Delta VFD Lv Fault: Low DC Bus Voltage

Quick answer

Lv on a Delta AC drive means low voltage: the drive detected that the DC bus voltage fell below its minimum value. VFD-EL-W and VFD-M show Lv. The MS300 shows LvA (during acceleration), Lvd (deceleration), Lvn (constant speed) or LvS (at stop), each when the DC bus is lower than Pr.06-00. Delta's causes are a power cut, supply voltage changes, a wrong drive model for the supply, starting a large motor on the same supply, or (MS300) a missing short circuit plate or DC reactor between +1 and +2.

Safety: Only a qualified electrician should work on the drive or motor wiring. Delta's MS300 manual says to switch off the AC input power before any wiring, not to touch internal parts until the POWER LED is off, and to measure the DC bus voltage and wait until it is below 25 VDC, because hazardous voltage can stay in the capacitors after power-off. The VFD-EL-W and VFD-M manuals also say to make sure the RUN command is OFF before you press RESET.

Common causes

  • Power cut or poor supply
  • Supply voltage changes or is outside the drive rating
  • Wrong drive model for the supply
  • A large motor starting on the same supply
  • Phase loss on a three-phase input (VFD-EL-W)
  • Load too large during acceleration (MS300 LvA)
  • MS300: no short circuit plate or DC reactor between terminals +1 and +2

Fix it step by step

  1. Have an electrician check the input supply voltage is within the drive rating.
  2. For three-phase models, have an electrician check the input wiring to R-S-T for phase loss.
  3. Check the drive model matches the supply.
  4. On MS300, if the drive keeps showing LvS after you cycle the power with a good supply, Delta says to return it to the factory for repair.

Still showing Lv?

  • On VFD-M, low voltage is not stored in the fault record (Pr.73 record 14).

हिंदी में

Delta VFD में Lv का मतलब है ड्राइव के अंदर DC बस वोल्टेज कम हो गया, यानी सप्लाई वोल्टेज कम या बिजली गई। MS300 में LvA, Lvd, Lvn, LvS दिखता है।

  1. इलेक्ट्रीशियन से सप्लाई वोल्टेज चेक कराएं कि ड्राइव की रेंज में है।
  2. थ्री-फ़ेज़ में इलेक्ट्रीशियन से फ़ेज़ लॉस चेक कराएं।
  3. सप्लाई ठीक होने पर भी MS300 में LvS रहे तो Delta फ़ैक्ट्री रिपेयर कहता है।

Questions people ask

What does LvS mean on Delta MS300?

Low voltage at stop: the DC bus is below Pr.06-00 while the drive is stopped. Delta also lists a hardware failure in voltage detection as a cause.