Quick answer
3220 on an ABB drive means DC link undervoltage: the intermediate circuit DC voltage inside the drive is not high enough. It shows as 3220 on the ACS580, as fault 0006 DC UNDERVOLT on the ACS355 (3220 is its fieldbus code) and as fault 6 DC UNDERVOLT on the ACS550. ABB lists a missing input supply phase, a blown fuse, undervoltage on the mains, the undervoltage controller being off (ACS355) and a fault in the rectifier bridge.
Safety: ABB's manuals say only qualified electricians may maintain or service the drive, following the safety instructions in the manual. For any check of wiring, cables, fuses or motor insulation, switch off the supply and call a qualified electrician. The ACS550 manual also warns not to attempt any measurement, parts replacement or other service procedure not described in the manual, and that if an external start command is active the drive may start immediately after a fault reset.
Common causes
- Missing phase in the input power supply
- Blown fuse
- Undervoltage on the mains
- Undervoltage controller switched off (ACS355, parameter 2006)
- Fault in the rectifier bridge
Fix it step by step
0 of 5 done
- Note the code and check the series on the drive's type label.
- ACS355: check that the undervoltage controller is on (parameter 2006 UNDERVOLT CTRL).
- Have a qualified electrician check the supply cabling, fuses and switchgear, and look for a missing phase or low mains voltage.
- ACS355: watch parameter 0107 DC BUS VOLTAGE on the panel. ABB also says to measure the input and DC voltage during start, stop and running with a multimeter; that measurement is a job for a qualified electrician only.
- Once the cause is fixed, reset the fault.
Still showing 3220?
- ACS355: if the rectifier bridge has an internal fault, ABB says to replace the drive.
- Related supply faults: 3130 Input phase loss (ACS580), 0022 SUPPLY PHASE (ACS355) and fault 22 SUPPLY PHASE (ACS550) mean the DC voltage is oscillating because of a missing input phase or blown fuse.
- Warnings: alarm 2003 UNDERVOLTAGE on ACS355 and ACS550 means the undervoltage controller is active. ACS580 warning A3A2 means DC voltage is too low while the drive is stopped, and A3AA means the DC circuit has not yet charged to operating level.
हिंदी में
ABB ड्राइव में 3220 का मतलब है DC लिंक अंडरवोल्टेज: ड्राइव के अंदर DC वोल्टेज कम है। ACS580 में 3220, ACS355 में 0006 DC UNDERVOLT और ACS550 में फ़ॉल्ट 6 दिखता है।
- सप्लाई में कोई फ़ेज़ गायब तो नहीं, फ़्यूज़ उड़ा तो नहीं, या मेन्स वोल्टेज कम तो नहीं, यह इलेक्ट्रीशियन से चेक कराएं।
- ACS355 में undervoltage controller (2006) चालू है या नहीं देखें।
- कारण ठीक होने के बाद ही रीसेट करें।
Questions people ask
What causes 3220 DC link undervoltage on an ABB ACS580?
ABB's ACS580 manual says the DC voltage is not sufficient because of a missing supply phase, a blown fuse or a fault in the rectifier bridge, and tells you to check supply cabling, fuses and switchgear.
Is ACS355 fault 0006 the same as 3220?
Yes. The ACS355 manual lists 0006 DC UNDERVOLT with fieldbus code 3220.
Did this fix your problem? क्या इससे मदद मिली?
What went wrong?
Thanks. This helps us fix our guides. धन्यवाद!
Sources
- ABB ACS580 standard control program Firmware manual 3AXD50000016097 Rev J (2025): Fault tracing, p.542 (A3A2, A3AA) and p.556 (3220)
- ABB ACS355 drives User's manual 3AUA0000066143 Rev E (2020): Fault tracing, p.353 (alarm 2003) and pp.360–361 (fault 0006)
- ABB ACS550-01/U1 User's Manual 3AFE64804588 Rev H (2014): Diagnostics, p.261 (fault 6) and p.267 (alarm 2003)
Last checked: