Quick answer
2330 on an ABB drive means earth leakage: the drive has found a load unbalance, typically from an earth (ground) fault in the motor or motor cable. On the ACS580 it is 2330 Earth leakage. On the ACS355 it is fault 0016 EARTH FAULT (fieldbus code 2330), and on the ACS550 it is fault 16 EARTH FAULT. This is an electrical safety fault: switch off and have a qualified electrician measure the insulation of the motor and motor cable.
Safety: This is an electrical leakage fault. Switch off the supply and call a qualified electrician. ABB's manuals say only qualified electricians may maintain or service the drive, and the ACS355 and ACS550 manuals warn that disabling earth fault protection may damage the drive or void the warranty. The ACS550 manual also warns that if an external start command is active the drive may start immediately after a fault reset.
Common causes
- Earth fault in the motor or the motor cable
- Power factor correction capacitors or surge absorbers in the motor cable (ACS580)
- Motor cable longer than the maximum specified length (ACS355, ACS550)
- Faults in the input wiring (ACS550)
- A delta grounded supply with high-capacitance motor cables, which can give false earth fault reports when the drive is not running (ACS550)
- Drive internal fault (ACS355)
Fix it step by step
0 of 6 done
- Note the code and check the series on the drive's type label.
- Switch off the supply and call a qualified electrician.
- The electrician should measure the insulation resistance of the motor and motor cable. ABB's ACS580 manual says: if an earth fault is found, fix or change the motor cable and/or motor.
- ACS580: check there are no power factor correction capacitors or surge absorbers in the motor cable. If allowed, ABB suggests trying the motor in scalar control mode (99.04).
- ACS355 and ACS550: check the motor cable does not exceed the maximum specified length. ACS550: also check the input wiring.
- Once the fault is fixed, reset the fault.
Still showing 2330?
- ACS580: if no earth fault can be found, ABB says to contact your local ABB representative.
- ACS355: an internal short circuit can cause an earth fault indication. ABB says this has happened if fault 0001 appears after disabling the earth fault; then replace the drive. ABB warns that disabling earth fault may damage the drive.
- ACS550: the drive checks for earth faults while running and while stopped, and detection is more sensitive when stopped, which can give false trips. ABB lists 3028 EARTH FAULT LVL to lower the detection level, 3023 WIRING FAULT to turn off checks while stopped and 3017 EARTH FAULT to turn off all earth fault checks, but notes that disabling earth fault may void the warranty.
- ACS580 warning A2B3 Earth leakage is the same condition shown as a warning.
हिंदी में
ABB ड्राइव में 2330 का मतलब है अर्थ लीकेज: मोटर या मोटर केबल में अर्थ (ग्राउंड) फ़ॉल्ट। ACS580 में 2330, ACS355 में 0016 EARTH FAULT और ACS550 में फ़ॉल्ट 16 दिखता है। यह बिजली से जुड़ा सुरक्षा फ़ॉल्ट है।
- बिजली बंद करें और योग्य इलेक्ट्रीशियन को बुलाएं।
- इलेक्ट्रीशियन मोटर और मोटर केबल का इंसुलेशन मापे; फ़ॉल्ट मिले तो केबल या मोटर ठीक कराएं या बदलें।
Questions people ask
Is ABB 2330 the same as ACS355 0016 EARTH FAULT?
Yes. The ACS355 manual lists 0016 EARTH FAULT with fieldbus code 2330. The ACS580 calls 2330 Earth leakage, and the ACS550 calls it fault 16 EARTH FAULT.
Why does my ABB ACS550 show EARTH FAULT when the motor is stopped?
ABB says the ACS550 checks for earth faults even when not running, and detection is more sensitive then, which can produce false positives, for example with a delta grounded supply and high-capacitance motor cables.
Can I disable the earth fault on an ABB drive?
ABB's manuals mention parameters for it, but warn that disabling earth fault may damage the drive (ACS355) or void the warranty (ACS550). Have an electrician find the cause instead.
Did this fix your problem? क्या इससे मदद मिली?
What went wrong?
Thanks. This helps us fix our guides. धन्यवाद!
Sources
- ABB ACS580 standard control program Firmware manual 3AXD50000016097 Rev J (2025): Fault tracing, p.540 (A2B3) and p.555 (2330)
- ABB ACS355 drives User's manual 3AUA0000066143 Rev E (2020): Fault tracing, p.363 (fault 0016)
- ABB ACS550-01/U1 User's Manual 3AFE64804588 Rev H (2014): Diagnostics, p.262 (fault 16)
Last checked: