Quick answer
3210 on an ABB drive means DC link overvoltage: the intermediate circuit DC voltage inside the drive is too high, so the drive tripped. It shows as 3210 on the ACS580, as fault 0002 DC OVERVOLT on the ACS355 (3210 is its fieldbus code; trip limit 420 V on 200 V drives and 840 V on 400 V drives), and as fault 2 DC OVERVOLT on the ACS550. ABB lists a high or noisy supply voltage, a deceleration time that is too short, the overvoltage controller being off, and a faulty or undersized brake chopper.
Safety: ABB's manuals say only qualified electricians may maintain or service the drive, following the safety instructions in the manual. For any check of wiring, cables, fuses or motor insulation, switch off the supply and call a qualified electrician. The ACS550 manual also warns not to attempt any measurement, parts replacement or other service procedure not described in the manual, and that if an external start command is active the drive may start immediately after a fault reset.
Common causes
- Supply voltage too high or noisy: static or transient overvoltage in the input power supply
- Deceleration time too short
- Overvoltage controller switched off
- Faulty or undersized brake chopper
- Supply voltage not matching the drive's nominal input voltage (ACS580)
- Drive used in a floating network (ACS355)
Fix it step by step
0 of 6 done
- Note the code and check the series on the drive's type label.
- Check that overvoltage control is on: parameter 30.30 Overvoltage control on ACS580, 2005 OVERVOLT CTRL on ACS355 and ACS550 (on ACS355 with a brake chopper and resistor, ABB says 2005 must be deactivated instead: see below).
- If the trip comes while the motor slows down, check the deceleration time: 2203 and 2206 on ACS355 and ACS550; on ACS580, check deceleration time (ABB also suggests the coast-to-stop function if applicable).
- Have a qualified electrician check that the supply voltage matches the drive's nominal input voltage and look for static or transient overvoltage on the supply line.
- If a brake chopper and resistor are fitted, have them checked, and that the resistor is dimensioned correctly for the drive (ACS580). On ACS355, ABB says DC overvoltage control must be deactivated (2005) when a brake chopper and resistor are used.
- Once the cause is fixed, reset the fault.
Still showing 3210?
- Both the ACS355 and ACS580 manuals list retrofitting the drive with a brake chopper and brake resistor as a corrective action.
- ACS355 in a floating network: ABB says to remove the EMC screw from the drive. This is an electrician's job with the power off.
- Warnings before a trip: alarm 2002 OVERVOLTAGE on ACS355 and ACS550 means the overvoltage controller is active. ACS580 warning A3A1 means the DC voltage is too high while the drive is stopped; ABB says to check the supply voltage setting 95.01 and the supply voltage. ABB notes a wrong 95.01 setting may make the motor rush uncontrollably or overload the brake chopper or resistor.
हिंदी में
ABB ड्राइव में 3210 का मतलब है DC लिंक ओवरवोल्टेज: ड्राइव के अंदर DC वोल्टेज बहुत ज़्यादा हो गया। ACS580 में 3210, ACS355 में 0002 DC OVERVOLT और ACS550 में फ़ॉल्ट 2 दिखता है।
- Overvoltage control चालू है या नहीं देखें (ACS580 में 30.30, ACS355/ACS550 में 2005)। ACS355 में ब्रेक चॉपर और रेज़िस्टर लगे हों तो ABB के अनुसार 2005 बंद रखना है।
- मोटर रुकते समय ट्रिप हो तो देखें कि deceleration time बहुत कम तो नहीं (ACS355/ACS550 में 2203, 2206)।
- सप्लाई वोल्टेज और ब्रेक रेज़िस्टर की जांच इलेक्ट्रीशियन से कराएं।
- कारण ठीक होने के बाद ही रीसेट करें।
Questions people ask
What is the DC overvoltage trip level on an ABB ACS355?
ABB's ACS355 manual gives 420 V for 200 V drives and 840 V for 400 V drives.
Why does an ABB drive trip on 3210 while stopping the motor?
ABB's ACS355 manual lists three causes when the fault appears during deceleration: the overvoltage controller is disabled, the deceleration time is too short, or the braking chopper is faulty or undersized.
Is 3210 the same as ACS550 fault 2?
Yes, both are DC overvoltage. The ACS550 calls it fault 2 DC OVERVOLT and the ACS355 calls it 0002 DC OVERVOLT with fieldbus code 3210.
Did this fix your problem? क्या इससे मदद मिली?
What went wrong?
Thanks. This helps us fix our guides. धन्यवाद!
Sources
- ABB ACS580 standard control program Firmware manual 3AXD50000016097 Rev J (2025): Fault tracing, p.542 (A3A1) and p.556 (3210)
- ABB ACS355 drives User's manual 3AUA0000066143 Rev E (2020): Fault tracing, p.353 (alarm 2002) and pp.359–360 (fault 0002)
- ABB ACS550-01/U1 User's Manual 3AFE64804588 Rev H (2014): Diagnostics, p.261 (fault 2) and p.267 (alarm 2002)
Last checked: