ABB VFD Fault Codes: ACS355, ACS550 and ACS580 Full List
This list comes from the fault tracing chapters of three ABB manuals in the ABB Library: the ACS355 User's manual (Rev E, 2020), the ACS550-01/U1 User's Manual (Rev H, 2014) and the ACS580 standard control program Firmware manual (Rev J, 2025). The same problem has a different code on each series: an overcurrent trip is 2310 on the ACS580, 0001 on the ACS355 (fieldbus code 2310) and fault 1 on the ACS550. ACS580 codes are hexadecimal; most warnings start with A (for example A2B1), and the pump and compressor warnings start with D (for example D50A). Check the series on the drive's type label, then read the rows for that series.
Safety: ABB's manuals say only qualified electricians may maintain or service the drive, and that all electrical installation and maintenance work must be done by qualified service personnel following the safety instructions in the manual. The ACS550 manual also warns: do not attempt any measurement, parts replacement or other service procedure not described in the manual, and if an external start command is active, the drive may start immediately after a fault reset.
How to see the code
- Read the code and name on the control panel (ACS580 shows both; ACS550 basic panel shows F0007 for fault 7 and A2008 for alarm 2008).
- Check the series on the drive's type label (ACS355, ACS550 or ACS580).
- Match the code in the rows for that series. Faults stop the motor. ACS550 alarms are advisory, and ACS580 warnings do not trip the drive.
- Fix the cause, then reset the fault from the panel, a digital input or fieldbus (the reset source is set by 1604 FAULT RESET SEL on ACS355/ACS550, 31.11 on ACS580).
ABB VFD / drive error code list
| Code | Model type | Meaning | What to do |
|---|---|---|---|
| 1080 | ACS580 | Backup/Restore timeout: the control panel or PC tool failed to communicate with the drive while a backup was being made or restored. | Request the backup or restore again. |
| 1081 | ACS580 | Rating ID fault: the drive software could not read the drive's rating ID. | Reset the fault so the drive rereads the rating ID. If it comes back, cycle the power (maybe more than once). If it persists, contact ABB. |
| 2281 | ACS580 | Calibration: measured offset of output phase current measurement, or the difference between U2 and W2 current measurement, is too great. | Try the current calibration again (parameter 99.13). If the fault persists, contact ABB. |
| 2310 | ACS580 | Overcurrent: output current has exceeded the internal fault limit. Besides a real overcurrent, an earth fault or supply phase loss can also cause it. · full fix | Check motor load, acceleration times, motor and motor cable (phasing, star/delta), contactors in the motor cable, motor data in group 99, no power factor capacitors or surge absorbers in the motor cable, and insulation. |
| 2330 | ACS580 | Earth leakage: the drive has detected load unbalance, typically due to an earth fault in the motor or motor cable. · full fix | Check for power factor capacitors or surge absorbers in the motor cable and measure motor and cable insulation. Try scalar control if allowed (99.04). If no earth fault is found, contact ABB. |
| 2381 | ACS580 | IGBT overload: excessive IGBT junction to case temperature. Can be caused by a short circuit in the motor cable. | Check motor cable, ambient conditions, air flow and fan, heatsink fins for dust, and motor power against drive power. |
| 3130 | ACS580 | Input phase loss: DC voltage is oscillating because an input power line phase is missing or a fuse is blown. | Check input fuses, loose power cable connections and supply imbalance. If phases are fine and it still trips, ABB says enabling 97.48 Udc stabilizer is reasonable. |
| 3181 | ACS580 | Wiring or earth fault: input power cable is connected to the drive's motor terminals. | Check input power connections. |
| 3210 | ACS580 | DC link overvoltage: intermediate circuit DC voltage is too high. · full fix | Check overvoltage control is on (30.30), supply voltage matches the drive, supply for overvoltage, brake chopper and resistor, and deceleration time. |
| 3220 | ACS580 | DC link undervoltage: DC voltage is not enough because of a missing supply phase, blown fuse or a fault in the rectifier bridge. · full fix | Check supply cabling, fuses and switchgear. |
| 3381 | ACS580 | Output phase loss: motor circuit fault, all three motor phases are not connected. | Connect the motor cable. |
| 3385 | ACS580 | Autophasing: the autophasing routine has failed. | Try other autophasing modes (21.13), check the motor ID run was completed, the motor is not already turning, and 99.03 is set to permanent magnet motor. |
| 4110 | ACS580 | Control board temperature: control unit temperature is too high. | Check cooling of the drive and the auxiliary cooling fan. |
| 4210 | ACS580 | IGBT overtemperature: estimated drive IGBT temperature is excessive. · full fix | Check ambient conditions, air flow and fan, heatsink fins for dust, and motor power against drive power. |
| 4290 | ACS580 | Cooling: drive module temperature is excessive. | Check ambient temperature and derating, cooling air flow and fan, and clean dust from the cabinet and heatsink. |
| 42F1 | ACS580 | IGBT temperature: drive IGBT temperature is excessive. | Check ambient conditions, air flow and fan, heatsink fins for dust, and motor power against drive power. |
| 4310 | ACS580 | Excess temperature: power unit module temperature is excessive. | See warning A4B0. |
| 4380 | ACS580 | Excess temperature difference: high temperature difference between the IGBTs of different phases. | Check the motor cabling and cooling of the drive module(s). |
| 4981 | ACS580 | External temperature 1: measured temperature 1 has exceeded the fault limit. | Check 35.02 and the cooling of the motor or measured equipment. |
| 4982 | ACS580 | External temperature 2: measured temperature 2 has exceeded the fault limit. | Check 35.03 and the cooling of the motor or measured equipment. |
| 4990 | ACS580 | CPTC-02 not found: the CPTC-02 extension module is not detected in option slot 2. | Power down the drive and check the module is properly inserted in slot 2. |
| 4991 | ACS580 | Safe motor temperature: the CPTC-02 module shows overtemperature (motor too hot, or thermistor shorted or disconnected). | Check motor cooling, motor load and drive ratings, sensor wiring and sensor resistance. |
| 5080 | ACS580 | Fan: cooling fan feedback missing (frame R6 or larger). | See warning A581. |
| 5081 | ACS580 | Auxiliary fan broken: an auxiliary cooling fan on the control unit fan connectors is stuck or disconnected. | Check the auxiliary code, fans and connections; replace a faulty fan; make sure the front cover is in place. Reboot the control unit (96.08) or cycle power. |
| 5089 | ACS580 | SMT circuit malfunction: a safe motor temperature fault is generated but no STO event, fault or warning. | Check the connection between the module's relay output and the STO terminal. |
| 5090 | ACS580 | STO hardware failure: STO hardware diagnostics detected a hardware failure. | Contact ABB quoting the auxiliary code. |
| 5091 | ACS580 | Safe torque off: STO safety circuit signal is broken during start or run. | Check safety circuit connections and parameter 95.04. |
| 5092 | ACS580 | PU logic error: power unit memory has cleared. | Contact ABB. |
| 5093 | ACS580 | Rating ID mismatch: drive hardware does not match the information in memory (for example after a firmware update). | Cycle the power (maybe more than once). If it persists, contact ABB. |
| 5094 | ACS580 | Measurement circuit temperature: problem with the drive's internal temperature measurement. | Contact ABB. |
| 5098 | ACS580 | I/O communication loss: communication failure to standard I/O. | Try resetting the fault or cycle the power. |
| 50A0 | ACS580 | Fan: cooling fan stuck or disconnected. | Check fan operation and connection; replace the fan if faulty. |
| 5681 | ACS580 | PU communication: communication errors between the drive control unit and the power unit. | Check the connection between control unit and power unit, and parameter 95.04. |
| 5682 | ACS580 | Power unit lost: connection between the control unit and the power unit is lost. | Check the connection between control unit and power unit. |
| 5691 | ACS580 | Measurement circuit ADC: measurement circuit fault. | Contact ABB. |
| 5692 | ACS580 | PU board powerfail: power unit power supply failure. | Contact ABB. |
| 5693 | ACS580 | Measurement circuit DFF: measurement circuit fault. | Contact ABB. |
| 5697 | ACS580 | Charging feedback: charging feedback signal missing. | Check the feedback signal from the charging system. |
| 5698 | ACS580 | Unknown PU fault: the power unit logic generated a fault the software does not know. | Check logic and software compatibility. |
| 6181 | ACS580 | FPGA version incompatible: firmware and FPGA versions are incompatible. | Reboot the control unit (96.08) or cycle power. If it persists, contact ABB. |
| 6200 | ACS580 | Checksum mismatch: actual parameter checksum does not match the approved checksum. | Revert parameter changes made after approval, or approve the new checksum (96.55 bits 12/13). |
| 6306 | ACS580 | FBA A mapping file: fieldbus adapter A mapping file read error. | Contact ABB. |
| 6481 | ACS580 | Task overload: internal fault. | Reboot the control unit (96.08) or cycle power. If it persists, contact ABB. |
| 6487 | ACS580 | Stack overflow: internal fault. | Reboot the control unit (96.08) or cycle power. If it persists, contact ABB. |
| 64A1 | ACS580 | Internal file load: file read error. | Reboot the control unit (96.08) or cycle power. If it persists, contact ABB. |
| 64A4 | ACS580 | Rating ID fault: rating ID load error. | Contact ABB. |
| 64A6 | ACS580 | Adaptive program: error running the adaptive program. | Check the auxiliary code. |
| 64B1 | ACS580 | Internal SSW fault: internal fault. | Reboot the control unit (96.08) or cycle power. If it persists, contact ABB. |
| 64B2 | ACS580 | User set fault: loading a user parameter set failed (set missing, not compatible, or drive switched off during loading). | Make sure a valid user parameter set exists; reload if uncertain. |
| 64B3 | ACS580 | Macro parameterization error: macro parameterization failed, for example a write to a default value that cannot be changed. | — |
| 64E1 | ACS580 | Kernel overload: operating system error. | Reboot the control unit (96.08) or cycle power. If it persists, contact ABB. |
| 6581 | ACS580 | Parameter system: parameter load or save failed. | Force a save with 96.07 and retry. |
| 6591 | ACS580 | Backup/Restore timeout: control panel or PC tool stopped communicating during backup or restore. | Check control panel or PC tool communication. |
| 65A1 | ACS580 | FBA A parameter conflict: the drive does not have a function the PLC requests, or it is not activated. | Check PLC programming and parameter groups 50 and 51. |
| 6681 | ACS580 | EFB comm loss: communication break in embedded fieldbus (EFB). | Check the fieldbus master status and cable connections to EIA-485/X5 terminals 29, 30 and 31. |
| 6682 | ACS580 | EFB config file: embedded fieldbus configuration file could not be read. | Contact ABB. |
| 6683 | ACS580 | EFB invalid parameterization: embedded fieldbus settings are inconsistent or not compatible with the protocol. | Check parameter group 58. |
| 6684 | ACS580 | EFB load fault: EFB protocol firmware could not be loaded, or its version does not match the drive firmware. | Contact ABB. |
| 6685 | ACS580 | EFB fault 2: fault reserved for the EFB protocol application. | Check the protocol documentation. |
| 6686 | ACS580 | EFB fault 3: fault reserved for the EFB protocol application. | Check the protocol documentation. |
| 6882 | ACS580 | Text 32-bit table overflow: internal fault. | Reset the fault. Contact ABB if it persists. |
| 6885 | ACS580 | Text file overflow: internal fault. | Reset the fault. Contact ABB if it persists. |
| 7081 | ACS580 | Control panel loss: control panel or PC tool selected as control location has stopped communicating. | Check panel or PC tool connection and connector; disconnect and reconnect the panel. |
| 7082 | ACS580 | I/O module comm loss: communication between I/O module and drive is not working properly. | Check the I/O module installation. |
| 7085 | ACS580 | Incompatible option module: fieldbus option module not supported. | Replace the module with a supported type. |
| 7086 | ACS580 | AI Overvoltage: overvoltage detected on an analog input; the input is temporarily switched to voltage mode. | Check AI signal levels. |
| 7121 | ACS580 | Motor stall: motor is operating in the stall region, for example because of excessive load or too small motor power. | Check motor load, drive ratings and fault function parameters. |
| 7122 | ACS580 | Motor overload: continuous average motor current is above motor nominal current. | Check the motor rotation is not obstructed and the motor torque suits the application; adjust 35.51–35.53 and 35.55–35.56. |
| 7181 | ACS580 | Brake resistor: brake resistor broken or not connected. | Check that a brake resistor is connected, its condition and its dimensioning. |
| 7183 | ACS580 | BR excess temperature: brake resistor temperature has exceeded the fault limit (43.11). | Stop the drive and let the resistor cool; check group 43 settings and the braking cycle. |
| 7191 | ACS580 | BC short circuit: short circuit in the brake chopper IGBT. | Make sure the brake resistor is connected and not damaged; check its specifications; replace the brake chopper if replaceable. |
| 7192 | ACS580 | BC IGBT excess temperature: brake chopper IGBT temperature has exceeded the internal fault limit. | Let the chopper cool; check ambient, fan, air flow, group 43 settings, braking cycle and supply voltage. |
| 7310 | ACS580 | Overspeed: motor is turning faster than the highest allowed speed (wrong min/max speed, too little braking torque, or load changes with torque reference). | Check 30.11 and 30.12, motor braking torque, torque control, and need for a brake chopper and resistor. |
| 73B0 | ACS580 | Emergency ramp failed: emergency stop did not finish within the expected time. | Check 31.32, 31.33 and the ramp times (23.11–23.15 for Off1, 23.23 for Off3). |
| 73F0 | ACS580 | Overfrequency: maximum allowed output frequency exceeded. | Check the auxiliary code, 30.13 and 30.14, and supply voltage selection 95.01. |
| 7510 | ACS580 | FBA A communication: cyclical communication with fieldbus adapter module A (or between PLC and module A) is lost. | Check fieldbus status, parameter groups 50–53, cables and that the master can communicate. |
| 8001 | ACS580 | ULC underload fault: signal has been under the user underload curve for too long. | See parameter 37.04. |
| 8002 | ACS580 | ULC overload fault: signal has been over the user overload curve for too long. | See parameter 37.03. |
| 80A0 | ACS580 | AI supervision: an analog signal is outside the limits set for the analog input. | Check the signal level, auxiliary code, wiring and the limits in group 12. |
| 80B0 | ACS580 | Signal supervision 1: fault generated by signal supervision function 1. | Check the source of the fault (parameter 32.07). |
| 80B1 | ACS580 | Signal supervision 2: fault generated by signal supervision function 2. | Check the source of the fault (parameter 32.17). |
| 80B2 | ACS580 | Signal supervision 3: fault generated by signal supervision function 3. | Check the source of the fault (parameter 32.27). |
| 80B3 | ACS580 | Signal supervision 4: fault generated by signal supervision function 4. | Check the source of the fault (parameter 32.37). |
| 80B4 | ACS580 | Signal supervision 5: fault generated by signal supervision function 5. | Check the source of the fault (parameter 32.47). |
| 80B5 | ACS580 | Signal supervision 6: fault generated by signal supervision function 6. | Check the source of the fault (parameter 32.57). |
| 9081 | ACS580 | External fault 1: fault in external device 1. | Check the external device and parameter 31.01. |
| 9082 | ACS580 | External fault 2: fault in external device 2. | Check the external device and parameter 31.03. |
| 9083 | ACS580 | External fault 3: fault in external device 3. | Check the external device and parameter 31.05. |
| 9084 | ACS580 | External fault 4: fault in external device 4. | Check the external device and parameter 31.07. |
| 9085 | ACS580 | External fault 5: fault in external device 5. | Check the external device and parameter 31.09. |
| D401 | ACS580 | Max cleaning fault: maximum number of pump cleanings reached in the set time; the pump needs manual cleaning. | Check the pump for blockages and clean it manually if needed; check 83.35–83.37. |
| D404 | ACS580 | Running dry: dry run protection is activated. | Check the pump inlet has enough water; check 82.20 and 82.21. |
| D405 | ACS580 | Pipe fill-timeout: soft pipe fill reached its timeout limit without the PID output reaching the setpoint. | Check the pipe for leakage; see 82.25 and 82.26. |
| D40C | ACS580 | Cavitation detected: the pump is not getting enough liquid. | Check the fluid level, restart the pump and see if cavitation continues; adjust 86.12–86.30 if needed. |
| FA81 | ACS580 | Safe torque off 1: STO circuit 1 is broken. | Check safety circuit connections and parameter 95.04. |
| FA82 | ACS580 | Safe torque off 2: STO circuit 2 is broken. | Check safety circuit connections and parameter 95.04. |
| FF61 | ACS580 | ID run: motor ID run was not completed. | Check motor data in group 99, no external control system connected, motor shaft not locked, and the auxiliary code; cycle the power. |
| FF63 | ACS580 | STO diagnostics failure: software internal malfunction. | Reboot the control unit (96.08) or cycle power. |
| FF81 | ACS580 | FB A force trip: a fault trip command was received through fieldbus adapter A. | Check the fault information from the PLC. |
| FF8E | ACS580 | EFB force trip: a fault trip command was received through the embedded fieldbus. | Check the fault information from the PLC. |
| 64FF | ACS580 event | Fault reset: a fault has been reset from the control panel, Drive composer, fieldbus or I/O. Informative only. | — |
| B686 | ACS580 event | Checksum mismatch: parameter checksum does not match the approved checksum. Event, informative only. | — |
| B5A0 | ACS580 event | STO event: Safe torque off is active (STO signal lost). Informative. | Check safety circuit connections. |
| A2A1 | ACS580 warning | Current calibration: current offset and gain calibration will occur at next start. Informative. | — |
| A2B1 | ACS580 warning | Overcurrent: output current has exceeded the internal fault limit; can also be caused by an earth fault or supply phase loss. | Same checks as fault 2310: motor load, acceleration times, motor and cable, insulation, group 99. |
| A2B3 | ACS580 warning | Earth leakage: load unbalance, typically an earth fault in the motor or motor cable. | Check for power factor capacitors or surge absorbers in the motor cable and measure insulation. If no earth fault is found, contact ABB. |
| A2B4 | ACS580 warning | Short circuit: short circuit in motor cable(s) or motor. | Check motor and cable for cabling errors, phasing, insulation and power factor capacitors; on frames R6–R11 check the auxiliary code. |
| A2BA | ACS580 warning | IGBT overload: excessive IGBT junction to case temperature; can be caused by a short circuit in the motor cable. | Check motor cable, ambient, air flow, fan, heatsink dust, motor power against drive power. |
| A3A1 | ACS580 warning | DC link overvoltage: DC voltage too high while the drive is stopped. | Check the supply voltage setting (95.01) and the supply voltage. ABB notes a wrong 95.01 setting may make the motor rush uncontrollably or overload the brake chopper or resistor. |
| A3A2 | ACS580 warning | DC link undervoltage: DC voltage too low while the drive is stopped. | Check the supply voltage setting (95.01) and the supply voltage. ABB notes a wrong 95.01 setting may make the motor rush uncontrollably or overload the brake chopper or resistor. |
| A3AA | ACS580 warning | DC not charged: DC circuit voltage has not yet risen to operating level. | If the problem persists, contact ABB. |
| A490 | ACS580 warning | Incorrect temperature sensor setup: temperature cannot be supervised because of wrong adapter or AO setup. | Check 35.11 and 35.21 against AO parameters 13.12 and 13.22. |
| A491 | ACS580 warning | External temperature 1: measured temperature 1 has exceeded the warning limit. | Check 35.02, the cooling of the measured equipment and 35.13. |
| A492 | ACS580 warning | External temperature 2: measured temperature 2 has exceeded the warning limit. | Check 35.03, the cooling of the measured equipment and 35.23. |
| A4A0 | ACS580 warning | Control board temperature: control unit temperature is too high (aux code 1 = thermistor broken). | Check ambient, air flow, fan and heatsink dust. Aux code 1: contact ABB for control unit replacement. |
| A4A1 | ACS580 warning | IGBT overtemperature: estimated drive IGBT temperature is excessive. | Check ambient, air flow and fan, heatsink dust, motor power against drive power. |
| A4A9 | ACS580 warning | Cooling: drive module temperature is excessive. | Check ambient temperature and derating, cooling air flow and fan, and dust in the cabinet and heatsink. |
| A4B0 | ACS580 warning | Excess temperature: power unit module temperature is excessive. | Check ambient, air flow and fan, heatsink dust, motor power against drive power. |
| A4B1 | ACS580 warning | Excess temperature difference: high temperature difference between IGBTs of different phases. | Check the motor cabling and drive module cooling. |
| A4F6 | ACS580 warning | IGBT temperature: drive IGBT temperature is excessive. | Check ambient, air flow and fan, heatsink dust, motor power against drive power. |
| A581 | ACS580 warning | Fan: cooling fan feedback missing (frame R6 or larger). | Check the auxiliary code, fan operation and connection; replace the fan if faulty. |
| A582 | ACS580 warning | Auxiliary fan missing: an auxiliary cooling fan (IP55 internal fan) is stuck or disconnected. | Check the fan and connection; replace a faulty fan; make sure the front cover is in place and tightened. |
| A5A0 | ACS580 warning | Safe torque off: STO is active, the safety circuit signal to the STO connector is lost. | Check safety circuit connections and parameter 95.04. |
| A5EA | ACS580 warning | Measurement circuit temperature: problem with the drive's internal temperature measurement. | Contact ABB. |
| A5EB | ACS580 warning | PU board powerfail: power unit power supply failure. | Contact ABB. |
| A5ED | ACS580 warning | Measurement circuit ADC: measurement circuit fault. | Contact ABB. |
| A5EE | ACS580 warning | Measurement circuit DFF: measurement circuit fault. | Contact ABB. |
| A5EF | ACS580 warning | PU state feedback: state feedback from output phases does not match control signals. | Contact ABB. |
| A5F0 | ACS580 warning | Charging feedback: charging feedback signal missing. | Check the feedback signal from the charging system. |
| A682 | ACS580 warning | Flash erase speed exceeded: the flash memory has been erased too often, shortening its life. | Avoid unnecessary forced parameter saves (96.07) and cyclic parameter writes. |
| A686 | ACS580 warning | Checksum mismatch: actual parameter checksum does not match the approved checksum. | Revert parameter changes, or approve the new checksum (96.55 bits 12/13). |
| A6A4 | ACS580 warning | Motor nominal value: motor parameters are set wrong, or the drive is not sized correctly. | Check the auxiliary code, groups 98 and 99, and that the drive suits the motor. |
| A6A5 | ACS580 warning | No motor data: parameters in group 99 have not been set. Normal during start-up until motor data is entered. | Set all required parameters in group 99. |
| A6A6 | ACS580 warning | Voltage category unselected: the voltage category has not been defined. | Set it in parameter 95.01 Supply voltage. |
| A6A7 | ACS580 warning | System time not set: timed functions cannot be used and fault log dates are wrong. | Set the time manually or connect the control panel; or disable timed functions (34.10). |
| A6B0 | ACS580 warning | User lock is open: user lock configuration parameters 96.100–96.102 are visible. | Close the user lock by entering an invalid pass code in 96.02. |
| A6B1 | ACS580 warning | User pass code not confirmed: a new pass code was entered in 96.100 but not confirmed in 96.101. | Enter the same code in 96.101, or close the user lock to cancel. |
| A6D1 | ACS580 warning | FBA A parameter conflict: the drive lacks a function the PLC requests, or it is not activated. | Check PLC programming and parameter group 50. |
| A6E5 | ACS580 warning | AI parametrization: an analog input's current/voltage hardware setting does not match the parameter settings. | Adjust the hardware setting or 12.15/12.25, then reboot the control unit. |
| A6E6 | ACS580 warning | ULC configuration: user load curve configuration error. | Check the auxiliary code and the points in group 37. |
| A780 | ACS580 warning | Motor stall: motor is operating in the stall region (for example excessive load or too small motor power). | Check motor load, drive ratings and fault function parameters. |
| A783 | ACS580 warning | Motor overload: motor current is too high. | Check for an overloaded motor; adjust 35.51–35.53 and 35.55–35.56. |
| A784 | ACS580 warning | Motor disconnect: all three output phases are disconnected from the motor. | Check switches between drive and motor are closed and all motor cables are connected. |
| A793 | ACS580 warning | BR excess temperature: brake resistor temperature has exceeded the warning limit (43.12). | Stop the drive and let the resistor cool; check group 43, resistor sizing and braking cycle. |
| A794 | ACS580 warning | BR data: brake resistor data has not been given. | Check 43.08–43.10 (the auxiliary code names the parameter). |
| A79C | ACS580 warning | BC IGBT excess temperature: brake chopper IGBT temperature has exceeded the internal warning limit. | Let the chopper cool; check ambient, fan, air flow, cabinet cooling, 43.06–43.10, braking cycle and supply voltage. |
| A7A2 | ACS580 warning | Mechanical brake opening failed: brake acknowledgement is not as expected when opening. | Check brake connection, group 44 and the acknowledgement signal. |
| A7AB | ACS580 warning | Extension I/O configuration failure: installed C-type module is not as configured, or communication is disturbed. | Check 15.02 matches 15.01; remove disturbance sources. |
| A7C1 | ACS580 warning | FBA A communication: cyclical communication with fieldbus adapter A is lost. | Check fieldbus status, groups 50–53, cables and the master. |
| A7CE | ACS580 warning | EFB comm loss: communication break in embedded fieldbus. | Check the master status and cables to EIA-485/X5 terminals 29, 30 and 31. |
| A7EE | ACS580 warning | Panel loss: control panel or PC tool selected as control location has stopped communicating. | Check the panel or PC tool connection, connector and mounting platform; reconnect the panel. |
| A88F | ACS580 warning | Cooling fan: maintenance timer limit exceeded. | Consider changing the cooling fan (05.04 shows fan running time). |
| A8A0 | ACS580 warning | AI supervision: an analog signal is outside the limits set for the analog input. | Check signal level, wiring and limits in group 12. |
| A8A1 | ACS580 warning | RO life warning: a relay output has changed state more than the recommended number of times. | Change the control unit or stop using that relay output. |
| A8A2 | ACS580 warning | RO toggle warning: a relay output is switching faster than recommended; relay life will be exceeded soon. | Connect a less frequently changing signal (10.24, 10.27 or 10.30). |
| A8B0 | ACS580 warning | ABB Signal supervision 1: warning generated by signal supervision function 1. | Check the source of the warning (parameter 32.07). |
| A8B1 | ACS580 warning | ABB Signal supervision 2: warning generated by signal supervision function 2. | Check the source of the warning (parameter 32.17). |
| A8B2 | ACS580 warning | ABB Signal supervision 3: warning generated by signal supervision function 3. | Check the source of the warning (parameter 32.27). |
| A8B3 | ACS580 warning | ABB Signal supervision 4: warning generated by signal supervision function 4. | Check the source of the warning (parameter 32.37). |
| A8B4 | ACS580 warning | ABB Signal supervision 5: warning generated by signal supervision function 5. | Check the source of the warning (parameter 32.47). |
| A8B5 | ACS580 warning | ABB Signal supervision 6: warning generated by signal supervision function 6. | Check the source of the warning (parameter 32.57). |
| A8BE | ACS580 warning | ULC overload warning: selected signal has exceeded the user overload curve. | Check for conditions raising the signal (for example motor load) and the curve in group 37. |
| A8BF | ACS580 warning | ULC underload warning: selected signal has fallen below the user underload curve. | Check for conditions lowering the signal (for example loss of load) and the curve in group 37. |
| A981 | ACS580 warning | External warning 1: fault in external device 1. | Check the external device and parameter 31.01. |
| A982 | ACS580 warning | External warning 2: fault in external device 2. | Check the external device and parameter 31.03. |
| A983 | ACS580 warning | External warning 3: fault in external device 3. | Check the external device and parameter 31.05. |
| A984 | ACS580 warning | External warning 4: fault in external device 4. | Check the external device and parameter 31.07. |
| A985 | ACS580 warning | External warning 5: fault in external device 5. | Check the external device and parameter 31.09. |
| AF88 | ACS580 warning | Season configuration warning: a season is set to start before the previous season. | Set increasing start dates in 34.60–34.63. |
| AF90 | ACS580 warning | Speed controller autotuning: the speed controller autotune did not complete. | Check the auxiliary code. |
| AFAA | ACS580 warning | Autoreset: a fault is about to be autoreset. Informative. | See parameter group 31. |
| AFE1 | ACS580 warning | Emergency stop (off2): the drive has received an emergency stop (off2) command. | Check it is safe to continue, return the emergency stop button to normal, restart the drive. |
| AFE2 | ACS580 warning | Emergency stop (off1 or off3): the drive has received an emergency stop (off1 or off3) command. | If unintentional, check the source in 21.05. |
| AFE9 | ACS580 warning | Start delay: start delay is active; the drive will start the motor after a set delay. Informative. | See parameter 21.22. |
| AFEB | ACS580 warning | Run enable missing: no run enable signal is received. | Check 20.12 and switch the signal on, or check wiring of the source. |
| AFED | ACS580 warning | Enable to rotate: the enable to rotate signal was not received within 240 s. | Switch the signal on and check 20.22. |
| AFF6 | ACS580 warning | Identification run: motor ID run will occur at next start. Informative. | — |
| AFF8 | ACS580 warning | Motor heating active: motor pre-heating current (21.16) is passing through the motor. Informative. | — |
| D501 | ACS580 warning | No more available PFC motors: no more PFC motors can start (interlocked or in Hand mode). | Check interlocks 76.81–76.84; if all motors are in use, the PFC system is too small for the demand. |
| D502 | ACS580 warning | All motors interlocked: all motors in the PFC system are interlocked. | Check interlocks 76.81–76.84. |
| D503 | ACS580 warning | VSD controlled PFC motor interlocked: the motor on the drive is interlocked and cannot start. | Remove the interlock (76.81–76.84). |
| D505 | ACS580 warning | Max cleaning warning: maximum number of pump cleanings reached in the set time; manual cleaning needed. | Check the pump for blockages, clean it manually if needed; check 83.35–83.37. |
| D506 | ACS580 warning | Pump cleaning not possible: drive must be in remote control with the start signal on. | Change control location to Auto. |
| D507 | ACS580 warning | Pump cleaning needed: dirt detection says the pump needs cleaning but automatic cleaning is not allowed. | Clean the pump manually, or start cleaning with 83.12. |
| D50A | ACS580 warning | Running dry: dry run protection is activated. | Check the pump inlet has enough water; check 82.20 and 82.21. |
| D50B | ACS580 warning | Pipe fill-timeout: soft pipe fill reached its timeout limit. | Check the pipe for leakage; see 82.25 and 82.26. |
| D511 | ACS580 warning | Cavitation control: cavitation control warning. | Check the auxiliary code, the fluid level and group 86 settings. |
| D58B | ACS580 warning | Gas pressure outside limits: compressor gas pressure is outside the limits. | Check the limits set as AI min and max values. |
| D590 | ACS580 warning | Restart delay: compressor restart delay; the drive cannot start until it has passed. | Wait, and check parameter 21.40. |
| D591 | ACS580 warning | Min. run time: compressor minimum run time; the drive runs at minimum speed during it. | Check parameter 21.41. |
| D602 | ACS580 warning | Cavitation tune completed: cavitation auto tune has finished and stopped the drive. Information only. | — |
| 0001 (fieldbus code 2310) | ACS355 | OVERCURRENT: output current has exceeded the trip level (sudden load change or stall, short acceleration time, wrong motor data, motor or drive too small, damaged motor or cables, wrong star/delta, internal fault, or noise in STO lines). | Check motor load, acceleration time (2202, 2205), motor data (group 99), sizing, motor, cables and connections. |
| 0002 (fieldbus code 3210) | ACS355 | DC OVERVOLT: DC voltage too high (trip at 420 V on 200 V drives, 840 V on 400 V drives): high or noisy supply, floating network, or during deceleration: overvoltage controller off, short deceleration time, faulty or undersized brake chopper. | Check input voltage, overvoltage controller (2005), deceleration time (2203, 2206), brake chopper and resistor. |
| 0003 (fieldbus code 4210) | ACS355 | DEV OVERTEMP: drive IGBT temperature is excessive (high ambient, blocked air flow, fan not working, or drive overload). | Check ambient, free space and air flow, fan operation. ABB allows 50% overload for one minute in ten minutes. |
| 0004 (fieldbus code 2340) | ACS355 | SHORT CIRC: short circuit in motor cable(s) or motor; also internal drive fault or noise in STO lines. | Check motor and cable insulation and the motor winding. |
| 0006 (fieldbus code 3220) | ACS355 | DC UNDERVOLT: DC voltage not sufficient (undervoltage controller off, missing input phase, blown fuse, or rectifier bridge fault). | Check input supply and fuses, undervoltage controller (2006); measure input and DC voltage (0107). |
| 0007 (fieldbus code 8110) | ACS355 | AI1 LOSS: analog input AI1 has fallen below 3021 AI1 FAULT LIMIT (signal weak or missing). | Check the signal source and wiring, and parameters 3001 and 3021. |
| 0008 (fieldbus code 8110) | ACS355 | AI2 LOSS: analog input AI2 has fallen below 3022 AI2 FAULT LIMIT (signal weak or missing). | Check the signal source and wiring, and parameter 3001. |
| 0009 (fieldbus code 4310) | ACS355 | MOT OVERTEMP: motor temperature estimate too high (excessive load, too small motor, wrong start-up data), or measured motor temperature above 3504 FAULT LIMIT. | Check motor ratings, load, cooling and start-up data; let the motor cool down. |
| 0010 (fieldbus code 5300) | ACS355 | PANEL LOSS: control panel selected as control location has stopped communicating. | Check panel connection and connector, parameter 3002; refit the panel. |
| 0011 (fieldbus code FF84) | ACS355 | ID RUN FAIL: motor ID run did not complete. | Check motor connection, group 99, and that 2002 is at least 80% of motor nominal speed (9908). |
| 0012 (fieldbus code 7121) | ACS355 | MOTOR STALL: motor is operating in the stall region (excessive load or too small motor). | Check motor load, drive ratings and 3010–3012. |
| 0014 (fieldbus code 9000) | ACS355 | EXT FAULT 1: external fault 1. | Check external devices and parameter 3003. |
| 0015 (fieldbus code 9001) | ACS355 | EXT FAULT 2: external fault 2. | Check external devices and parameter 3004. |
| 0016 (fieldbus code 2330) | ACS355 | EARTH FAULT: earth (ground) fault in motor or motor cable, or a drive internal fault. | Check motor and motor cable; cable must not exceed maximum length. ABB notes disabling earth fault may damage the drive. |
| 0017 (fieldbus code FF6A) | ACS355 | UNDERLOAD: motor load too low, for example a release mechanism in the driven equipment. | Check the driven equipment, fault function parameters, motor power against drive power. |
| 0018 (fieldbus code 5210) | ACS355 | THERM FAIL: drive temperature exceeds the operating level of the thermistor, or the internal thermistor is open or shorted. | Check the ambient temperature is not too low. Internal fault: replace the drive. |
| 0021 (fieldbus code 2211) | ACS355 | CURR MEAS: drive internal fault, current measurement out of range. | Replace the drive. |
| 0022 (fieldbus code 3130) | ACS355 | SUPPLY PHASE: DC voltage oscillating because an input phase is missing or a fuse is blown (ripple above 14% of nominal). | Check input fuses, installation, supply imbalance, load, and 2619 DC STABILIZER. |
| 0023 (fieldbus code 7301) | ACS355 | ENCODER ERR: communication fault between pulse encoder and interface module, or module and drive. | Check encoder, wiring, interface module and group 50. |
| 0024 (fieldbus code 7310) | ACS355 | OVERSPEED: motor turning faster than 120% of the highest allowed speed. | Check min/max speed (2001, 2002) or frequency (2007, 2008), braking torque, torque control, brake chopper and resistor. |
| 0027 (fieldbus code 630F) | ACS355 | CONFIG FILE: internal configuration file error. | Replace the drive. |
| 0028 (fieldbus code 7510) | ACS355 | SERIAL 1 ERR: fieldbus communication break. | Check fieldbus status, 3018 and 3019, connections and noise, and that the master can communicate. |
| 0029 (fieldbus code 6306) | ACS355 | EFB CON FILE: error reading the embedded fieldbus configuration file. | See the fieldbus user's manual. |
| 0030 (fieldbus code FF90) | ACS355 | FORCE TRIP: trip command received from fieldbus. | See the fieldbus user's manual. |
| 0034 (fieldbus code FF56) | ACS355 | MOTOR PHASE: motor circuit fault, missing motor phase or motor thermistor relay fault. | Check motor, motor cable and thermistor relay (if used). |
| 0035 (fieldbus code FF95) | ACS355 | OUTP WIRING: input power cable connected to the drive's motor terminals. Can also show on a delta grounded supply with high motor cable capacitance. | Check input power is not connected to the drive output. Can be disabled with 3023. |
| 0036 (fieldbus code 630F) | ACS355 | INCOMPATIBLE SW: loaded software is not compatible with the drive. | Contact ABB. |
| 0037 (fieldbus code 4110) | ACS355 | CB OVERTEMP: control board overheated (95 °C on IP20, 102 °C on IP66), with 3024 set to fault. | Check ambient, fan, air flow and cabinet cooling. |
| 0044 (fieldbus code FFA0) | ACS355 | SAFE TORQUE OFF: STO requested and working; 3025 STO OPERATION set to fault. | If unexpected, check STO safety circuit cabling (terminals X1C). Reset the fault before starting. |
| 0045 (fieldbus code FFA1) | ACS355 | STO1 LOST: STO channel 1 has not de-energized but channel 2 has (damaged contacts or short circuit). | Check STO circuit cabling and contacts. |
| 0046 (fieldbus code FFA2) | ACS355 | STO2 LOST: STO channel 2 has not de-energized but channel 1 has (damaged contacts or short circuit). | Check STO circuit cabling and contacts. |
| 0101 (fieldbus code FF55) | ACS355 | SERF CORRUPT: drive internal error. | Replace the drive. |
| 0103 (fieldbus code FF55) | ACS355 | SERF MACRO: drive internal error (ABB's table gives one shared cause and action for 0101 and 0103). | Replace the drive. |
| 0201 (fieldbus code 6100) | ACS355 | DSP T1 OVERLOAD: drive internal error. | If fieldbus is used, check it; note the code and contact ABB. |
| 0202 (fieldbus code 6100) | ACS355 | DSP T2 OVERLOAD: drive internal error (ABB's table gives one shared cause and action for 0201–0204). | If fieldbus is used, check it; note the code and contact ABB. |
| 0203 (fieldbus code 6100) | ACS355 | DSP T3 OVERLOAD: drive internal error (ABB's table gives one shared cause and action for 0201–0204). | If fieldbus is used, check it; note the code and contact ABB. |
| 0204 (fieldbus code 6100) | ACS355 | DSP STACK ERROR: drive internal error (ABB's table gives one shared cause and action for 0201–0204). | If fieldbus is used, check it; note the code and contact ABB. |
| 0206 (fieldbus code 5000) | ACS355 | CB ID ERROR: drive internal error. | Replace the drive. |
| 1000 (fieldbus code 6320) | ACS355 | PAR HZRPM: wrong speed or frequency limit setting. | Check 2001 < 2002, 2007 < 2008, and the ratios to 9907/9908 are in range. |
| 1003 (fieldbus code 6320) | ACS355 | PAR AI SCALE: wrong analog input scaling. | Check 1301 < 1302 and 1304 < 1305. |
| 1004 (fieldbus code 6320) | ACS355 | PAR AO SCALE: wrong analog output scaling. | Check 1504 < 1505. |
| 1005 (fieldbus code 6320) | ACS355 | PAR PCU 2: wrong motor nominal power setting. | Check 9909 MOTOR NOM POWER against motor current and voltage. |
| 1006 (fieldbus code 6320) | ACS355 | PAR EXT RO: wrong relay output extension parameters. | Check MREL-01 module is connected (0181) and relay outputs 1402, 1403, 1410. |
| 1007 (fieldbus code 6320) | ACS355 | PAR FBUSMISS: fieldbus control has not been activated. | Check fieldbus parameter settings. |
| 1009 (fieldbus code 6320) | ACS355 | PAR PCU 1: wrong motor nominal speed or frequency setting. | Check 9907, 9908 and 9913. |
| 1015 (fieldbus code 6320) | ACS355 | PAR USER U/F: wrong voltage to frequency (U/f) ratio setting. | Check 2610–2617. |
| 1017 (fieldbus code 6320) | ACS355 | PAR SETUP 1: only two of MTAC-01 encoder module, frequency input and frequency output can be used at the same time. | Disable the frequency output, frequency input or encoder. |
| 2001 | ACS355 alarm | OVERCURRENT: output current limit controller is active; high ambient temperature. | Check ambient; load capacity drops above 40 °C. See fault 0001. |
| 2002 | ACS355 alarm | OVERVOLTAGE: DC overvoltage controller is active. | See fault 0002. |
| 2003 | ACS355 alarm | UNDERVOLTAGE: DC undervoltage controller is active. | See fault 0006. |
| 2004 | ACS355 alarm | DIR LOCK: change of direction is not allowed. | Check parameter 1003 DIRECTION. |
| 2005 | ACS355 alarm | IO COMM: fieldbus communication break. | Check fieldbus status, fault function parameters, connections and the master. |
| 2006 | ACS355 alarm | AI1 LOSS: analog input AI1 below the 3021 limit. | See fault 0007. |
| 2007 | ACS355 alarm | AI2 LOSS: analog input AI2 below the 3022 limit. | See fault 0008. |
| 2008 | ACS355 alarm | PANEL LOSS: control panel selected as control location has stopped communicating. | See fault 0010. |
| 2009 | ACS355 alarm | DEVICE OVERTEMP: drive IGBT temperature is excessive. | Check ambient, air flow and fan, motor power against drive power. |
| 2010 | ACS355 alarm | MOTOR TEMP: motor temperature too high (or appears so), or measured temperature above 3503 ALARM LIMIT. | See fault 0009. |
| 2011 | ACS355 alarm | UNDERLOAD: motor load is too low. | Check the driven equipment, fault function parameters, motor power against drive power. |
| 2012 | ACS355 alarm | MOTOR STALL: motor operating in the stall region. | Check motor load, drive ratings and fault function parameters. |
| 2013 | ACS355 alarm | AUTORESET: automatic reset alarm. | Check parameter group 31. |
| 2018 | ACS355 alarm | PID SLEEP: sleep function has entered sleeping mode. | See parameter groups 40 and 41. |
| 2019 | ACS355 alarm | ID RUN: motor identification run is on. Normal during start-up. | Wait until the drive shows identification is completed. |
| 2021 | ACS355 alarm | START ENABLE 1 MISSING: no Start enable 1 signal received. | Check 1608, digital inputs and fieldbus settings. |
| 2022 | ACS355 alarm | START ENABLE 2 MISSING: no Start enable 2 signal received. | Check 1609, digital inputs and fieldbus settings. |
| 2023 | ACS355 alarm | EMERGENCY STOP: drive received an emergency stop command and ramps to stop (2208). | Check it is safe to continue, then return the emergency stop button to normal. |
| 2024 | ACS355 alarm | ENCODER ERROR: communication fault between pulse encoder and interface module, or module and drive. | Check encoder, wiring, module and group 50. |
| 2025 | ACS355 alarm | FIRST START: motor identification magnetization is on. Normal during start-up. | Wait until the drive shows identification is completed. |
| 2026 | ACS355 alarm | INPUT PHASE LOSS: DC voltage oscillating because an input phase is missing or a fuse is blown. | Check input fuses, supply imbalance and fault function parameters. |
| 2029 | ACS355 alarm | MOTOR BACK EMF: a permanent magnet motor is rotating with start mode DC MAGN selected; it cannot be magnetized with DC. | To start a rotating motor, set 2101 START FUNCTION to 1 (AUTO); otherwise the drive starts after the motor stops. |
| 2035 | ACS355 alarm | SAFE TORQUE OFF: STO requested and working; 3025 set to alarm. | If unexpected, check STO cabling (X1C). Toggle the start signal if STO was used while running. |
| 5001 (A5001 on basic panel) | ACS355 panel alarm | Drive is not responding. | Check panel connection. |
| 5002 (A5002 on basic panel) | ACS355 panel alarm | Incompatible communication profile. | Contact ABB. |
| 5010 (A5010 on basic panel) | ACS355 panel alarm | Corrupted panel parameter backup file. | Retry parameter upload or download. |
| 5011 (A5011 on basic panel) | ACS355 panel alarm | Drive is controlled from another source. | Change drive control to local control mode. |
| 5012 (A5012 on basic panel) | ACS355 panel alarm | Direction of rotation is locked. | Enable change of direction (1003). |
| 5013 (A5013 on basic panel) | ACS355 panel alarm | Panel control disabled because start inhibit is active. | Reset the emergency stop or remove the 3-wire stop command before starting from the panel. |
| 5014 (A5014 on basic panel) | ACS355 panel alarm | Panel control disabled because of a drive fault. | Reset the drive fault and retry. |
| 5015 (A5015 on basic panel) | ACS355 panel alarm | Panel control disabled because local control mode lock is active. | Deactivate the lock (1606) and retry. |
| 5018 (A5018 on basic panel) | ACS355 panel alarm | Parameter default value not found. | Contact ABB. |
| 5019 (A5019 on basic panel) | ACS355 panel alarm | Writing a non-zero parameter value is prohibited. | Only parameter reset is allowed. |
| 5020 (A5020 on basic panel) | ACS355 panel alarm | Parameter or group does not exist, or value is inconsistent. | Contact ABB. |
| 5021 (A5021 on basic panel) | ACS355 panel alarm | Parameter or group is hidden. | Contact ABB. |
| 5022 (A5022 on basic panel) | ACS355 panel alarm | Parameter is write protected. | The value is read-only. |
| 5023 (A5023 on basic panel) | ACS355 panel alarm | Parameter change not allowed while the drive is running. | Stop the drive, then change the value. |
| 5024 (A5024 on basic panel) | ACS355 panel alarm | Drive is executing a task. | Wait until the task is completed. |
| 5025 (A5025 on basic panel) | ACS355 panel alarm | Software is being uploaded or downloaded. | Wait until upload/download is complete. |
| 5026 (A5026 on basic panel) | ACS355 panel alarm | Value is at or below minimum limit. | Contact ABB. |
| 5027 (A5027 on basic panel) | ACS355 panel alarm | Value is at or above maximum limit. | Contact ABB. |
| 5028 (A5028 on basic panel) | ACS355 panel alarm | Invalid value. | Contact ABB. |
| 5029 (A5029 on basic panel) | ACS355 panel alarm | Memory is not ready. | Retry. |
| 5030 (A5030 on basic panel) | ACS355 panel alarm | Invalid request. | Contact ABB. |
| 5031 (A5031 on basic panel) | ACS355 panel alarm | Drive not ready for operation, for example low DC voltage. | Check input power supply. |
| 5032 (A5032 on basic panel) | ACS355 panel alarm | Parameter error. | Contact ABB. |
| 5040 (A5040 on basic panel) | ACS355 panel alarm | Parameter download error: selected parameter set is not in the backup file. | Upload before download. |
| 5041 (A5041 on basic panel) | ACS355 panel alarm | Parameter backup file does not fit into memory. | Contact ABB. |
| 5042 (A5042 on basic panel) | ACS355 panel alarm | Parameter download error: selected parameter set is not in the backup file. | Upload before download. |
| 5043 (A5043 on basic panel) | ACS355 panel alarm | No start inhibit. | — |
| 5044 (A5044 on basic panel) | ACS355 panel alarm | Parameter backup file restoring error. | Check the file is compatible with the drive. |
| 5050 (A5050 on basic panel) | ACS355 panel alarm | Parameter upload aborted. | Retry upload. |
| 5051 (A5051 on basic panel) | ACS355 panel alarm | File error. | Contact ABB. |
| 5052 (A5052 on basic panel) | ACS355 panel alarm | Parameter upload has failed. | Retry upload. |
| 5060 (A5060 on basic panel) | ACS355 panel alarm | Parameter download aborted. | Retry download. |
| 5062 (A5062 on basic panel) | ACS355 panel alarm | Parameter download has failed. | Retry download. |
| 5070 (A5070 on basic panel) | ACS355 panel alarm | Panel backup memory write error. | Contact ABB. |
| 5071 (A5071 on basic panel) | ACS355 panel alarm | Panel backup memory read error. | Contact ABB. |
| 5080 (A5080 on basic panel) | ACS355 panel alarm | Not allowed: drive is not in local control mode. | Switch to local control mode. |
| 5081 (A5081 on basic panel) | ACS355 panel alarm | Not allowed because of an active fault. | Check the cause and reset the fault. |
| 5083 (A5083 on basic panel) | ACS355 panel alarm | Not allowed: parameter lock is on. | Check 1602 PARAMETER LOCK. |
| 5084 (A5084 on basic panel) | ACS355 panel alarm | Not allowed: drive is performing a task. | Wait and retry. |
| 5085 (A5085 on basic panel) | ACS355 panel alarm | Parameter download between drives failed. | Check both drives are the same type (ACS355). |
| 5086 (A5086 on basic panel) | ACS355 panel alarm | Parameter download between drives failed. | Check both drives have the same type designation. |
| 5087 (A5087 on basic panel) | ACS355 panel alarm | Parameter download failed: parameter sets incompatible. | Check drive information in group 33 is the same. |
| 5088 (A5088 on basic panel) | ACS355 panel alarm | Operation failed: drive memory error. | Contact ABB. |
| 5089 (A5089 on basic panel) | ACS355 panel alarm | Download failed: CRC error. | Contact ABB. |
| 5090 (A5090 on basic panel) | ACS355 panel alarm | Download failed: data processing error. | Contact ABB. |
| 5091 (A5091 on basic panel) | ACS355 panel alarm | Operation failed: parameter error. | Contact ABB. |
| 5092 (A5092 on basic panel) | ACS355 panel alarm | Parameter download failed: parameter sets incompatible. | Check drive information in group 33 is the same. |
| 1 (F0001 on basic panel) | ACS550 | OVERCURRENT: output current is excessive. | Check motor load, acceleration time (2202, 2205), motor, motor cables and connections. |
| 2 (F0002 on basic panel) | ACS550 | DC OVERVOLT: intermediate circuit DC voltage is excessive. | Check supply for overvoltage, deceleration time (2203, 2206), brake chopper size, and overvoltage controller ON (2005). |
| 3 (F0003 on basic panel) | ACS550 | DEV OVERTEMP: drive heatsink overheated (115 °C on R1–R4, 125 °C on R5–R6). | Check fan, air flow, dust on heatsink, ambient temperature, motor load. |
| 4 (F0004 on basic panel) | ACS550 | SHORT CIRC: fault current. | Check for a short circuit in motor cable(s) or motor, and supply disturbances. |
| 6 (F0006 on basic panel) | ACS550 | DC UNDERVOLT: intermediate circuit DC voltage is not sufficient. | Check for a missing input phase, blown fuse, low mains voltage. |
| 7 (F0007 on basic panel) | ACS550 | AI1 LOSS: analog input 1 is below AI1 FAULT LIMIT (3021). | Check the input source and connection, 3021 and 3001. |
| 8 (F0008 on basic panel) | ACS550 | AI2 LOSS: analog input 2 is below AI2 FAULT LIMIT (3022). | Check the input source and connection, 3022 and 3001. |
| 9 (F0009 on basic panel) | ACS550 | MOT OVERTEMP: motor is too hot (drive estimate or temperature feedback). | Check for an overloaded motor, 3005–3009, temperature sensors and group 35. |
| 10 (F0010 on basic panel) | ACS550 | PANEL LOSS: panel communication lost while in local control, or in remote control set to take commands from the panel. | Check communication lines, 3002, and groups 10 and 11. |
| 11 (F0011 on basic panel) | ACS550 | ID RUN FAIL: motor ID run was not completed. | Check motor connections and 9905–9909. |
| 12 (F0012 on basic panel) | ACS550 | MOTOR STALL: motor or process stall, motor in the stall region. | Check for excessive load, too small motor, and 3010–3012. |
| 14 (F0014 on basic panel) | ACS550 | EXT FAULT 1: digital input set for external fault 1 is active. | See parameter 3003. |
| 15 (F0015 on basic panel) | ACS550 | EXT FAULT 2: digital input set for external fault 2 is active. | See parameter 3004. |
| 16 (F0016 on basic panel) | ACS550 | EARTH FAULT: possible ground fault in the motor or motor cables. More sensitive when stopped; can give false trips. | Check input wiring and motor cable length; detection level 3028. ABB notes disabling it (3023, 3017) may void the warranty. |
| 18 (F0018 on basic panel) | ACS550 | THERM FAIL: internal fault, drive temperature thermistor open or shorted. | Contact ABB. |
| 19 (F0019 on basic panel) | ACS550 | OPEX LINK: internal fault on the fiber optic link between control and OINT boards. | Contact ABB. |
| 20 (F0020 on basic panel) | ACS550 | OPEX PWR: internal fault, very low voltage on the OINT power supply. | Contact ABB. |
| 21 (F0021 on basic panel) | ACS550 | CURR MEAS: internal fault, current measurement out of range. | Contact ABB. |
| 22 (F0022 on basic panel) | ACS550 | SUPPLY PHASE: ripple voltage in the DC link is too high. | Check for a missing mains phase or blown fuse. |
| 23 (F0023 on basic panel) | ACS550 | ENCODER ERR: no valid encoder signal. | Check encoder connection, logic levels, OTAC-01 module, 5001 PULSE NR and 5002. |
| 24 (F0024 on basic panel) | ACS550 | OVERSPEED: motor speed above 120% of the larger of 2001 and 2002. | Check 2001 and 2002, braking torque, torque control, brake chopper and resistor. |
| 26 (F0026 on basic panel) | ACS550 | DRIVE ID: internal fault, configuration block drive ID not valid. | Contact ABB. |
| 27 (F0027 on basic panel) | ACS550 | CONFIG FILE: internal configuration file has an error. | Contact ABB. |
| 28 (F0028 on basic panel) | ACS550 | SERIAL 1 ERR: fieldbus communication has timed out. | Check 3018 and 3019, group 51 or 53, connections and noise. |
| 29 (F0029 on basic panel) | ACS550 | EFB CON FILE: error reading the embedded fieldbus configuration file. | — |
| 30 (F0030 on basic panel) | ACS550 | FORCE TRIP: fault trip forced by the fieldbus. | See the fieldbus user's manual. |
| 31 (F0031 on basic panel) | ACS550 | EFB 1: reserved for the embedded fieldbus protocol; meaning depends on the protocol. | — |
| 32 (F0032 on basic panel) | ACS550 | EFB 2: reserved for the embedded fieldbus protocol; meaning depends on the protocol (description shared with 31 EFB 1). | — |
| 33 (F0033 on basic panel) | ACS550 | EFB 3: reserved for the embedded fieldbus protocol; meaning depends on the protocol (description shared with 31 EFB 1). | — |
| 34 (F0034 on basic panel) | ACS550 | MOTOR PHASE: one motor phase is lost. | Check motor, motor cable, thermal relay (if used); can be an internal fault. |
| 35 (F0035 on basic panel) | ACS550 | OUTP WIRING: input power cable connected to the drive's motor terminals. Can be falsely declared on a delta grounded supply with large cable capacitance. | Check input power connections and grounding. Can be disabled with 3023. |
| 36 (F0036 on basic panel) | ACS550 | INCOMPATIBLE SW: the drive cannot use the loaded software. | Call ABB support. |
| 37 (F0037 on basic panel) | ACS550 | CB OVERTEMP: control board overheated (trip at 88 °C). Not for OMIO control boards. | Check ambient temperature, fan, air flow. |
| 38 (F0038 on basic panel) | ACS550 | USER LOAD CURVE: condition in 3701 has been valid longer than 3703. | — |
| 101…199 | ACS550 | SYSTEM ERROR: error internal to the drive. | Contact ABB and report the error number. |
| 201…299 | ACS550 | SYSTEM ERROR: error in the system. | Contact ABB and report the error number. |
| UNKNOWN DRIVE TYPE | ACS550 | Wrong type of control panel connected (supports another drive, not the ACS550). | — |
| 1000 (F1000 on basic panel) | ACS550 | PAR HZRPM: speed or frequency limit parameters are inconsistent. | Check 2001 < 2002, 2007 < 2008, and ratios to 9907/9908. |
| 1001 (F1001 on basic panel) | ACS550 | PAR PFC REF NEG: 2007 MINIMUM FREQ is negative while PFC (8123) is active. | — |
| 1003 (F1003 on basic panel) | ACS550 | PAR AI SCALE: analog input scaling inconsistent. | Check 1301 < 1302 and 1304 < 1305. |
| 1004 (F1004 on basic panel) | ACS550 | PAR AO SCALE: analog output scaling inconsistent. | Check 1504 < 1505 and 1510 < 1511. |
| 1005 (F1005 on basic panel) | ACS550 | PAR PCU 2: motor nominal kVA or power inconsistent. | Check 9905, 9906 and 9909. |
| 1006 (F1006 on basic panel) | ACS550 | PAR EXT RO: extension relay module not connected but 1410–1412 are non-zero. | — |
| 1007 (F1007 on basic panel) | ACS550 | PAR FIELDBUS MISSING: a parameter is set for fieldbus control but 9802 COMM PROT SEL = 0. | — |
| 1008 (F1008 on basic panel) | ACS550 | PAR PFC MODE: 9904 must be 3 (SCALAR:FREQ) when PFC (8123) is active. | — |
| 1009 (F1009 on basic panel) | ACS550 | PAR PCU 1: motor nominal frequency or speed inconsistent. | Check 9907 and 9908. |
| 1012 (F1012 on basic panel) | ACS550 | PAR PFC IO 1: not enough relays set for PFC, or conflict between group 14, 8117 and 8118. | — |
| 1013 (F1013 on basic panel) | ACS550 | PAR PFC IO 2: number of PFC motors (8127) does not match group 14 and 8118. | — |
| 1014 (F1014 on basic panel) | ACS550 | PAR PFC IO 3: the drive cannot allocate an interlock digital input for each PFC motor (8120, 8127). | — |
| 1016 (F1016 on basic panel) | ACS550 | PAR USER LOAD C: user load curve parameters inconsistent. | Check load frequencies 3704 < 3707 < 3710 < 3713 < 3716 and each low torque below its high torque. |
| 2001 (A2001) | ACS550 alarm | OVERCURRENT: current limiting controller is active. | Check motor load, acceleration time (2202, 2205), motor, cables and connections. |
| 2002 (A2002) | ACS550 alarm | OVERVOLTAGE: overvoltage controller is active. | Check supply for overvoltage and deceleration time (2203, 2206). |
| 2003 (A2003) | ACS550 alarm | UNDERVOLTAGE: undervoltage controller is active. | Check for undervoltage on mains. |
| 2004 (A2004) | ACS550 alarm | DIR LOCK: the direction change is not allowed. | Do not change direction, or allow it in 1003 (if reverse is safe). |
| 2005 (A2005) | ACS550 alarm | IO COMM: fieldbus communication has timed out. | Check 3018 and 3019, group 51 or 53, connections and noise. |
| 2006 (A2006) | ACS550 alarm | AI1 LOSS: analog input 1 lost or below the minimum. | Check input source and connections, 3021 and 3001. |
| 2007 (A2007) | ACS550 alarm | AI2 LOSS: analog input 2 lost or below the minimum. | Check input source and connections, 3022 and 3001. |
| 2008 (A2008) | ACS550 alarm | PANEL LOSS: panel communication lost (local control, or remote set to take panel commands). | Check communication lines, 3002, and groups 10 and 11. |
| 2009 (A2009) | ACS550 alarm | DEVICE OVERTEMP: drive heatsink is hot (100 °C R1–R4, 110 °C R5–R6); a DEV OVERTEMP fault may be near. | Check fan, air flow, heatsink dust, ambient, motor load. |
| 2010 (A2010) | ACS550 alarm | MOTOR TEMP: motor is hot; a MOT OVERTEMP fault may be near. | Check for overload, 3005–3009, sensors and group 35. |
| 2012 (A2012) | ACS550 alarm | MOTOR STALL: motor in the stall region; a MOTOR STALL fault may be near. | — |
| 2013 (A2013) | ACS550 alarm | AUTORESET: the drive is about to auto-reset a fault, which may start the motor. | Use group 31 to control automatic reset. |
| 2014 (A2014) | ACS550 alarm | AUTOCHANGE: PFC autochange function is active. | Use group 81 to control PFC. |
| 2015 (A2015) | ACS550 alarm | PFC I LOCK: PFC interlocks are active; the drive cannot start the motor(s). | — |
| 2018 (A2018) | ACS550 alarm | PID SLEEP: PID sleep is active; the motor could accelerate when it ends. | Use 4022–4026 or 4122–4126. |
| 2019 (A2019) | ACS550 alarm | ID RUN: performing ID run. | — |
| 2021 (A2021) | ACS550 alarm | START ENABLE 1 MISSING: the Start Enable 1 signal is missing. | Check 1608, digital input configuration and communication settings. |
| 2022 (A2022) | ACS550 alarm | START ENABLE 2 MISSING: the Start Enable 2 signal is missing. | Check 1609, digital input configuration and communication settings. |
| 2023 (A2023) | ACS550 alarm | EMERGENCY STOP: emergency stop activated. | — |
| 2024 (A2024) | ACS550 alarm | ENCODER ERROR: no valid encoder signal. | Check encoder connection, logic levels, OTAC-01, 5001 and 5002. |
| 2025 (A2025) | ACS550 alarm | FIRST START: First Start evaluation of motor characteristics. Normal the first time after motor data is entered or changed. | — |
| 2027 (A2027) | ACS550 alarm | USER LOAD CURVE: condition in 3701 valid longer than half the time in 3703. | — |
| 2028 (A2028) | ACS550 alarm | START DELAY: shown during the start delay (2113). | — |
| 5001 (A5001 on basic panel) | ACS550 panel alarm | Drive is not responding. | — |
| 5002 (A5002 on basic panel) | ACS550 panel alarm | The communication profile is incompatible with the drive. | — |
| 5010 (A5010 on basic panel) | ACS550 panel alarm | The panel's parameter backup file is corrupted. | — |
| 5011 (A5011 on basic panel) | ACS550 panel alarm | Drive is controlled from another source. | — |
| 5012 (A5012 on basic panel) | ACS550 panel alarm | Rotation direction is locked. | — |
| 5013 (A5013 on basic panel) | ACS550 panel alarm | Button disabled because start is inhibited. | — |
| 5014 (A5014 on basic panel) | ACS550 panel alarm | Button disabled because the drive is faulted. | — |
| 5015 (A5015 on basic panel) | ACS550 panel alarm | Button disabled because local mode lock is on. | — |
| 5018 (A5018 on basic panel) | ACS550 panel alarm | Parameter default value can't be found. | — |
| 5019 (A5019 on basic panel) | ACS550 panel alarm | Writing a non-zero value is prohibited (only zero can be written). | — |
| 5020 (A5020 on basic panel) | ACS550 panel alarm | Group or parameter does not exist, or parameter value is inconsistent. | — |
| 5021 (A5021 on basic panel) | ACS550 panel alarm | Group or parameter is hidden. | — |
| 5022 (A5022 on basic panel) | ACS550 panel alarm | Group or parameter is write protected. | — |
| 5023 (A5023 on basic panel) | ACS550 panel alarm | Modification not allowed while the drive is running. | — |
| 5024 (A5024 on basic panel) | ACS550 panel alarm | Drive is busy, try again. | — |
| 5025 (A5025 on basic panel) | ACS550 panel alarm | Write not allowed while upload or download is in progress. | — |
| 5026 (A5026 on basic panel) | ACS550 panel alarm | Value is at or below low limit. | — |
| 5027 (A5027 on basic panel) | ACS550 panel alarm | Value is at or above high limit. | — |
| 5028 (A5028 on basic panel) | ACS550 panel alarm | Value is invalid (not in the list of allowed values). | — |
| 5029 (A5029 on basic panel) | ACS550 panel alarm | Memory is not ready, try again. | — |
| 5030 (A5030 on basic panel) | ACS550 panel alarm | Request is invalid. | — |
| 5031 (A5031 on basic panel) | ACS550 panel alarm | Drive is not ready, for example due to low DC voltage. | — |
| 5032 (A5032 on basic panel) | ACS550 panel alarm | Parameter error was detected. | — |
| 5040 (A5040 on basic panel) | ACS550 panel alarm | Selected parameter set can't be found in the current parameter backup. | — |
| 5041 (A5041 on basic panel) | ACS550 panel alarm | Parameter backup doesn't fit into memory. | — |
| 5042 (A5042 on basic panel) | ACS550 panel alarm | Selected parameter set can't be found in the current parameter backup. | — |
| 5043 (A5043 on basic panel) | ACS550 panel alarm | No start inhibit was granted. | — |
| 5044 (A5044 on basic panel) | ACS550 panel alarm | Parameter backup versions do not match. | — |
| 5050 (A5050 on basic panel) | ACS550 panel alarm | Parameter upload was aborted. | — |
| 5051 (A5051 on basic panel) | ACS550 panel alarm | File error was detected. | — |
| 5052 (A5052 on basic panel) | ACS550 panel alarm | Parameter upload attempt has failed. | — |
| 5060 (A5060 on basic panel) | ACS550 panel alarm | Parameter download was aborted. | — |
| 5062 (A5062 on basic panel) | ACS550 panel alarm | Parameter download attempt has failed. | — |
| 5070 (A5070 on basic panel) | ACS550 panel alarm | Panel backup memory write error. | — |
| 5071 (A5071 on basic panel) | ACS550 panel alarm | Panel backup memory read error. | — |
| 5080 (A5080 on basic panel) | ACS550 panel alarm | Not allowed because the drive is not in local mode. | — |
| 5081 (A5081 on basic panel) | ACS550 panel alarm | Not allowed because a fault is active. | — |
| 5083 (A5083 on basic panel) | ACS550 panel alarm | Not allowed because parameter lock is not open. | — |
| 5084 (A5084 on basic panel) | ACS550 panel alarm | Not allowed because the drive is busy, try again. | — |
| 5085 (A5085 on basic panel) | ACS550 panel alarm | Download not allowed: drive types are incompatible. | — |
| 5086 (A5086 on basic panel) | ACS550 panel alarm | Download not allowed: drive models are incompatible. | — |
| 5087 (A5087 on basic panel) | ACS550 panel alarm | Download not allowed: parameter sets do not match. | — |
| 5088 (A5088 on basic panel) | ACS550 panel alarm | Operation failed: drive memory error. | — |
| 5089 (A5089 on basic panel) | ACS550 panel alarm | Download failed: CRC error. | — |
| 5090 (A5090 on basic panel) | ACS550 panel alarm | Download failed: data processing error. | — |
| 5091 (A5091 on basic panel) | ACS550 panel alarm | Operation failed: parameter error. | — |
| 5092 (A5092 on basic panel) | ACS550 panel alarm | Download failed: parameter sets do not match. | — |
Good to know
- ACS355: the four-digit number in brackets after each fault (for example 2310 for OVERCURRENT) is the fieldbus code. To show alarms on the panel, set 1610 DISPLAY ALARMS to 1 (YES). The last faults are in 0401, 0412 and 0413.
- ACS550: faults shown with a flashing red LED reset only by turning the power off for 5 minutes. For a steady red LED, fix the problem and press RESET or turn the power off for 5 minutes. The last three faults are in 0401, 0412 and 0413.
- ACS580: warnings do not need a reset and stop showing when the cause ends. Some faults need a control unit reboot (power off and on, or 96.08 Control board boot). Many events also have an auxiliary code that helps find the cause; the last 32 faults and 32 warnings are in the event log.
- Rows marked panel alarm (A5xxx) come from the basic control panel itself, not the drive.
- ABB's manuals tell you to replace the drive or contact ABB for internal faults such as ACS355 0021 CURR MEAS or 0027 CONFIG FILE, and ACS550 18–21 and 26–27.
हिंदी में
ABB VFD (ड्राइव) के फ़ॉल्ट कोड ABB के अपने मैनुअल से। हर सीरीज़ में कोड अलग है: ज़्यादा करंट ACS580 में 2310, ACS355 में 0001 और ACS550 में फ़ॉल्ट 1 है। 3210 मतलब DC वोल्टेज ज़्यादा, 3220 मतलब DC वोल्टेज कम, 4210 मतलब IGBT ज़्यादा गरम, 2330 मतलब अर्थ (ग्राउंड) लीकेज।
- ड्राइव के लेबल पर सीरीज़ देखें (ACS355, ACS550 या ACS580)।
- कोड का मतलब नीचे उसी सीरीज़ की लाइन में देखें।
- ABB के अनुसार ड्राइव का काम सिर्फ़ योग्य इलेक्ट्रीशियन करे।
- कारण ठीक करने के बाद पैनल से RESET करें। ध्यान दें: बाहर से स्टार्ट कमांड चालू हो तो रीसेट के बाद मोटर तुरंत चल सकती है (ACS550 मैनुअल की चेतावनी)।
Questions people ask
What is fault 2310 in an ABB drive?
Overcurrent. On the ACS580, output current went above the internal fault limit; ABB says an earth fault or a supply phase loss can also cause it. On the ACS355 the same trip shows as fault 0001 OVERCURRENT, and 2310 is its fieldbus code.
What is fault 3210 in ABB ACS580?
DC link overvoltage: the intermediate circuit DC voltage is too high. ABB's first checks are that overvoltage control (30.30) is on, the supply voltage matches the drive, the deceleration time, and the brake chopper and resistor if present.
Why do ABB ACS355 and ACS550 show different numbers for the same fault?
Each series has its own code list. ACS355 faults are four-digit numbers like 0001 with a fieldbus code in brackets; ACS550 faults are numbered 1, 2, 3 and so on; ACS580 uses hexadecimal codes like 2310.
How do I reset an ABB VFD fault?
Fix the cause first, then press RESET on the panel, or use a digital input or fieldbus if set up. On the ACS550, a fault with a flashing red LED needs the power off for 5 minutes. Some ACS580 faults need a control board reboot.
Sources
- ABB ACS355 drives User's manual 3AUA0000066143 Rev E (2020): Fault tracing, pp.351–369
- ABB ACS550-01/U1 User's Manual 3AFE64804588 Rev H (2014): Diagnostics, pp.259–270
- ABB ACS580 standard control program Firmware manual 3AXD50000016097 Rev J (2025): Fault tracing, pp.537–567
Last checked: