Quick answer
ocn on a Delta AC drive means over-current while running at constant speed. On the MS300, Delta says output current went above three times the rated current, so the drive shut off its output at once and the motor coasted. Delta's causes include a short circuit in the motor cable, a locked motor shaft, poor motor insulation, a sudden change in load, and a motor larger than the drive. VFD-EL-W calls it over-current during constant speed operation and VFD-M calls it OCn.
Safety: Only a qualified electrician should work on the drive or motor wiring. Delta's MS300 manual says to switch off the AC input power before any wiring, not to touch internal parts until the POWER LED is off, and to measure the DC bus voltage and wait until it is below 25 VDC, because hazardous voltage can stay in the capacitors after power-off. The VFD-EL-W and VFD-M manuals also say to make sure the RUN command is OFF before you press RESET.
Common causes
- Short circuit at the motor output because of poor cable insulation
- Motor shaft locked, or burnt or aged motor insulation
- Sudden change in load
- Motor larger than the drive
- A contactor on the drive output switching while the drive is running
- V/F curve or torque compensation set too high
- Interference from control or main circuit wiring
Fix it step by step
0 of 5 done
- Note the code and the series.
- Check whether the motor or machine is jammed (motor stall), with the power off.
- Have an electrician check the motor cable for short circuits and the motor insulation with a megger.
- Check the load and that the motor rated current is not more than the drive rated current.
- Wait 5 seconds after the fault is cleared, make sure RUN is OFF, then press RESET.
Still showing ocn?
- If the load is right and wiring is fine, Delta's suggestion is a drive with larger capacity.
- The 300% trip level is from the MS300 manual. The VFD-M error code list (p.4-69) describes ocA, ocd and ocn as output current exceeding 2 times the rated current.
हिंदी में
Delta VFD में ocn का मतलब है एक ही स्पीड पर चलते समय करंट बहुत ज़्यादा हो गया।
- बिजली बंद करके देखें कि मशीन या मोटर जाम तो नहीं।
- इलेक्ट्रीशियन से मोटर केबल और इंसुलेशन चेक कराएं।
- लोड कम करें या बड़ी क्षमता की ड्राइव लगाएं।
- RUN बंद करके RESET दबाएं।
Questions people ask
Why does ocn come after the motor has been running fine?
Delta lists a sudden load change, a locked motor shaft and motor or cable insulation faults as causes during steady running.
Did this fix your problem? क्या इससे मदद मिली?
What went wrong?
Thanks. This helps us fix our guides. धन्यवाद!