| E1 (indoor unit) | Split AC, "conventional series" table (SAC 123 Vectra Elegant, SAC 125V DZX manuals) | Room sensor short or open · full fix | E1 on a Voltas AC depends on the model. Voltas's "conventional series" table and window AC manuals say E1 shows when the room sensor is short or open. On inverter models (SAC 183V WZJ split, WAC 183V ADI window) and in the Wi-Fi error list, E1 is an indoor fan fault, and the outdoor light flashes 26 times. Both need a technician. |
| E2 (indoor unit) | Split AC, "conventional series" table (SAC 123 Vectra Elegant, SAC 125V DZX manuals) | Indoor coil sensor short or open · full fix | E2 on a Voltas AC depends on the model. Voltas's "conventional series" table says E2 shows when the indoor coil sensor is short or open, and the window AC manuals say E2 is a coil sensor short or open. On inverter models (SAC 183V WZJ split, WAC 183V ADI window) and in the Wi-Fi error list, E2 means indoor fan zero-crossing detection abnormal, and the outdoor light flashes 27 times. Both need a technician. |
| dF (indoor unit) | Split AC, "conventional series" table (SAC 123 Vectra Elegant, SAC 125V DZX manuals) | Indoor defrost protection error in cool and dry mode · full fix | dF on a Voltas AC relates to defrost. Voltas's conventional series table says dF indicates an indoor unit defrost protection error in cool and dry mode. The window AC manuals say dF is for defrost and occurs in cool mode and dry mode. In heat mode the matching code is HF (outdoor or condenser coil defrost). Voltas does not give a home fix for dF; if it keeps showing, call Voltas customer care. |
| E5 (indoor unit) | Split AC, "conventional series" table (SAC 123 Vectra Elegant, SAC 125V DZX manuals) | Fan motor error · full fix | E5 on a Voltas split AC indicates a fan motor error. It is listed for the indoor unit in the "Error code for conventional series models" table in Voltas's user manuals (for example SAC 123 Vectra Elegant and SAC 125V DZX). The Voltas inverter table (SAC 183V WZJ, WAC 183V ADI) does not list E5. There is no home fix for a fan motor error; call Voltas customer care. |
| E6 (indoor unit) | Split AC, "conventional series" table (SAC 123 Vectra Elegant, SAC 125V DZX manuals) | Zero crossing error · full fix | E6 on a Voltas AC depends on the model. In the "conventional series" split AC table, Voltas says E6 indicates a zero crossing error. On the SAC 183V WZJ inverter split AC, E6 is an indoor and outdoor machine communication fault. On the WAC 183V ADI inverter window AC, E6 is a main board and drive board communication fault. On both inverter models the outdoor light flashes 2 times. All need a technician. |
| EC (selected models only) | Split AC, "conventional series" table (SAC 123 Vectra Elegant, SAC 125V DZX manuals) | Gas leak detection · full fix | EC on a Voltas split AC means gas leak detection. Voltas's conventional series error table lists EC for the indoor unit as "Gas Leak Detection (applicable for selected models)", so not every Voltas AC has it. There is no home fix. Switch off the AC and call Voltas customer care (9650694555 or 1860 599 4555). |
| HP (heat mode) | Split AC, "conventional series" table (SAC 123 Vectra Elegant, SAC 125V DZX manuals) | Indoor coil high temperature protection in heat mode | — |
| E3 (outdoor unit) | Split AC, "conventional series" table (SAC 123 Vectra Elegant, SAC 125V DZX manuals) | Outdoor coil sensor short or open · full fix | E3 on a Voltas AC depends on the model. In the "conventional series" table, E3 shows when the outdoor (ODU) coil sensor is short or open. The window AC manuals say E3 shows when the condenser coil sensor is short or open in heat mode. On inverter models (SAC 183V WZJ, WAC 183V ADI) and in the Wi-Fi list, E3 is an indoor coil fault and sensor fault, and the outdoor light flashes 28 times. All need a technician. |
| HF (outdoor unit, heat mode) | Split AC, "conventional series" table (SAC 123 Vectra Elegant, SAC 125V DZX manuals) | Outdoor defrost protection error in heat mode | — |
| EE | Split AC, Wi-Fi error code list (SAC 123 Vectra Elegant, SAC 125V DZX manuals) | Indoor machine EE fault | — |
| E1 | Split AC, Wi-Fi error code list (SAC 123 Vectra Elegant, SAC 125V DZX manuals) | Indoor fan fault · full fix | E1 on a Voltas AC depends on the model. Voltas's "conventional series" table and window AC manuals say E1 shows when the room sensor is short or open. On inverter models (SAC 183V WZJ split, WAC 183V ADI window) and in the Wi-Fi error list, E1 is an indoor fan fault, and the outdoor light flashes 26 times. Both need a technician. |
