Schneider VFD OCF Fault: Overcurrent (Altivar ATV12, ATV320)

Quick answer

OCF on a Schneider Electric Altivar drive (ATV12, ATV320) means Overcurrent. Schneider lists three causes: the motor control parameters are not correct, the inertia or load is too high, or the mechanism is locked. First check the parameters, the size of the motor, drive and load, and the state of the mechanism. On ATV12 it needs a power cycle after the cause is removed. On ATV310 the code with the same name (Overcurrent) is F010; its manual does not print a letter code beside it.

Safety: Only a qualified electrician should work on the drive, the motor or their wiring. Schneider's ATV320 manual warns of electric shock, explosion or arc flash. For a detected error that cannot be reset, it says to disconnect all power, including external control power, lock the disconnects open, wait 15 minutes for the DC bus capacitors to discharge (the drive LEDs do not show that the DC bus is dead), and measure the DC bus voltage between PA/+ and PC/- to make sure it is below 42 Vdc. If the capacitors do not discharge completely, contact Schneider Electric and do not repair or operate the drive.

Common causes

  • Motor control parameters are not correct (ATV12: drC- menu; ATV320: SET- and DRC- menus; ATV310 F010: menu 300-)
  • Inertia or load too high
  • Mechanical locking

Fix it step by step

  1. Note the code and check the model on the nameplate (ATV12, ATV310 or ATV320).
  2. Check the motor control parameters.
  3. Check the size of the motor, the drive and the load.
  4. Have the mechanism checked for locking or jamming, with the power off and the DC bus discharged.
  5. ATV12: connect line chokes and reduce the switching frequency SFr. ATV310 (F010): connect line motor chokes and reduce the switching frequency range 315. ATV320: decrease Current Limitation CLI and increase the switching frequency.
  6. ATV12 and ATV310: have an electrician check the ground connection of the drive, the motor cable and the motor insulation.
  7. Reset: ATV12 and ATV310 need the drive turned off and on after the cause is removed. ATV320 needs a power reset, unless Extended Fault Reset HRFC = YES, when the Fault Reset Assign RSF input can clear it.

Still showing OCF?

  • The manuals differ on switching frequency for this fault: the ATV12 and ATV310 manuals say reduce it, the ATV320 manual says increase it. Follow the manual for your model.
  • On ATV310 the code named Overcurrent is F010 (same fault name), with the same causes as ATV12 OCF.
  • If the drive also shows SCF1, SCF3 or SCF4, see the short-circuit rows on the Schneider hub. For SCF4 (IGBT short circuit) Schneider says to contact its representative or Product Support.

हिंदी में

Schneider Altivar VFD में OCF का मतलब है ओवरकरंट (करंट बहुत ज़्यादा)। कारण: मोटर पैरामीटर गलत, लोड या जड़त्व (inertia) बहुत ज़्यादा, या मशीन जाम। ATV310 में इसी नाम (Overcurrent) का कोड F010 है।

  1. कोड नोट करें और नेमप्लेट पर मॉडल देखें (ATV12, ATV310 या ATV320)।
  2. मोटर कंट्रोल पैरामीटर चेक करें।
  3. मोटर, ड्राइव और लोड का साइज़ चेक करें।
  4. मशीन कहीं जाम तो नहीं, यह बिजली बंद करके और DC बस डिस्चार्ज होने के बाद चेक कराएं।
  5. ATV12: line chokes लगाएं और switching frequency SFr कम करें। ATV310 (F010): line motor chokes लगाएं और switching frequency range 315 कम करें। ATV320: Current Limitation CLI कम करें और switching frequency बढ़ाएं।
  6. ATV12 और ATV310: इलेक्ट्रीशियन से ड्राइव का ग्राउंड कनेक्शन, मोटर केबल और मोटर इंसुलेशन चेक कराएं।
  7. रीसेट: ATV12 और ATV310 में कारण हटाने के बाद ड्राइव बंद करके फिर चालू करें। ATV320 में power reset चाहिए; अगर Extended Fault Reset HRFC = YES हो, तो Fault Reset Assign RSF input से भी साफ़ हो जाता है।
  8. वायरिंग या मोटर का काम सिर्फ़ इलेक्ट्रीशियन करे। Schneider के ATV320 मैनुअल के अनुसार: बाहरी कंट्रोल सप्लाई समेत सारी बिजली बंद करें, स्विच को बंद हालत में लॉक करें, 15 मिनट रुकें (ड्राइव की LED से पता नहीं चलता कि DC बस में करंट नहीं है), और PA/+ व PC/- के बीच DC बस वोल्टेज 42 V DC से कम नापें। वोल्टेज कम न हो तो ड्राइव को न छुएं, न चलाएं; Schneider Electric से संपर्क करें।

Questions people ask

Is OCF the same as F010 on ATV310?

Both are named Overcurrent in Schneider's manuals and list the same causes (parameters not correct, inertia or load too high, mechanical locking). The ATV310 manual uses the number F010 and does not print OCF beside it.

Why does OCF not clear with the reset input?

On ATV12 OCF is in the group that needs a power cycle. On ATV320 the RSF reset input clears it only if Extended Fault Reset HRFC is set to YES; otherwise it needs a power reset.

Sources

Last checked:

↑