Schneider VFD Fault Codes: Altivar ATV12, ATV310 and ATV320 Full List

By FaultDecode · Checked against Schneider Electric's official documents · Updated · How we check

144 Schneider Electric codes on this page.

Your model:

This list comes from the diagnostics chapters of three Schneider Electric manuals on se.com: the Altivar 12 user manual (2026), the Altivar ATV310 user manual (2026) and the ATV320 programming manual (2025). ATV12 and ATV320 show letter codes such as OCF, OBF and USF. ATV310 shows numbered codes, F001 to F036. Names, causes and remedies are close but not identical across the three, so check the model on the nameplate and read the rows for that model. Rows marked "Not a fault" are normal stop states from the manuals' "drive does not start" sections.

Safety: Only a qualified electrician should work on the drive or motor wiring. Schneider's ATV320 manual warns of electric shock, explosion or arc flash. For a detected error that cannot be reset it says: disconnect all power, including external control power; lock the disconnects open; wait 15 minutes for the DC bus capacitors to discharge (the drive LEDs do not show that the DC bus is dead); measure the DC bus voltage between PA/+ and PC/- and make sure it is below 42 Vdc. If the capacitors do not discharge completely, contact Schneider Electric and do not repair or operate the drive.

How to see the code

  1. Read the code on the drive's display.
  2. Check the model on the nameplate: ATV12, ATV310 or ATV320. ATV310 shows numbered codes (F001 to F036); ATV12 and ATV320 show letter codes.
  3. Match the code in the rows for that model. On ATV320 the graphic display terminal's Diagnostics menu (DGT-) also shows the error and its cause in plain text.
  4. nSt and FSt (ATV12/ATV320), rdY (ATV12), or 502.1, --01 and --00 (ATV310) are not faults: a stop input is not powered, or the drive is waiting for a bus command.
  5. Remove the cause first, then reset the way the manual says for that code (see the notes on the Schneider code list).

