% Remove the extra load. The installer should select the correct motor in the menu and check the cable joints.
25 (shown as 25 USPC FREQUENCY HIGH) Kalpavriksha USPC, 2022 manual Output frequency higher than the permissible (settable) range The installer should check the connections, the over-frequency limit and rated frequency settings, and the connected load. Contact Shakti customer care.
26 (shown as 26 USPC FREQUENCY LOW) Kalpavriksha USPC, 2022 manual Output frequency lower than the permissible (settable) range The installer should check the connections, the under-frequency limit and rated frequency settings, and the connected load. Contact Shakti customer care.
27 (shown as 27 USPC SHORT CIRCUIT) Kalpavriksha USPC, 2022 manual Short circuit: an internal or output connection is shorted, the voltage is too low, or there was a sudden load Switch off. An electrician or installer should correct the shorted connection and check the cable insulation. Contact Shakti customer care.
28 (shown as 28 USPC VOLTAGE HIGH) Kalpavriksha USPC, 2022 manual Output voltage high: 4% above rated voltage, or the input is connected to the output The installer should check the connections and the connected load. Contact Shakti customer care.
29 (shown as 29 USPC VOLTAGE LOW) Kalpavriksha USPC, 2022 manual Output voltage lower than the permissible (settable) range Remove extra load. The installer should check the connections and the under-voltage limit setting. Contact Shakti customer care.
31 (shown as 31 OVER CURRENT) Kalpavriksha USPC, 2022 manual Over current: output current is above the over-current value set in the display The installer should check the over-current setting. Contact Shakti customer care.
32 (shown as 32 START FAIL PMSM) Kalpavriksha USPC, 2022 manual PMSM start fail: starting torque not enough, or the pump or motor is jammed The installer can increase the torque boost % and INIT_RAMP_TIME_PMSM parameters, and check the pump for a jam.

Good to know

हिंदी में

Shakti सोलर पंप ड्राइव की LCD पर नंबर और संदेश आता है, जैसे 05 DRY RUN DETECTED। Nandi, Lotus और Simha Plus में 01 से 12 तक एक ही टेबल है; Kalpavriksha USPC के नंबर अलग हैं। 01 LOW POWER खराबी नहीं, चेतावनी है: पैनल से बिजली कम आ रही है (अक्सर धूप कम होने से)।

  1. LCD पर नंबर और संदेश पढ़ें, और कंट्रोलर का नाम देखें।
  2. 01 LOW POWER या 02 DC BUS UNDER VOLTAGE (Kalpavriksha में 19 PV UNDER VOLTAGE): धूप अच्छी होने का इंतज़ार करें, पैनल पर धूल और पैनल की दिशा देखें।
  3. 05 DRY RUN: पंप तक पानी नहीं पहुंच रहा। सबमर्सिबल में पानी आने का इंतज़ार करें; सरफ़ेस पंप में टंकी का पानी देखें और ठीक से प्राइमिंग करें।
  4. शॉर्ट सर्किट, ओवर वोल्टेज, अनबैलेंस या ज़्यादा गर्म वाला कोड हो तो ड्राइव बंद करें और इंस्टॉलर या Shakti कस्टमर केयर बुलाएं। ड्राइव खुद न खोलें।
  5. सेटिंग (करंट, टॉर्क, पैनल की संख्या) बदलने का काम इंस्टॉलर का है।

Questions people ask

What does 05 Dry Run mean on a Shakti solar pump?

05 DRY RUN DETECTED means there is no water on the suction or inlet side of the pump. Check that water is reaching the pump. For a submersible pump, wait for water to come in; for a surface pump, check the tank level and prime the pump properly.

Is 01 Low Power a fault?

Lotus and Simha Plus mark 01 LOW POWER as a warning, not a fault: the panels are not giving enough power, usually because of weak sunlight or shadow. Wait for proper sunlight and check the panels for dust and direction.

My Shakti solar pump is not working in the morning. Why?

If the display shows 01 LOW POWER or 02 DC BUS UNDER VOLTAGE (Nandi, Lotus, Simha Plus), or 01 LOW POWER or 19 PV UNDER VOLTAGE (Kalpavriksha USPC), the panels are not giving enough power yet. Shakti's fix is to wait for proper sunlight; the Lotus and Simha Plus manuals also say to check dust on the panels and their direction. If it happens in full sun, ask the installer to check the panels and the minimum input power setting.

What does 11 PMSM Start Fail mean?

On Nandi, Lotus and Simha Plus drives, 11 PMSM START FAIL means the starting torque was not enough or the pump or motor is jammed. The installer can raise the torque boost and initial ramp time settings and check the pump. On Kalpavriksha USPC the same fault is 32 START FAIL PMSM.