Lloyd AC Error Codes List: E0, E6, dF, P3, L4 (Inverter and Non-Inverter)

By FaultDecode · Checked against Lloyd's official documents · Updated · How we check

63 Lloyd codes on this page.

Your model:

This list is from the Errors & Troubleshooting table in Lloyd's split AC owner's manual, published by Havells. Lloyd uses different tables for inverter and non-inverter split ACs, and the same code can mean different things: on an inverter model E1 is an indoor fan fault, on a non-inverter model it is a room temperature sensor fault. Check whether your AC is inverter before reading a code. The manual gives meanings only, not home fixes.

Safety: Lloyd's manual says to cut off the power supply before any work, not to repair the AC yourself, and to call a qualified technician. For E5 (refrigerant leak), switch off and call Lloyd service.

How to see the code

  1. Look at the indoor unit display for a 2-character code such as E6 or P3.
  2. If there is no display, count the indoor LED flashes. Lloyd's manual says to count from the second cycle of flashes.
  3. Inverter models may also flash a light on the outdoor unit; the count is listed below next to each code.
  4. Check whether your AC is an inverter or non-inverter model, then match the code in the right part of the table.

Only a blinking light? Use the Lloyd blink decoder: tap once per flash and see the code.

How to check the error code on other AC brands

Lloyd AC error code list

CodeModel typeMeaningWhat to do
EE (indoor LED 25 flashes, outdoor 25) Inverter split Indoor unit memory (EE) fault —
E0 (indoor LED 1 flashes, outdoor 1) Inverter split Outdoor unit memory (EE) fault —
E1 (indoor LED 26 flashes, outdoor 26) Inverter split Indoor fan fault —
E2 (indoor LED 27 flashes, outdoor 27) Inverter split Indoor fan zero-crossing detection abnormal —
E3 (indoor LED 28 flashes, outdoor 28) Inverter split Indoor coil fault and coil sensor fault · full fix E3 on a Lloyd AC points to a coil sensor, but which one depends on the model. On a Lloyd inverter split AC, E3 is an indoor coil fault and coil sensor fault. On selected non-inverter split ACs, E3 is an outdoor coil temperature sensor fault. Lloyd's manual gives no home fix. Switch off and call Lloyd service.
E4 (indoor LED 29 flashes, outdoor 29) Inverter split Indoor room temperature sensor fault —
E5 (indoor LED 30 flashes, outdoor 30) Inverter split Refrigerant leak fault (selected models) · full fix E5 on a Lloyd AC means different things on different models. On a Lloyd inverter split AC, E5 is a refrigerant (gas) leak fault, on selected models. On a non-inverter split AC, E5 (also shown as H6) is an indoor fan motor fault. Lloyd's manual gives no home fix for either. Switch off the AC and call Lloyd service.
E6 (indoor LED 2 flashes, outdoor 2) Inverter split Indoor and outdoor units not communicating · full fix E6 on a Lloyd inverter split AC means the indoor and outdoor units are not communicating. On models without a display, the indoor LED flashes 2 times. Lloyd's manual gives the meaning but no home fix. Switch off the AC and call Lloyd service.
E9 / EF (indoor LED 3 flashes) Inverter split Wi-Fi module fault (selected models) —
EH (indoor LED 24 flashes, outdoor 24) Inverter split Humidity sensor fault (selected models) —
EP (indoor LED 37 flashes) Inverter split PM2.5 sensor fault (selected models) —
EU (indoor LED 38 flashes) Inverter split Voice module communication fault (selected models) —
F1 (indoor LED 4 flashes, outdoor 4) Inverter split Compressor start abnormal or phase failure —
F2 (indoor LED 5 flashes, outdoor 5) Inverter split Compressor out-of-step fault —
F3 (indoor LED 6 flashes, outdoor 6) Inverter split IPM (inverter power module) fault —
F4 (indoor LED 7 flashes, outdoor 7) Inverter split Compressor shell top fault or protection —
F5 (indoor LED 8 flashes, outdoor 8) Inverter split Discharge temperature sensor fault —
F6 (indoor LED 9 flashes, outdoor 9) Inverter split Suction temperature sensor fault (selected models) —
F7 (indoor LED 10 flashes, outdoor 10) Inverter split Outdoor coil temperature sensor fault —
F8 (indoor LED 11 flashes, outdoor 11) Inverter split Outdoor air temperature sensor fault —
F9 (indoor LED 12 flashes, outdoor 12) Inverter split Outdoor DC fan fault (selected models) —
P1 (indoor LED 13 flashes, outdoor 13) Inverter split Outdoor unit AC current protection —
P2 (indoor LED 14 flashes, outdoor 14) Inverter split Compressor phase current protection —
P3 (indoor LED 15 flashes, outdoor 15) Inverter split Outdoor unit supply voltage too high or too low · full fix P3 on a Lloyd inverter split AC means the supply voltage to the outdoor unit is too high or too low. Lloyd's manual gives the meaning but no home fix. Switch off the AC and call Lloyd service.
P4 (indoor LED 16 flashes, outdoor 16) Inverter split DC voltage too high or too low —
P5 (indoor LED 17 flashes, outdoor 17) Inverter split IPM over-temperature protection —
P6 (indoor LED 18 flashes, outdoor 18) Inverter split Discharge temperature overheat protection —
P7 (indoor LED 19 flashes, outdoor 19) Inverter split Indoor coil anti-freeze protection in cooling The AC is defrosting the indoor coil in cooling; the code shows for some time while frost is removed
P8 (indoor LED 20 flashes, outdoor 20) Inverter split Outdoor coil overheat protection in cooling —
P9 (indoor LED 21 flashes, outdoor 21) Inverter split Indoor coil overheat protection in heating (selected models) —
PC (indoor LED 22 flashes, outdoor 22) Inverter split Outdoor temperature too low for cooling —
PH (indoor LED 23 flashes, outdoor 23) Inverter split Outdoor temperature too high for heating (selected models) —
L1 (indoor LED 31 flashes, outdoor 31) Inverter split Drive bus voltage too high —
L2 (indoor LED 32 flashes, outdoor 32) Inverter split Drive bus voltage too low —
L3 (indoor LED 33 flashes, outdoor 33) Inverter split Drive phase current overload fault —
L4 (indoor LED 34 flashes, outdoor 34) Inverter split Phase current sampling abnormal —
E1 (indoor LED 29 flashes) Split (non-inverter) Indoor room temperature sensor fault —
E2 (indoor LED 28 flashes) Split (non-inverter) Indoor coil temperature sensor fault —
E5 / H6 (indoor LED 26 flashes) Split (non-inverter) Indoor fan motor fault · full fix E5 on a Lloyd AC means different things on different models. On a Lloyd inverter split AC, E5 is a refrigerant (gas) leak fault, on selected models. On a non-inverter split AC, E5 (also shown as H6) is an indoor fan motor fault. Lloyd's manual gives no home fix for either. Switch off the AC and call Lloyd service.
dF (indoor LED 19 flashes) Split (non-inverter) Indoor defrost protection in cooling · full fix The AC is defrosting the indoor coil in cooling; the code shows for some time while frost is removed
E3 Split (non-inverter) Outdoor coil temperature sensor fault (selected models) · full fix E3 on a Lloyd AC points to a coil sensor, but which one depends on the model. On a Lloyd inverter split AC, E3 is an indoor coil fault and coil sensor fault. On selected non-inverter split ACs, E3 is an outdoor coil temperature sensor fault. Lloyd's manual gives no home fix. Switch off and call Lloyd service.
HP (indoor LED 21 flashes) Split (non-inverter) Indoor coil overheat protection in heating (selected models) —
HF Split (non-inverter) Outdoor defrost protection in heating (selected models) —
CL Inverter split Filter cleaning reminder (selected models) Clean the filter (remove, brush or vacuum, wash under running water, air-dry out of direct sun, refit). Newer manual: reset the reminder by pressing TURBO for 5 seconds. On side display type B the Power (green) LED blinks while the reminder is on.
go Inverter split Intelligent Diagnosis passed: the self-test found no fault (selected models) —
ng Inverter split Intelligent Diagnosis found a fault: the Sleep LED (red) blinks the error code and the buzzer beeps 5 times (selected models) The manual gives no fix. Note the error and call Lloyd service.
Ht Both Heat mode indication, not a fault —
P3 01 (no LED flash) Inverter split Low voltage indication / notification (newer manual) —
P3 02 (no LED flash) Inverter split High voltage indication / notification (newer manual) —
PE (outdoor light 39 flashes, no indoor flash) Inverter split Earth fault protection (newer manual) —
LO / Lb Inverter split Remote control battery low: the remote handset shows Lb or Lo (newer manual) Replace the two AAA 1.5 V batteries in the remote.
do Inverter split Door open alert: room temperature keeps rising, so the AC warns of low cooling, as from an open door. Shows "do" for a few seconds with a beep (selected models, newer manual p.37) —
dg Inverter split DG mode is on (switched on with the DG key, for running on a diesel generator). "dg" shows continuously; switching the AC off and on at the power switch ends it (newer manual p.42) —
Ic Inverter split Ice Clean is running: "Ic" blinks during the 20-30 minute self-clean, then the AC goes to standby (newer manual p.43) —
E1 Window AC (fixed speed) Ambient / room temperature sensor fault —
E2 Window AC (fixed speed) Evaporator / coil temperature sensor fault —
dF Window AC (fixed speed) Defrost protection · full fix dF on a Lloyd AC is defrost protection, a protection the AC runs by itself. Lloyd's manual lists dF on non-inverter split ACs as indoor defrost protection in cooling: the AC is defrosting the indoor coil, and the code shows for some time while the frost is removed. On Lloyd fixed-speed window ACs, the manual lists dF as defrost protection. On Lloyd inverter split ACs the same protection shows as P7.
CL Window AC (fixed speed) Filter cleaning reminder (not a fault) Clean the filter (remove, brush or vacuum, wash under running water, air-dry, refit), then press TURBO four times to reset the reminder.
F1 Window AC (fixed speed), touch panel display Fan speed LOW selected (not an error) Nothing to fix. This is a display setting, not an error.
F2 Window AC (fixed speed), touch panel display Fan speed MEDIUM selected (not an error) Nothing to fix. This is a display setting, not an error.
F3 Window AC (fixed speed), touch panel display Fan speed HIGH selected (not an error) Nothing to fix. This is a display setting, not an error.
FA Window AC (fixed speed), touch panel display Auto fan speed selected (not an error) Nothing to fix. This is a display setting, not an error.
Co / dY / Fn / AU Window AC (fixed speed), touch panel display Mode shown on the display: Co = Cool, dY = Dry, Fn = Fan, AU = Auto (not an error) Nothing to fix. This is a display setting, not an error.

No code, but a problem?

Good to know

हिंदी में

Lloyd इन्वर्टर और नॉन-इन्वर्टर AC के कोड अलग हैं। इन्वर्टर AC में E1 का मतलब अंदर वाले पंखे की खराबी है, नॉन-इन्वर्टर में कमरे का तापमान सेंसर खराब। पहले देखें आपका AC इन्वर्टर है या नहीं।

  1. स्क्रीन पर कोड देखें। स्क्रीन न हो तो अंदर वाली LED कितनी बार ब्लिंक होती है, दूसरे चक्कर से गिनें।
  2. E6: अंदर और बाहर की यूनिट में बात नहीं हो रही। E5: गैस लीक, AC बंद करें।
  3. P7 या dF: ठंडक में AC कुछ देर अंदर की कॉइल की बर्फ हटाता (डीफ्रॉस्ट) है, उस दौरान यह कोड दिखता है।
  4. कोई भी काम करने से पहले बिजली बंद करें। AC खुद न खोलें, Lloyd सर्विस बुलाएं।

Questions people ask

What is E1 error in a Lloyd AC?

It depends on the model. Lloyd's manual lists E1 as an indoor fan fault on inverter split ACs and as an indoor room temperature sensor fault on non-inverter split ACs.

What is E6 error in a Lloyd inverter AC?

Lloyd's manual lists E6 as a communication fault between the indoor and outdoor units. The indoor LED flashes 2 times.

What do P7 and dF mean?

Lloyd's manual says that in cooling, when the indoor coil is very cold and humidity is high, the AC runs a defrost for some time to remove frost, and shows dF or P7 while it does.

My Lloyd AC LED is blinking. How do I read it?

Count the indoor LED flashes from the second cycle, as Lloyd's manual says, then match the number in the table.

Sources

Last checked:

↑