How to check the error code on other VFD / drive brands

Schneider Electric VFD / drive error code list

CodeModel typeMeaningWhat to do
CrF1 ATV12 Precharge: charging relay control fault or charging resistor damaged Turn the drive off and back on; check the connections and the stability of the main supply. Contact your local Schneider Electric representative.
InFI ATV12 Unknown drive rating: the power card is different from the card stored Contact your local Schneider Electric representative.
InF2 ATV12 Unknown or incompatible power board: the power card is incompatible with the control card Contact your local Schneider Electric representative.
InF3 ATV12 Internal serial link: communication interruption between the internal cards Contact your local Schneider Electric representative.
InF4 ATV12 Invalid industrialization zone: inconsistent internal data Contact your local Schneider Electric representative.
InF9 ATV12 Current measurement circuit: current measurement is not correct due to the hardware circuit Contact your local Schneider Electric representative.
---- ATV12, ATV310 Problem with the application firmware: invalid application firmware update using the Multi-Loader tool Flash (re-download) the application firmware of the product again.
InFb ATV12 Internal thermal sensor fault: the drive temperature sensor is not operating correctly, or is in short circuit or open Contact your local Schneider Electric representative.
InFE ATV12 Internal CPU: internal microprocessor fault Turn the drive off and back on. Contact your local Schneider Electric representative.
OCF ATV12 Overcurrent: motor control parameters (drC- menu) not correct, inertia or load too high, or mechanical locking · full fix Check the parameters, the size of the motor/drive/load and the state of the mechanism; connect line chokes; reduce the switching frequency SFr; check the ground connection of the drive, the motor cable and the motor insulation.
SCF1 ATV12 Motor or ground short circuit: short circuit or grounding at the drive output · full fix Check the cables connecting the drive to the motor, and the motor insulation; connect motor chokes. (The ATV12 manual prints SCF1 and SCF3 in one shared cell.)
SCF3 ATV12 Ground short circuit: ground fault while running, motors switched while running, or significant current leakage to ground with several motors in parallel Check the cables connecting the drive to the motor, and the motor insulation; connect motor chokes. (The ATV12 manual prints SCF1 and SCF3 in one shared cell.)
SCF4 ATV12 IGBT short circuit: internal power component short circuit detected at power-on Contact your local Schneider Electric representative.
SOF ATV12 Overspeed: instability, or overspeed linked to the inertia of the application Check the motor; overspeed is 10% above Maximum frequency tFr, so adjust tFr if needed; add a braking resistor; check the size of the motor/drive/load and the speed loop parameters (gain and stability).
tnF ATV12 Auto-tuning fault: motor not connected, one motor phase lost, special motor, or motor rotating (for example driven by the load) Check that the motor and drive are compatible and that the motor is present and completely stopped during auto-tuning; if an output contactor is used, close it during auto-tuning.
LFF1 ATV12 AI current lost: AI1 is set as a current input, its 0% scaling CrL1 is above 3 mA, and the input current is below 2 mA Check the terminal connection.
ObF ATV12 Overbraking: braking too sudden or driving load too high · full fix Increase the deceleration time; install a module unit with a braking resistor if necessary; check that the line supply voltage is under the maximum acceptable.
OHF ATV12 Drive overheat: drive temperature too high · full fix Check the motor load, the drive ventilation and the ambient temperature. Wait for the drive to cool down before restarting.
OLC ATV12 Process overload Check that the process and the drive parameters are in phase.
OLF ATV12 Motor overload: triggered by excessive motor current · full fix Check the setting of the motor thermal protection and the motor load.
OPF1 ATV12 1 output phase loss: loss of one phase at the drive output Check the connections from the drive to the motor; with a downstream contactor, check the connection, cable and contactor.
OPF2 ATV12 3 output phase loss: motor not connected, motor power below 6% of the drive nominal current, output contactor open, or instantaneous instability in the motor current Check the connections from the drive to the motor. To test without a matching motor, set Output Phase loss detection OPL = nO. Check UFr, UnS and nCr and perform Auto-tuning tUn.
OSF ATV12 Main overvoltage: line voltage too high (10% over the maximum at power-on, or 20% over the maximum with no run order) or disturbed line supply Turn off the drive; check and adjust the line voltage; power on again once it is back to nominal. If OSF comes and goes, relay R1 can be set to FLt and connected to upstream protection.
PHF ATV12 Input phase loss: drive incorrectly supplied or a fuse blown, one phase failed, 3-phase ATV12 on a 1-phase supply, or unbalanced load (only operates with the drive on load) · full fix Check the power connection and the fuses; use a 3-phase supply. The fault can be disabled with Input Phase loss detection IPL = nO.
SCF5 ATV12 Load short circuit: short circuit at the drive output (also detected at the run or DC injection order if IGBT test Strt = YES) Check the cables connecting the drive to the motor, and the motor insulation.
SLF1 ATV12 Modbus communication: interruption in communication on the Modbus network Check the bus connections and the time-out (Modbus time out ttO); refer to the Modbus user manual.
SLF2 ATV12 SoMove communication: communication interruption with SoMove Check the SoMove connecting cable and the time-out.
SLF3 ATV12 HMI communication: communication interruption with the external display terminal Check the terminal connection.
SPIF ATV12 PI feedback fault: PID feedback below the lower limit Check the PID function feedback, the PI feedback supervision threshold LPI and time delay tPI.
ULF ATV12 Process underload: motor current below the underload threshold LUL for the time set in ULt Check that the process and the drive parameters are in phase.
tJF ATV12 IGBT overheat: drive overheated; IGBT internal temperature too high for the ambient temperature and load Check the size of the load/motor/drive; reduce the switching frequency SFr; wait for the drive to cool before restarting.
EPF1 ATV12 External fault by logic input: event triggered by an external device Check the device which caused the trip and reset.
CFF ATV12 Incorrect configuration: HMI block replaced by one configured on a drive with a different rating, or customer parameters inconsistent Return to factory settings or retrieve the backup configuration, if it is valid. If the fault remains after factory settings, contact your local Schneider Electric representative.
CFI ATV12 Invalid configuration: the configuration loaded through the bus or network is inconsistent, or the upload was interrupted or not finished Check the configuration loaded previously; load a compatible configuration.
CFI2 ATV12 Download invalid configuration: download with Loader or SoMove was interrupted Check the connection with Loader or SoMove; restart the download or restore the factory setting.
USF ATV12 Undervoltage: line supply too low, or transient voltage dip · full fix Check the voltage and the parameters of the Undervoltage/Phase Loss menu USb-.
F001 ATV310 Precharge: charging relay control fault or charging resistor damaged Turn the drive off and back on; check the connections and the stability of the main supply. Contact your local Schneider Electric representative.
F002 ATV310 Unknown drive rating: power card and stored card versions different Contact your local Schneider Electric representative.
F003 ATV310 Unknown or incompatible power board: the power card is incompatible with the control card Contact your local Schneider Electric representative.
F004 ATV310 Internal serial link fault: communication interruption between the internal cards Contact your local Schneider Electric representative.
F005 ATV310 Invalid industrialization zone: internal data inconsistent Contact your local Schneider Electric representative.
F006 ATV310 Current measurement circuit fault: current measurement is not correct due to the hardware circuit Contact your local Schneider Electric representative.
F007 ATV310 Internal thermal sensor fault: the drive temperature sensor is not operating correctly, or is in short circuit or open Contact your local Schneider Electric representative.
F008 ATV310 Internal CPU: internal microprocessor fault Turn the drive off and back on. Contact your local Schneider Electric representative.
F010 ATV310 Overcurrent: motor control parameters (menu 300-) not correct, inertia or load too high, or mechanical locking Check the parameters, the size of the motor/drive/load and the state of the mechanism; connect line motor chokes; reduce the switching frequency range 315; check the ground connection of the drive, the motor cable and the motor insulation.
F018 ATV310 Motor short-circuit: short circuit or grounding at the drive output Verify the cables connecting the drive to the motor and the motor insulation; adjust the switching frequency; connect chokes in series with the motor; verify the adjustment of the speed loop. (The ATV310 manual prints F018 and F019 in one shared cell.)
F019 ATV310 Ground short-circuit: ground fault while running, motor switching while running, or significant current leakage to ground with several motors in parallel Verify the cables connecting the drive to the motor and the motor insulation; adjust the switching frequency; connect chokes in series with the motor; verify the adjustment of the speed loop. (The ATV310 manual prints F018 and F019 in one shared cell.)
F020 ATV310 IGBT short circuit: internal power component short circuit detected at power on Contact your local Schneider Electric representative.
F025 ATV310 Overspeed: instability, or overspeed linked to the inertia of the application Check the motor; if overspeed is 10% above Top frequency 308, adjust it if needed; add a braking resistor; check the size of the motor/drive/load and the speed loop parameters (gain and stability).
F028 ATV310 Autotuning fault: motor not connected, motor phase loss, special motor, or motor rotating (for example driven by the load) Check that the motor and drive are compatible and that the motor is present and completely stopped; if a downstream output contactor is used, close it during auto-tuning.
F036 ATV310 Angle setting fault: during the phase-shift angle measurement, a motor phase is disconnected or the motor inductance is too high Check the motor phases and the maximum current allowed by the drive.
F009 ATV310 Overbraking: sudden braking or load inertia too high Increase the deceleration time; install a module unit with a braking resistor if necessary; check that the main supply voltage is under the maximum acceptable.
F011 ATV310 Drive overheat: drive temperature too high Check the motor load, the drive ventilation and the ambient temperature. Wait for the drive to cool down before restarting.
F012 ATV310 Process overload fault Check that the drive parameters and the application process are compatible.
F013 ATV310 Motor overload: triggered by excessive motor current Check the configuration of the motor thermal protection and the motor load.
F014 ATV310 1 output phase loss: loss of one phase on the drive output Check the connections from the drive to the motor; with a downstream contactor, make sure the connection, cable and contactor are right.
F015 ATV310 3 output phases loss: motor not connected, motor power below 6% of the rated drive current, output contactor open, or transient instability in the motor current Check the connections from the drive to the motor. To test without a matching motor, set Output Phase loss detection 605 = 00. Check IR compensation 310, Rated motor voltage 304 and Rated motor current 305, then perform Auto-tuning 318.
F016 ATV310 Main overvoltage: line voltage too high (10% over the maximum at power on, or 20% over the maximum with no run command) or disturbed mains supply Turn off the drive; check and adjust the line voltage; power on again once it is back to nominal. If F016 comes and goes, R1 assignment 205.0 can be set to 01 and connected to upstream protection.
F017 ATV310 Input phase loss: drive incorrectly supplied or a fuse blown, one phase failed, 3-phase ATV310 on a single-phase supply, or unbalanced load (only operates with the drive on load) Check the power connection and the fuses; use a 3-phase supply. Reporting can be disabled with Input Phase loss detection 606 = 00.
F021 ATV310 Load short circuit: short circuit at the drive output (also detected at the run or DC injection command if IGBT Test 608 = 01) Check the cables connecting the drive to the motor and the condition of the motor insulation.
F022 ATV310 Modbus interruption: interrupted communication on the Modbus network Check the bus connections and the time-out (Modbus time out 704); refer to the Modbus user manual.
F024 ATV310 HMI communication: communication interruption with the external display terminal Check the terminal connection.
F026 ATV310 PI feedback fault: PID feedback below the lower limit Verify the PID function feedback, PID feedback supervision 59.25 and time delay 59.23.
F027 ATV310 IGBT overheat: drive overheated; IGBT internal temperature too high for the ambient temperature and load Check the size of the load/motor/drive; reduce the switching frequency 315; wait for the drive to cool down before restarting.
F029 ATV310 Process underload fault: motor current below the underload threshold 211 for longer than the time delay 210 Check that the drive parameters and the application process are compatible.
F033 ATV310 AI1 current loss: AI1 is set as a current input, its 0% scaling 204.1 is above 3 mA, and the input current is below 2 mA Check the terminal connection.
F030 ATV310 Undervoltage: line supply too low, or transient voltage dip Check the voltage and the parameters in the Undervoltage phase loss menu 607-.
F031 ATV310 Incorrect configuration: HMI block replaced by one configured on a drive with a different rating, or customer parameters inconsistent Return to factory settings or retrieve the backup configuration, if it is valid. If the fault remains after factory settings, contact your local Schneider Electric representative.
