ABB VFD Fault 4210: IGBT Overtemperature (ACS580, ACS355 0003, ACS550 Fault 3)

Quick answer

4210 on an ABB drive means the drive's power transistors (IGBTs) are too hot. On the ACS580 it is 4210 IGBT overtemperature (estimated IGBT temperature is excessive). On the ACS355 it is fault 0003 DEV OVERTEMP (fieldbus code 4210), and on the ACS550 it is fault 3 DEV OVERTEMP, which trips when the heatsink reaches 115 °C (frames R1–R4) or 125 °C (R5, R6). ABB's checks: ambient temperature, air flow and fan, dust on the heatsink fins, and motor power against drive power.

Safety: ABB's manuals say only qualified electricians may maintain or service the drive, following the safety instructions in the manual. For any check of wiring, cables, fuses or motor insulation, switch off the supply and call a qualified electrician. The ACS550 manual also warns not to attempt any measurement, parts replacement or other service procedure not described in the manual, and that if an external start command is active the drive may start immediately after a fault reset.

Common causes

  • Ambient temperature too high
  • Air flow through the drive blocked, or not enough free space around it
  • Cooling fan not working properly
  • Dirt or dust on the heatsink
  • Excessive motor load, or the drive is overloaded
  • Motor power too large for the drive

Fix it step by step

  1. Note the code and check the series on the drive's type label.
  2. Check the ambient temperature around the drive. The ACS355 manual says load capacity decreases if the ambient temperature at the installation site exceeds 40 °C (104 °F) and refers to its Derating section; for ACS580, ABB's 4290 Cooling entry refers to the Derating section of the drive's Hardware manual.
  3. Check that air flows freely and that there is enough free space above and below the drive.
  4. Have a qualified electrician, with the supply switched off, check the cooling fan and clean dust from the heatsink fins.
  5. Check the motor load, and compare the motor power with the drive power.
  6. ACS355: ABB allows 50% overload for one minute in ten minutes; if a higher switching frequency (2606) is used, follow the derating rules.
  7. Once the cause is fixed, reset the fault.

Still showing 4210?

  • ACS550: the fault trips at a heatsink temperature of 115 °C on frames R1–R4 and 125 °C on R5 and R6. Alarm 2009 DEVICE OVERTEMP comes first, at 100 °C and 110 °C.
  • ACS580: related temperature codes are 42F1 IGBT temperature, 4290 Cooling (drive module temperature), 2381 IGBT overload and warning A4A1 IGBT overtemperature.
  • ACS355: alarm 2009 DEVICE OVERTEMP warns that the IGBT temperature is excessive before the trip.

हिंदी में

ABB ड्राइव में 4210 का मतलब है IGBT (पावर ट्रांजिस्टर) बहुत गरम हो गए। ACS580 में 4210, ACS355 में 0003 DEV OVERTEMP और ACS550 में फ़ॉल्ट 3 दिखता है।

  1. ड्राइव के आसपास का तापमान बहुत ज़्यादा तो नहीं, देखें।
  2. हवा आने-जाने का रास्ता खुला हो, ड्राइव के ऊपर-नीचे जगह हो।
  3. बिजली बंद करके इलेक्ट्रीशियन से पंखा और हीटसिंक की धूल साफ़ कराएं।
  4. मोटर का लोड और मोटर की पावर ड्राइव की क्षमता से ज़्यादा न हो।

Questions people ask

At what temperature does an ABB ACS550 trip on DEV OVERTEMP?

ABB's ACS550 manual gives a heatsink trip limit of 115 °C for frames R1–R4 and 125 °C for frames R5 and R6. The DEVICE OVERTEMP alarm (2009) comes at 100 °C and 110 °C.

Is ACS355 fault 0003 the same as 4210?

Yes. The ACS355 manual lists 0003 DEV OVERTEMP (drive IGBT temperature is excessive) with fieldbus code 4210.

What is the difference between 4210 and 42F1 on ACS580?

ABB describes 4210 as estimated drive IGBT temperature being excessive and 42F1 as drive IGBT temperature being excessive. The checks are the same: ambient, air flow and fan, heatsink dust, motor power against drive power.