| E2 | Split AC, Wi-Fi error code list (SAC 123 Vectra Elegant, SAC 125V DZX manuals) | Indoor fan zero-crossing detection abnormal · full fix | E2 on a Voltas AC depends on the model. Voltas's "conventional series" table says E2 shows when the indoor coil sensor is short or open, and the window AC manuals say E2 is a coil sensor short or open. On inverter models (SAC 183V WZJ split, WAC 183V ADI window) and in the Wi-Fi error list, E2 means indoor fan zero-crossing detection abnormal, and the outdoor light flashes 27 times. Both need a technician. |
| E3 | Split AC, Wi-Fi error code list (SAC 123 Vectra Elegant, SAC 125V DZX manuals) | Indoor coil fault and sensor fault · full fix | E3 on a Voltas AC depends on the model. In the "conventional series" table, E3 shows when the outdoor (ODU) coil sensor is short or open. The window AC manuals say E3 shows when the condenser coil sensor is short or open in heat mode. On inverter models (SAC 183V WZJ, WAC 183V ADI) and in the Wi-Fi list, E3 is an indoor coil fault and sensor fault, and the outdoor light flashes 28 times. All need a technician. |
| E4 | Split AC, Wi-Fi error code list (SAC 123 Vectra Elegant, SAC 125V DZX manuals) | Indoor ambient temperature sensor fault | — |
| E9 (test mode only) | Split AC, Wi-Fi error code list (SAC 123 Vectra Elegant, SAC 125V DZX manuals) | Wi-Fi module fault (seen while pressing the emergency switch and powering on the indoor unit) | — |
| E1 | Window AC (WAC 173 DZA, WAC 093 Vectra Platina; not the WAC 183V ADI inverter) | Room sensor short or open · full fix | E1 on a Voltas AC depends on the model. Voltas's "conventional series" table and window AC manuals say E1 shows when the room sensor is short or open. On inverter models (SAC 183V WZJ split, WAC 183V ADI window) and in the Wi-Fi error list, E1 is an indoor fan fault, and the outdoor light flashes 26 times. Both need a technician. |
| E2 | Window AC (WAC 173 DZA, WAC 093 Vectra Platina; not the WAC 183V ADI inverter) | Coil sensor short or open · full fix | E2 on a Voltas AC depends on the model. Voltas's "conventional series" table says E2 shows when the indoor coil sensor is short or open, and the window AC manuals say E2 is a coil sensor short or open. On inverter models (SAC 183V WZJ split, WAC 183V ADI window) and in the Wi-Fi error list, E2 means indoor fan zero-crossing detection abnormal, and the outdoor light flashes 27 times. Both need a technician. |
| E3 (heat mode) | Window AC (WAC 173 DZA, WAC 093 Vectra Platina; not the WAC 183V ADI inverter) | Condenser coil sensor short or open in heat mode · full fix | E3 on a Voltas AC depends on the model. In the "conventional series" table, E3 shows when the outdoor (ODU) coil sensor is short or open. The window AC manuals say E3 shows when the condenser coil sensor is short or open in heat mode. On inverter models (SAC 183V WZJ, WAC 183V ADI) and in the Wi-Fi list, E3 is an indoor coil fault and sensor fault, and the outdoor light flashes 28 times. All need a technician. |
| HF (heat mode) | Window AC (WAC 173 DZA, WAC 093 Vectra Platina; not the WAC 183V ADI inverter) | Condenser coil defrost in heat mode | — |
| dF (cool and dry mode) | Window AC (WAC 173 DZA, WAC 093 Vectra Platina; not the WAC 183V ADI inverter) | Defrost; occurs in cool mode and dry mode · full fix | dF on a Voltas AC relates to defrost. Voltas's conventional series table says dF indicates an indoor unit defrost protection error in cool and dry mode. The window AC manuals say dF is for defrost and occurs in cool mode and dry mode. In heat mode the matching code is HF (outdoor or condenser coil defrost). Voltas does not give a home fix for dF; if it keeps showing, call Voltas customer care. |
| EE (outdoor light flashes 25) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Indoor machine EE fault | — |
| E1 (outdoor light flashes 26) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Indoor fan fault · full fix | E1 on a Voltas AC depends on the model. Voltas's "conventional series" table and window AC manuals say E1 shows when the room sensor is short or open. On inverter models (SAC 183V WZJ split, WAC 183V ADI window) and in the Wi-Fi error list, E1 is an indoor fan fault, and the outdoor light flashes 26 times. Both need a technician. |
| E2 (outdoor light flashes 27) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Indoor fan zero-crossing detection abnormal · full fix | E2 on a Voltas AC depends on the model. Voltas's "conventional series" table says E2 shows when the indoor coil sensor is short or open, and the window AC manuals say E2 is a coil sensor short or open. On inverter models (SAC 183V WZJ split, WAC 183V ADI window) and in the Wi-Fi error list, E2 means indoor fan zero-crossing detection abnormal, and the outdoor light flashes 27 times. Both need a technician. |
| E3 (outdoor light flashes 28) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Indoor coil fault and sensor fault · full fix | E3 on a Voltas AC depends on the model. In the "conventional series" table, E3 shows when the outdoor (ODU) coil sensor is short or open. The window AC manuals say E3 shows when the condenser coil sensor is short or open in heat mode. On inverter models (SAC 183V WZJ, WAC 183V ADI) and in the Wi-Fi list, E3 is an indoor coil fault and sensor fault, and the outdoor light flashes 28 times. All need a technician. |
| E4 (outdoor light flashes 29) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Indoor ambient temperature sensor fault | — |
| E0 (outdoor light flashes 1) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Outdoor EE fault | — |
| F1 (outdoor light flashes 4) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Compressor starting abnormal (phase failure, reverse) | — |
| F2 (outdoor light flashes 5) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Compressor out-of-step fault | — |
| F3 (outdoor light flashes 6) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | IPM module fault | — |
| F4 (outdoor light flashes 7) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Compressor shell roof fault / protection | — |
| F5 (outdoor light flashes 8) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Discharge temperature sensor fault | — |
| F6 (outdoor light flashes 9) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Suction temperature sensor fault | — |
| F7 (outdoor light flashes 10) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Outdoor coil temperature sensor fault | — |
| F8 (outdoor light flashes 11) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Outdoor ambient temperature sensor fault | — |
| F9 (outdoor light flashes 12) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Outdoor DC fan fault | — |
| P1 (outdoor light flashes 13) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Outdoor machine AC current protection (WAC 183V ADI table: AC current / power overload protection) | — |
| P2 (outdoor light flashes 14) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Compressor phase current protection | — |
| P3 (outdoor light flashes 15) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Outdoor unit AC voltage too high or too low protection | — |
| P4 (outdoor light flashes 16) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | DC voltage too high or too low protection | — |
| P5 (outdoor light flashes 17) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | IPM over-high temperature protection | — |
| P6 (outdoor light flashes 18) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Discharge temperature overheat protection | — |
| P7 (outdoor light flashes 19) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Cooling: indoor coil anti-freezing protection | — |
| P8 (outdoor light flashes 20) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Cooling: outdoor coil overheat protection | — |
| P9 (outdoor light flashes 21) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Heating: indoor coil overheat protection | — |
| PC (outdoor light flashes 22) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Cooling: outdoor ambient temperature too low protection | — |
| PH (outdoor light flashes 23) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Heating: outdoor ambient temperature too high protection | — |
| L1 (outdoor light flashes 31) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Drive bus voltage too high protection | — |
| L2 (outdoor light flashes 32) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Drive bus voltage too low protection | — |
| L3 (outdoor light flashes 33) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Drive phase current overload fault | — |
| L4 (outdoor light flashes 34) | Inverter AC (SAC 183V WZJ split, WAC 183V ADI window) | Phase current sampling abnormal | — |
| E6 (outdoor light flashes 2) | Inverter split AC, SAC 183V WZJ | Indoor and outdoor machine communication fault · full fix | E6 on a Voltas AC depends on the model. In the "conventional series" split AC table, Voltas says E6 indicates a zero crossing error. On the SAC 183V WZJ inverter split AC, E6 is an indoor and outdoor machine communication fault. On the WAC 183V ADI inverter window AC, E6 is a main board and drive board communication fault. On both inverter models the outdoor light flashes 2 times. All need a technician. |
| E6 (outdoor light flashes 2) | Inverter window AC, WAC 183V ADI | Main board and drive board communication fault · full fix | E6 on a Voltas AC depends on the model. In the "conventional series" split AC table, Voltas says E6 indicates a zero crossing error. On the SAC 183V WZJ inverter split AC, E6 is an indoor and outdoor machine communication fault. On the WAC 183V ADI inverter window AC, E6 is a main board and drive board communication fault. On both inverter models the outdoor light flashes 2 times. All need a technician. |
| E8 (no outdoor flash count) | Inverter split AC, SAC 183V WZJ only | Outdoor communication fault | — |