F032 ATV310 Invalid configuration: the configuration loaded through the bus or network is inconsistent, or the upload was interrupted or not finished Check the configuration loaded previously; load a compatible configuration.
F034 ATV310 Download invalid configuration: the drive found an invalid configuration while saving parameters or restoring factory settings Power cycle the drive; restore the factory setting. If the fault remains, contact your local Schneider Electric representative.
ANF ATV320 Load slipping: the difference between the output frequency and the speed feedback is not correct Check the motor, gain and stability parameters; add a braking resistor; check the size of the motor/drive/load; check the encoder coupling and wiring; check the parameter settings.
ASF ATV320 Angle error: during the phase-shift angle measurement, a motor phase is disconnected or the motor inductance is too high Check the motor phases and the maximum current allowed by the drive.
BLF ATV320 Brake control error: brake release current not reached; the manual also lists the brake engage frequency threshold BEN (only regulated when brake logic control is assigned) Check the drive/motor connection and the motor windings; check the IBR and IRD settings; apply the recommended settings for BEN.
BRF ATV320 Brake feedback error: the brake feedback contact does not match the brake logic, or the brake does not stop the motor quickly enough Check the feedback circuit and the brake logic control circuit; check the mechanical state of the brake and the brake linings.
CFF ATV320 Incorrect configuration: option module changed or removed, control block replaced by one from a drive with a different rating, or configuration inconsistent Check that there are no module errors; return to factory settings (FCS-) or retrieve the backup configuration, if it is valid.
CFI ATV320 Invalid configuration: the configuration loaded through the bus or network is inconsistent Check the configuration loaded previously; load a compatible configuration.
CFI2 ATV320 Configuration transfer error: the configuration loaded through the bus or network is inconsistent Check the configuration loaded previously; load a compatible configuration.
CNF ATV320 Fieldbus module communication interruption Check the environment (electromagnetic compatibility), the wiring and the time-out; replace the option module. Contact Schneider Electric Product Support.
COF ATV320 CANopen communication interruption Check the communication bus and the time-out; refer to the CANopen user manual.
CRF1 ATV320 Precharge capacitor error: charging relay control error or charging resistor damaged Turn the drive off and on again; check the internal connections. Contact Schneider Electric Product Support.
CSF ATV320 Channel switching error: switch to channels that are not valid Check the function parameters.
DLF ATV320 Dynamic load error: abnormal load variation Check that the load is not blocked by an obstacle. Removing the run command causes a reset.
EEF1 ATV320 EEprom control error: internal memory error, control block Check the environment (electromagnetic compatibility); turn off, reset, return to factory settings. Contact Schneider Electric Product Support.
EEF2 ATV320 EEprom power error: internal memory error, power board Check the environment (electromagnetic compatibility); turn off, reset, return to factory settings. Contact Schneider Electric Product Support.
EPF1 ATV320 External error: event triggered by an external device Check the device which caused the trip and reset.
EPF2 ATV320 Fieldbus external error: event triggered by a communication network Check the cause of the trip and reset.
FBE ATV320 Function block error See [FB Error] FBFT for details.
FBES ATV320 Function block stop error: function blocks were stopped while the motor was running Check the [FB Motor Stop Type] FBSM configuration.
FCF1 ATV320 Output contactor closed: the output contactor stays closed although the opening conditions are met Check the contactor and its wiring, and the feedback circuit.
FCF2 ATV320 Output contactor opened: the output contactor stays open although the closing conditions are met Check the contactor and its wiring, and the feedback circuit.
HCF ATV320 Boards compatibility: Boards pairing (PPI-) is configured and a drive card has been changed If a card is faulty, reinsert the original card; if the card was changed on purpose, confirm with the Pairing password PPI.
HDF ATV320 IGBT desaturation: short circuit or grounding at the drive Check the cables connecting the drive to the motor, and the motor insulation.
ILF ATV320 Internal link error: communication interruption between the option module and the drive Check the environment (electromagnetic compatibility) and the connections; replace the option module. Contact Schneider Electric Product Support.
INF1 ATV320 Internal error 1 (Rating): the power board is different from the board stored Check the reference of the power board.
INF2 ATV320 Internal error 2 (Soft): the power board is incompatible with the control block Check the reference of the power board and its compatibility.
INF3 ATV320 Internal error 3 (Intern Comm): communication interruption between the internal cards Check the internal connections. Contact Schneider Electric Product Support.
INF4 ATV320 Internal error 4 (Manufacturing): internal data inconsistent Re-calibrate the drive (done by Schneider Electric Product Support).
INF6 ATV320 Internal error 6 (Option): the option installed in the drive is not recognized Check the reference and compatibility of the option, and that it is well inserted.
INF9 ATV320 Internal error 9 (Measure): the current measurements are incorrect Replace the current sensors or the power board. Contact Schneider Electric Product Support.
INFA ATV320 Internal error 10 (Mains): the input stage is not operating correctly Contact Schneider Electric Product Support.
INFB ATV320 Internal error 11 (Temperature): the drive temperature sensor is not operating correctly Replace the drive temperature sensor. Contact Schneider Electric Product Support.
INFE ATV320 Internal error 14 (CPU): internal microprocessor error Turn off and reset. Contact Schneider Electric Product Support.
LCF ATV320 Input contactor error: the drive is not turned on even though Mains V. time out LCT has elapsed Check the contactor and its wiring, the time-out, and the supply mains/contactor/drive connection.
LFF3 ATV320 AI3 4-20 mA loss: loss of the 4-20 mA reference on analog input AI3 Check the connection on the analog inputs.
OBF ATV320 DC bus overvoltage: braking too sudden or driving load, or supply voltage too high · full fix Increase the deceleration time; install a braking resistor if necessary; activate Dec.Ramp Adapt BRA if compatible with the application; check the supply voltage.
OCF ATV320 Overcurrent: parameters in the SET- and DRC- menus not correct, inertia or load too high, or mechanical locking · full fix Check the parameters, the size of the motor/drive/load and the state of the mechanism; decrease Current Limitation CLI; increase the switching frequency.
OHF ATV320 Drive overheating: drive temperature too high · full fix Check the motor load, the drive ventilation and the ambient temperature. Wait for the drive to cool down before restarting.
OLC ATV320 Process overload Check and remove the cause of the overload; check the parameters of the Process overload OLD- function.
OLF ATV320 Motor overload: triggered by excessive motor current · full fix Check the setting of the motor thermal protection and the motor load. Wait for the motor to cool down before restarting.
OPF1 ATV320 Single output phase loss: loss of one phase at the drive output Check the connections from the drive to the motor.
OPF2 ATV320 Output phase loss: motor not connected or motor power too low, output contactor open, or instantaneous instability in the motor current Check the connections from the drive to the motor. If an output contactor is used, set Output phase loss OPL to OAC. To test without a matching motor, set OPL = NO. Check UFR, UNS and NCR and perform Autotuning TUN.
OSF ATV320 Supply mains overvoltage: supply voltage too high, or disturbed mains supply Check the supply voltage.
OTFL ATV320 DI6=PTC overheat: overheating of the PTC probes detected on input DI6 Check the motor load, motor size and motor ventilation; wait for the motor to cool before restarting; check the type and state of the PTC probes.
PHF ATV320 Input phase loss: drive incorrectly supplied or a fuse blown, one phase missing, 3-phase ATV320 on a single-phase supply, or unbalanced load (only operates with the drive on load) · full fix Check the power connection and the fuses; use a 3-phase supply. The error can be disabled with InPhaseLoss Assign IPL = NO.
PTFL ATV320 DI6=PTC probe error: the PTC probe on input DI6 is open or short-circuited Check the PTC probe and the wiring between it and the motor/drive.
SAFF ATV320 Safety function error: debounce time exceeded, SS1 threshold exceeded, incorrect configuration, or SLS type overspeed Check the safety functions configuration and the ATV320 Integrated Safety Functions manual. Contact Schneider Electric Product Support.
SCF1 ATV320 Motor short circuit: short circuit or grounding at the drive output · full fix Check the cables connecting the drive to the motor, and the motor insulation; connect chokes in series with the motor; check the speed loop and brake adjustment; increase Time to restart TTR. The remedy list gives both reduce and increase the switching frequency.
SCF3 ATV320 Ground short circuit: significant earth leakage current at the drive output if several motors are connected in parallel Check the cables connecting the drive to the motor, and the motor insulation; reduce the switching frequency; connect chokes in series with the motor; check the speed loop and brake adjustment; increase Time to restart TTR.
