ABB Fault 2310: Overcurrent (ACS580, ACS355 0001, ACS550 1)

Quick answer

2310 on an ABB drive means overcurrent: the output current went above the drive's limit, so the drive tripped and the motor stopped. On the ACS580 it shows as 2310 Overcurrent, and ABB says an earth fault or a supply phase loss can also cause it. On the ACS355 the same trip is fault 0001 OVERCURRENT (2310 is its fieldbus code), and on the ACS550 it is fault 1 OVERCURRENT. ABB's first checks are the motor load, the acceleration time, the motor data in group 99, and the motor and motor cable.

Safety: ABB's manuals say only qualified electricians may maintain or service the drive, following the safety instructions in the manual. For any check of wiring, cables, fuses or motor insulation, switch off the supply and call a qualified electrician. The ACS550 manual also warns not to attempt any measurement, parts replacement or other service procedure not described in the manual, and that if an external start command is active the drive may start immediately after a fault reset.

Common causes

  • Excessive motor load, or a sudden load change or stall
  • Acceleration time too short
  • Motor data (group 99) not matching the motor rating plate
  • Motor and/or drive too small for the application (ACS355)
  • Damaged motor or motor cables, faulty connections, or wrong star/delta connection
  • An earth fault or a supply phase loss (ACS580)
  • Contactors opening and closing in the motor cable, or power factor correction capacitors or surge absorbers in the motor cable (ACS580)
  • High-frequency noise in the STO lines (ACS355)
  • Internal fault of the drive (ACS355)

Fix it step by step

  1. Note the code and check the series on the drive's type label (ACS580, ACS355 or ACS550).
  2. Check the motor load and the driven machine for a sudden load change or stall.
  3. Check the acceleration time: parameters 2202 and 2205 on ACS355 and ACS550; on ACS580, parameter group 23 (speed control), 26 (torque control) or 28 (frequency control), and 46.01–46.03.
  4. Check that the motor data in group 99 matches the motor rating plate. On ACS355 with vector control, ABB says to perform an ID run (9910).
  5. Have a qualified electrician, with the supply switched off, check the motor and motor cable (including phasing and star/delta connection) and measure the insulation resistance of the motor and cable for an earth fault.
  6. ACS580: make sure no contactors open and close in the motor cable, and there are no power factor correction capacitors or surge absorbers in the motor cable.
  7. Once the cause is fixed, reset the fault from the panel (or the reset source you have set up).

Still showing 2310?

  • ACS355: if the drive gives an overcurrent fault after a start command even when the motor is not connected (ABB says to use scalar control for this trial), it is an internal fault of the drive and ABB says to replace the drive.
  • ACS355: if noise in the STO lines is the cause, check the STO cabling and remove noise sources nearby. Also check the drive sizing.
  • ACS580: check the auxiliary code. ABB says bit 7 = 1 means software overcurrent and bits 0, 1, 2 mean phase U, V, W (for example 0x83 = software overcurrent of phases U and V). No auxiliary code means hardware overcurrent.
  • Not a trip yet: alarm 2001 OVERCURRENT on ACS355 and ACS550 means the current limit controller is active, and A2B1 is the ACS580 overcurrent warning.

हिंदी में

ABB ड्राइव में 2310 का मतलब है ओवरकरंट: आउटपुट करंट ड्राइव की सीमा से ज़्यादा हो गया। ACS580 में यह 2310, ACS355 में 0001 OVERCURRENT और ACS550 में फ़ॉल्ट 1 दिखता है।

  1. मोटर का लोड और मशीन जाम तो नहीं, यह देखें।
  2. Acceleration time (ACS355/ACS550 में 2202, 2205) बहुत कम तो नहीं, देखें।
  3. ग्रुप 99 का मोटर डेटा मोटर की नेमप्लेट से मिलाएं।
  4. बिजली बंद करके इलेक्ट्रीशियन से मोटर, मोटर केबल और इंसुलेशन चेक कराएं।
  5. कारण ठीक होने के बाद ही रीसेट करें।

Questions people ask

Is ABB fault 2310 the same as ACS355 fault 0001?

Yes. The ACS355 manual lists fault 0001 OVERCURRENT with 2310 in brackets, which is its fieldbus code. The ACS580 shows the code 2310 directly, and the ACS550 calls it fault 1 OVERCURRENT.

Can an earth fault cause 2310 on an ACS580?

Yes. ABB's ACS580 manual says that besides a real overcurrent, this fault may also be caused by an earth fault or a supply phase loss, and tells you to measure the insulation resistance of the motor and motor cable.

What is alarm 2001 on an ABB ACS550 or ACS355?

It is the overcurrent alarm: the output current limit controller is active. It is a warning, not a trip. On the ACS550, ABB lists the same checks as for fault 1 (motor load, acceleration time, motor and cables). On the ACS355, ABB also lists high ambient temperature: check ambient conditions (load capacity decreases above 40 °C) and see fault 0001.