Siemens V20 VFD Fault Codes: F and A Codes Full List
This list comes from chapter 9, Faults and alarms, of Siemens' SINAMICS V20 Converter Operating Instructions (edition 12/2024). The V20 shows two kinds of codes. F codes are faults. A codes are alarms (warnings): the display shows the code starting with "A" and the alarm clears by itself once the cause is fixed. Several codes also store a fault value in parameter r0949 that tells you which exact cause was found.
Safety: Only a qualified electrician should work on the drive, the motor or their wiring. Siemens' fault and alarm tables tell you what to check, but changing parameters, checking cables or looking inside the drive is work for a trained person. Follow the safety instructions in the full SINAMICS V20 Operating Instructions before any work.
How to see the code
- Read the code on the V20 display. A code starting with F is a fault; a code starting with A is an alarm, shown after the alarm icon.
- Find the code in the Siemens V20 code list.
- For codes that list r0949 values (for example F1, F41, F51, F61, F350), read parameter r0949 to see which cause the drive found.
- Fix the cause first. Alarms then clear by themselves. Siemens gives a clearing rule only for some faults (F5, F51, F64, F350, F395): see the code list.
Siemens VFD / drive error code list
| Code | Model type | Meaning | What to do |
|---|---|---|---|
| F1 | SINAMICS V20 (fault) | Overcurrent: motor power (P0307) does not match converter power (r0206), motor lead short circuit, or earth fault · full fix | Check P0307 matches r0206, cable length limits, motor cable and motor for short circuits or earth faults, motor parameters and stator resistance (P0350), that the motor is not obstructed or overloaded. Increase ramp-up time (P1120), reduce starting boost (P1312). |
| F2 | SINAMICS V20 (fault) | Overvoltage: main supply voltage too high, or motor in regenerative mode · full fix | Check supply voltage (P0210) is within rating plate limits, ramp-down time (P1121) matches load inertia, braking power within limits, Vdc controller (P1240) enabled and set properly. Higher inertia needs longer ramp times, otherwise a braking resistor. |
| F3 | SINAMICS V20 (fault) | Undervoltage: main supply failed, or shock load outside specified limits · full fix | Check supply voltage. |
| F4 | SINAMICS V20 (fault) | Converter overtemperature: converter overloaded, poor ventilation, pulse frequency too high, surrounding temperature too high, or fan not working · full fix | Check load or load cycle, that P0307 matches r0206, pulse frequency at default, surrounding temperature, and that the fan turns when the converter runs. |
| F5 | SINAMICS V20 (fault) | Converter I2t: converter overloaded, load cycle too demanding, or motor power (P0307) exceeds converter power (r0206) · full fix | Load cycle must be within specified limits; P0307 must match r0206. F5 cannot be cleared until r0036 is lower than P0294. |
| F6 | SINAMICS V20 (fault) | Chip temperature rise exceeds critical levels: load at start-up or load step too high, or ramp-up too fast | Check load and load steps, increase ramp-up time (P1120), P0307 must match r0206. Siemens says P0290 = 0 or 2 prevents F6. |
| F11 | SINAMICS V20 (fault) | Motor overtemperature: motor overloaded (can also occur on small motors run below 15 Hz with motor temperature within limits) · full fix | Check load, P0626–P0628 and P0604. For small motors below 15 Hz: if motor current is within nameplate current and motor temperature is within limits, set P0335 = 1. |
| F12 | SINAMICS V20 (fault) | Converter temperature signal lost: wire breakage of heat sink temperature sensor | Contact service department or change converter. |
| F20 | SINAMICS V20 (fault) | DC ripple too high, commonly caused by loss of one of the mains input phases | Check the mains supply wiring. |
| F23 | SINAMICS V20 (fault) | Output current ripple too high: output phase missing or high motor vibration | Check output wiring, motor mechanical vibration, and the converter response setting P0296. |
| F26 | SINAMICS V20 (fault) | Internal error | Power-cycle converter. Contact service department or change converter. |
| F35 | SINAMICS V20 (fault) | Maximum number of auto restart attempts (P1211) exceeded | Increase the number of restart attempts (P1211). |
| F41 | SINAMICS V20 (fault) | Motor data identification failure | r0949 = 0: is the motor connected? r0949 = 1–49: are motor data P0304–P0311 correct? Check star or delta motor wiring. |
| F51 | SINAMICS V20 (fault) | Parameter EEPROM fault: read or write failure, or EEPROM full (too many parameters changed) | Power-cycle. If that does not clear it: factory reset (P0970 = 31) and new parameterization. If EEPROM is full, set some parameters back to default, then power-cycle. Otherwise change converter. |
| F52 | SINAMICS V20 (fault) | Converter software fault: read failure for converter information or invalid data | Power-cycle converter. Contact service department or change converter. |
| F60 | SINAMICS V20 (fault) | Asic timeout: internal communications failure | If sporadic (EMC problems): improve EMC, use EMC filter. If it appears immediately at power-on and ON command: contact service department or change converter. |
| F61 | SINAMICS V20 (fault) | SD card parameter cloning failed | Depends on r0949: use a FAT16/FAT32 SD card, check the card is not full, put the correct file in /USER/SINAMICS/DATA, or recreate the file. |
| F62 | SINAMICS V20 (fault) | Parameter cloning contents invalid (file exists but contents not valid) | Recopy and make sure the operation completes. |
| F63 | SINAMICS V20 (fault) | Parameter cloning contents incompatible (file from a different converter type) | Clone from a compatible converter type. |
| F64 | SINAMICS V20 (fault) | Converter attempted an automatic clone during startup but no Clone00.bin in /USER/SINAMICS/DATA | If automatic clone is needed, insert the SD card with the correct file and power-cycle. If not, remove the card if not needed and power-cycle, and reset P8458 = 0 and power-cycle. Cleared only by a power-cycle. |
| F70 | SINAMICS V20 (fault) | I/O Extension Module communication fault | Reconnect the module and check it works. Acknowledge the fault. If it persists, replace the module. |
| F71 | SINAMICS V20 (fault) | USS setpoint fault (on RS232): no setpoint values during telegram off time | Check USS master on RS232. |
| F72 | SINAMICS V20 (fault) | USS/MODBUS setpoint fault (on RS485): no setpoint values during telegram off time | Check USS/MODBUS master on RS485. |
| F80 | SINAMICS V20 (fault) | Signal lost on analog input: broken wire or signal out of limits | Check the wiring and whether analog inputs exceed voltage and current limits. Contact service department or change converter. |
| F85 | SINAMICS V20 (fault) | External fault triggered via control word 2, bit 13 | Check P2106. Disable control word 2 bit 13 as command source, or disable the terminal input for fault trigger. |
| F100 | SINAMICS V20 (fault) | Watchdog reset: software error | Contact service department or change converter. |
| F101 | SINAMICS V20 (fault) | Stack overflow: software error or processor failure | Contact service department or change converter. |
| F200 | SINAMICS V20 (fault) | Script error: internal converter script stopped because of script errors | Check the script and correct it. |
| F221 | SINAMICS V20 (fault) | PID feedback below minimum value (P2268) | Change P2268 or adjust feedback gain. |
| F222 | SINAMICS V20 (fault) | PID feedback above maximum value (P2267) | Change P2267 or adjust feedback gain. |
| F350 | SINAMICS V20 (fault) | Configuration vector for the converter failed (hardware does not match programmed configuration; r0949 = 13: wrong power module fitted) | Internal failures cannot be fixed. r0949 = 13: make sure the right power module is fitted. Needs a power-cycle to acknowledge. |
| F395 | SINAMICS V20 (fault) | Acceptance test/confirmation pending: after a startup clone (or faulty EEPROM read) the parameter set must be checked | Check the current parameter set and confirm it by clearing the fault. |
| F410 | SINAMICS V20 (fault) | Cavitation protection failure: conditions exist for pump cavitation damage (fluid not flowing enough) | If cavitation is not occurring, reduce the threshold P2361 or increase the cavitation protection delay. Make sure sensor feedback works. |
| F452 | SINAMICS V20 (fault) | Load monitoring trip: load conditions indicate belt failure or mechanical fault (r0949 = 0 low, 1 high torque/speed) | Check for breakage, seizure or obstruction of the drive train, lubricate if required, and check P2182–P2192 settings. |
| A501 | SINAMICS V20 (alarm) | Current limit: motor power does not match converter power, motor leads too long, earth faults, or small motor (120 W) under FCC at light load | See F1. Use V/f operation for very small motors. |
| A502 | SINAMICS V20 (alarm) | Overvoltage limit reached; can occur during ramp down if the Vdc controller is disabled (P1240 = 0) | If shown permanently, check converter input voltage. |
| A503 | SINAMICS V20 (alarm) | Undervoltage limit: main supply failed, or supply and DC-link voltage (r0026) below specified limit | Check main supply voltage. |
| A504 | SINAMICS V20 (alarm) | Converter overtemperature: heat sink or chip junction temperature warning level exceeded, so pulse frequency and/or output frequency is reduced (P0290) | Check surrounding temperature, load conditions and load steps, and that the fan turns when running. r0037[0] = heat sink, r0037[1] = chip junction temperature. |
| A505 | SINAMICS V20 (alarm) | Converter I2t warning level exceeded; current will be reduced if P0610 = 1 | Check the load cycle is within specified limits. |
| A506 | SINAMICS V20 (alarm) | IGBT junction temperature rise warning: heat sink to IGBT junction temperature difference exceeds warning limits | Check load steps and shock loads are within limits. |
| A507 | SINAMICS V20 (alarm) | Converter temperature signal lost: heat sink temperature signal loss, sensor may have fallen off | Contact service department or change converter. |
| A511 | SINAMICS V20 (alarm) | Motor overtemperature I2t: motor overloaded, or load cycles or load steps too high | Check P0604, P0625, nameplate data (quick commissioning, motor identification P1900 = 2), motor weight P0344; P0626–P0628 for non-Siemens motors. |
| A523 | SINAMICS V20 (alarm) | Output current ripple too high: loss of one output phase or high motor vibration | Check output wiring and motor mechanical vibration. |
| A535 | SINAMICS V20 (alarm) | Braking resistor overload: braking energy too large or resistor not suited | Reduce braking energy, or use a braking resistor with a higher rating. |
| A541 | SINAMICS V20 (alarm) | Motor data identification active (P1900 selected or running) | Complete the motor data identification. |
| A600 | SINAMICS V20 (alarm) | RTOS overrun warning: internal time slice overrun | Contact service department. |
| A910 | SINAMICS V20 (alarm) | Vdc_max controller de-activated: supply voltage (P0210) permanently too high, motor driven by an active load, or very high load inertia when ramping down | Input voltage must be within range, load must match, in some cases apply a braking resistor. |
| A911 | SINAMICS V20 (alarm) | Vdc_max controller active: keeping DC-link voltage (r0026) below r1242 | Check supply voltage is within rating plate limits and ramp-down time (P1121) matches load inertia; otherwise a braking resistor. |
| A912 | SINAMICS V20 (alarm) | Vdc_min controller active: DC-link voltage (r0026) fell below r1246; motor energy used to buffer it, so the converter decelerates. Can also occur on fast ramp-ups | Check converter input voltage. If it activates during ramp-up, increase ramp-up time (P1120). Check shock load (see F3). |
| A921 | SINAMICS V20 (alarm) | Analog output parameters not set properly (P0777 and P0779 identical) | Set P0777 and P0779 to different values; settings must match the analog output type. |
| A922 | SINAMICS V20 (alarm) | No load applied to converter; some functions may not work as normal | Check that the motor is connected to the converter. |
| A923 | SINAMICS V20 (alarm) | Both JOG left and JOG right requested (P1055/P1056); output frequency frozen | Do not press JOG right and left at the same time. |
| A930 | SINAMICS V20 (alarm) | Cavitation protection warning: conditions exist for possible cavitation damage | See F410. |
| A936 | SINAMICS V20 (alarm) | PID autotuning active (P2350 selected or running) | Disappears when PID autotuning has finished. |
| A952 | SINAMICS V20 (alarm) | Load monitoring warning: load conditions indicate belt failure or mechanical fault | See F452. |
Good to know
- Alarms cannot be acknowledged. Siemens says they are cleared automatically once the warning has been rectified.
- P2100 selects up to 3 faults for a non-default stop reaction, and P2101 sets that reaction. For alarms, P2100 and P2101 can disable the stop reaction for up to 3 selected alarms, and P2113 disables it for all alarms.
- r0949 gives the fault value. For F1: 0 and 22 = hardware reported, 1 = software reported. For F2 and F3: 0 = hardware reported, 1 or 2 = software reported.
- F5 cannot be cleared until the converter overload utilization (r0036) is lower than the converter I2t warning level (P0294).
- F64 can only be cleared by a power-cycle. F350 needs a power-cycle to be acknowledged. F51: power-cycle first; if that does not remove it, factory reset (P0970 = 31) and parameterize again.
- For F12, F26, F52, F80, F100, F101 and A507, Siemens says to contact the service department or change the converter.
हिंदी में
Siemens SINAMICS V20 ड्राइव में F से शुरू होने वाला कोड फ़ॉल्ट है और A से शुरू होने वाला कोड अलार्म (चेतावनी) है, जो कारण ठीक होते ही अपने आप हट जाता है। F1 मतलब ओवरकरंट, F2 ओवरवोल्टेज, F3 अंडरवोल्टेज, F4 ड्राइव ज़्यादा गरम, F5 ड्राइव ओवरलोड (I2t), F11 मोटर ज़्यादा गरम।
- डिस्प्ले पर कोड पढ़ें: F मतलब फ़ॉल्ट, A मतलब अलार्म।
- Siemens V20 कोड लिस्ट में कोड का मतलब और क्या चेक करना है देखें।
- कई कोड के लिए पैरामीटर r0949 बताता है कि असली कारण कौन सा है।
- पहले कारण ठीक करें। अलार्म अपने आप हट जाते हैं। कुछ फ़ॉल्ट (F5, F51, F64, F350, F395) को हटाने का तरीका Siemens ने कोड लिस्ट में बताया है।
- ड्राइव, मोटर या वायरिंग का काम सिर्फ़ प्रशिक्षित इलेक्ट्रीशियन करे।
Questions people ask
What is the difference between F and A codes on a Siemens V20?
F codes are faults and A codes are alarms. Siemens says alarms cannot be acknowledged; they clear automatically once the warning has been rectified.
What is F1 fault in Siemens V20?
Overcurrent. Siemens lists motor power (P0307) not matching converter power (r0206), a motor lead short circuit and earth faults as causes. Checks include cable length, motor parameters, stator resistance (P0350), a longer ramp-up time (P1120) and a lower starting boost (P1312).
Why does F5 not clear on my V20?
Siemens says F5 cannot be cleared until the converter overload utilization (r0036) is lower than the converter I2t warning level (P0294).
What does r0949 mean on a V20?
r0949 holds the fault value. For many faults it tells which cause was found, for example on F1 whether hardware or software reported the overcurrent, or on F41 why motor data identification failed.
Sources
- Siemens SINAMICS V20 Converter Operating Instructions, 12/2024 (A5E34559884-017): 9 Faults and alarms, pp.334–343
- Siemens Industry Online Support entry 109977897 (SINAMICS V20 Operating Instructions)