SCF4 ATV320 IGBT short circuit: power component error Contact Schneider Electric Product Support.
SCF5 ATV320 Motor short circuit: short circuit at the drive output Check the cables connecting the drive to the motor, and the motor insulation. Contact Schneider Electric Product Support.
SLF1 ATV320 Modbus communication interruption Check the communication bus and the time-out; refer to the Modbus user manual.
SLF2 ATV320 PC communication interruption: communication interruption with the PC software Check the PC software connecting cable and the time-out.
SLF3 ATV320 HMI communication interruption: with the graphic display terminal or remote display terminal Check the terminal connection and the time-out.
SOF ATV320 Motor overspeed: instability or driving load too high, downstream contactor not closed before the Run command, or overspeed threshold (110% of Max Frequency TFR) reached Check the motor, gain and stability parameters; add a braking resistor; check the size of the motor/drive/load; check the Frequency meter FQF- settings if used; close the motor contacts before the Run command; Schneider recommends TFR at least 110% of High Speed HSP.
SPF ATV320 Encoder feedback loss: signal on the Pulse input missing (if used for speed measurement), or encoder feedback signal missing Check the input cable wiring and the detector, the encoder configuration parameters, the wiring between the encoder and the drive, and the encoder.
SSF ATV320 Torque limitation error: switch to torque or current limitation Check for mechanical problems; check the parameters of Torque limitation TOL- and Torque or I limit detect TID-.
TJF ATV320 IGBT overheating: drive overheated Check the size of the load/motor/drive; reduce the switching frequency. The manual then says: "Wait for the motor to cool before restarting."
TNF ATV320 Autotuning error: special motor or motor power not suitable for the drive, motor not connected, or motor not stopped Check that the motor and drive are compatible, that the motor is present and stopped during auto-tuning; if an output contactor is used, close it during auto-tuning.
ULF ATV320 Process underload Check and remove the cause of the underload; check the parameters of the Process underload ULD- function.
USF ATV320 Supply mains undervoltage: supply mains too low, or transient voltage dip · full fix Check the voltage and the parameters of Undervoltage handling USB-.
InIt ATV12, ATV310, ATV320 Initializing: the microcontroller is initializing and searching for the communication configuration (not a fault) —
COM.E ATV12, ATV310, ATV320 Communication error (flashing): 50 ms time-out. ATV12 and ATV310 manuals: shown after 220 retry attempts; ATV320 manual: after 20 attempts —
A-17 ATV12, ATV310, ATV320 Key alarm (flashing): a key held down for more than 10 seconds, keypad (membrane switch) disconnected, or keypad woken up while a key is pressed —
cLr ATV12, ATV310, ATV320 Confirm fault reset (flashing): shown when the STOP key is pressed while there is a fault (ATV320: when the remote display terminal is the active command channel) —
dEU.E ATV12, ATV310, ATV320 Drive mismatch (flashing): the drive brand does not match the remote display terminal brand —
rOM.E ATV12, ATV310, ATV320 ROM abnormality (flashing): the terminal found a ROM problem by checksum calculation —
rAM.E ATV12, ATV310, ATV320 RAM abnormality (flashing): the terminal found a RAM problem —
CPU.E ATV12, ATV310, ATV320 Other fault (flashing): other detected fault (shown on the remote display terminal) —
nSt ATV12, ATV320 Not a fault: freewheel stop. Shown when the Freewheel stop input is not powered, or when control is on Modbus/fieldbus and the bus has not sent a command yet Normal. Check the logic input assignment (ATV12: COnF/FULL/FUn-/Stt-), or wait for the bus to send a command.
FSt ATV12, ATV320 Not a fault: fast stop. Shown when the Fast stop input is not powered Normal. Check the logic input assignment (ATV12: COnF/FULL/FUn-/Stt-).
rdY ATV12 Not a fault: shown with the Fast stop/Freewheel functions. The ATV12 manual's sentence reads "it will display rdY en freewheel stop"; the ATV310 manual's matching sentence says this code shows at the end of a freewheel stop. Normal. Check the logic input assignment (COnF/FULL/FUn-/Stt-) and that the run command input is active.
502.1 ATV310 Not a fault: freewheel stop. Shown when the Freewheel stop input is not powered, or when control is on Modbus and the bus has not sent a command yet Normal. Check the logic input assignment in COnF/FULL/500-/502-, or wait for the bus to send a command.
--01 ATV310 Not a fault: fast stop mode Normal. Check the logic input assignment in COnF/FULL/500-/502-.
--00 ATV310 Not a fault: shown at the end of a freewheel stop Normal. Check that the run command input is active for the selected control mode.

Good to know

हिंदी में

Schneider Electric Altivar VFD (ATV12, ATV310, ATV320) के फ़ॉल्ट कोड Schneider के अपने मैनुअल से: OCF मतलब ज़्यादा करंट, OBF/ObF मतलब Overbraking (ATV12) या DC बस ओवरवोल्टेज (ATV320), OHF मतलब ड्राइव गरम, OLF मतलब मोटर ओवरलोड, SCF1 मतलब मोटर शॉर्ट सर्किट, USF मतलब वोल्टेज कम, PHF मतलब इनपुट फ़ेज़ गायब। ATV310 में नंबर वाले कोड (F001 से F036) आते हैं।

  1. ड्राइव की नेमप्लेट पर मॉडल देखें (ATV12, ATV310 या ATV320)।
  2. कोड का मतलब नीचे उसी मॉडल की लाइन में देखें।
  3. nSt, FSt (ATV12/ATV320), rdY (ATV12) या 502.1, --01, --00 (ATV310) फ़ॉल्ट नहीं हैं: स्टॉप इनपुट चालू नहीं है या ड्राइव बस से कमांड का इंतज़ार कर रही है।
  4. वायरिंग या मोटर का काम सिर्फ़ इलेक्ट्रीशियन करे। Schneider के ATV320 मैनुअल के अनुसार: बाहरी कंट्रोल सप्लाई समेत सारी बिजली बंद करें, स्विच को बंद हालत में लॉक करें, 15 मिनट रुकें (ड्राइव की LED से पता नहीं चलता कि DC बस में करंट नहीं है), और PA/+ व PC/- के बीच DC बस वोल्टेज 42 V DC से कम नापें। वोल्टेज कम न हो तो ड्राइव को न छुएं, न चलाएं; Schneider Electric से संपर्क करें।
  5. कारण ठीक करने के बाद मैनुअल के अनुसार रीसेट करें (कुछ कोड के लिए बिजली बंद करके फिर चालू करनी पड़ती है)।

Questions people ask

What is OCF fault in a Schneider Altivar drive?

Overcurrent. The ATV12 and ATV320 manuals list wrong motor control parameters, inertia or load too high, and mechanical locking as causes. Check the parameters, the motor/drive/load size and the mechanism. On ATV12 and ATV320 it needs a power reset (on ATV320 the RSF input can clear it if Extended Fault Reset HRFC = YES).

What does OBF or ObF mean on a Schneider VFD?

ATV12 calls ObF Overbraking; ATV320 calls OBF DC bus overvoltage. Causes are braking too sudden or a driving load (ATV320 adds supply voltage too high). The first fix in both manuals is to increase the deceleration time, and to add a braking resistor if necessary.

What is F010 on an ATV310?

The ATV310 manual names F010 Overcurrent: motor control parameters not correct, inertia or load too high, or mechanical locking. It needs a power cycle after the cause is removed.

The drive shows nSt and will not start. Is it faulty?

No. Schneider says nSt (freewheel stop) shows when the Freewheel stop input is not powered, or when the drive is controlled over Modbus or a fieldbus and the bus has not sent a command yet. On ATV310 the same state shows as 502.1.

How do I reset a Schneider Altivar fault?

Remove the cause first. Some codes need the drive switched off and on, some clear by automatic restart or a logic input assigned to fault reset, and some clear on their own once the cause is gone. The groups for each model are listed under Good to know.