Schneider VFD Fault Codes: Altivar ATV12, ATV310 and ATV320 Full List
144 Schneider Electric codes on this page.
This list comes from the diagnostics chapters of three Schneider Electric manuals on se.com: the Altivar 12 user manual (2026), the Altivar ATV310 user manual (2026) and the ATV320 programming manual (2025). ATV12 and ATV320 show letter codes such as OCF, OBF and USF. ATV310 shows numbered codes, F001 to F036. Names, causes and remedies are close but not identical across the three, so check the model on the nameplate and read the rows for that model. Rows marked "Not a fault" are normal stop states from the manuals' "drive does not start" sections.
Safety: Only a qualified electrician should work on the drive or motor wiring. Schneider's ATV320 manual warns of electric shock, explosion or arc flash. For a detected error that cannot be reset it says: disconnect all power, including external control power; lock the disconnects open; wait 15 minutes for the DC bus capacitors to discharge (the drive LEDs do not show that the DC bus is dead); measure the DC bus voltage between PA/+ and PC/- and make sure it is below 42 Vdc. If the capacitors do not discharge completely, contact Schneider Electric and do not repair or operate the drive.
How to see the code
- Read the code on the drive's display.
- Check the model on the nameplate: ATV12, ATV310 or ATV320. ATV310 shows numbered codes (F001 to F036); ATV12 and ATV320 show letter codes.
- Match the code in the rows for that model. On ATV320 the graphic display terminal's Diagnostics menu (DGT-) also shows the error and its cause in plain text.
- nSt and FSt (ATV12/ATV320), rdY (ATV12), or 502.1, --01 and --00 (ATV310) are not faults: a stop input is not powered, or the drive is waiting for a bus command.
- Remove the cause first, then reset the way the manual says for that code (see the notes on the Schneider code list).
Schneider Electric VFD / drive error code list
| Code | Model type | Meaning | What to do |
|---|---|---|---|
| CrF1 | ATV12 | Precharge: charging relay control fault or charging resistor damaged | Turn the drive off and back on; check the connections and the stability of the main supply. Contact your local Schneider Electric representative. |
| InFI | ATV12 | Unknown drive rating: the power card is different from the card stored | Contact your local Schneider Electric representative. |
| InF2 | ATV12 | Unknown or incompatible power board: the power card is incompatible with the control card | Contact your local Schneider Electric representative. |
| InF3 | ATV12 | Internal serial link: communication interruption between the internal cards | Contact your local Schneider Electric representative. |
| InF4 | ATV12 | Invalid industrialization zone: inconsistent internal data | Contact your local Schneider Electric representative. |
| InF9 | ATV12 | Current measurement circuit: current measurement is not correct due to the hardware circuit | Contact your local Schneider Electric representative. |
| ---- | ATV12, ATV310 | Problem with the application firmware: invalid application firmware update using the Multi-Loader tool | Flash (re-download) the application firmware of the product again. |
| InFb | ATV12 | Internal thermal sensor fault: the drive temperature sensor is not operating correctly, or is in short circuit or open | Contact your local Schneider Electric representative. |
| InFE | ATV12 | Internal CPU: internal microprocessor fault | Turn the drive off and back on. Contact your local Schneider Electric representative. |
| OCF | ATV12 | Overcurrent: motor control parameters (drC- menu) not correct, inertia or load too high, or mechanical locking · full fix | Check the parameters, the size of the motor/drive/load and the state of the mechanism; connect line chokes; reduce the switching frequency SFr; check the ground connection of the drive, the motor cable and the motor insulation. |
| SCF1 | ATV12 | Motor or ground short circuit: short circuit or grounding at the drive output · full fix | Check the cables connecting the drive to the motor, and the motor insulation; connect motor chokes. (The ATV12 manual prints SCF1 and SCF3 in one shared cell.) |
| SCF3 | ATV12 | Ground short circuit: ground fault while running, motors switched while running, or significant current leakage to ground with several motors in parallel | Check the cables connecting the drive to the motor, and the motor insulation; connect motor chokes. (The ATV12 manual prints SCF1 and SCF3 in one shared cell.) |
| SCF4 | ATV12 | IGBT short circuit: internal power component short circuit detected at power-on | Contact your local Schneider Electric representative. |
| SOF | ATV12 | Overspeed: instability, or overspeed linked to the inertia of the application | Check the motor; overspeed is 10% above Maximum frequency tFr, so adjust tFr if needed; add a braking resistor; check the size of the motor/drive/load and the speed loop parameters (gain and stability). |
| tnF | ATV12 | Auto-tuning fault: motor not connected, one motor phase lost, special motor, or motor rotating (for example driven by the load) | Check that the motor and drive are compatible and that the motor is present and completely stopped during auto-tuning; if an output contactor is used, close it during auto-tuning. |
| LFF1 | ATV12 | AI current lost: AI1 is set as a current input, its 0% scaling CrL1 is above 3 mA, and the input current is below 2 mA | Check the terminal connection. |
| ObF | ATV12 | Overbraking: braking too sudden or driving load too high · full fix | Increase the deceleration time; install a module unit with a braking resistor if necessary; check that the line supply voltage is under the maximum acceptable. |
| OHF | ATV12 | Drive overheat: drive temperature too high · full fix | Check the motor load, the drive ventilation and the ambient temperature. Wait for the drive to cool down before restarting. |
| OLC | ATV12 | Process overload | Check that the process and the drive parameters are in phase. |
| OLF | ATV12 | Motor overload: triggered by excessive motor current · full fix | Check the setting of the motor thermal protection and the motor load. |
| OPF1 | ATV12 | 1 output phase loss: loss of one phase at the drive output | Check the connections from the drive to the motor; with a downstream contactor, check the connection, cable and contactor. |
| OPF2 | ATV12 | 3 output phase loss: motor not connected, motor power below 6% of the drive nominal current, output contactor open, or instantaneous instability in the motor current | Check the connections from the drive to the motor. To test without a matching motor, set Output Phase loss detection OPL = nO. Check UFr, UnS and nCr and perform Auto-tuning tUn. |
| OSF | ATV12 | Main overvoltage: line voltage too high (10% over the maximum at power-on, or 20% over the maximum with no run order) or disturbed line supply | Turn off the drive; check and adjust the line voltage; power on again once it is back to nominal. If OSF comes and goes, relay R1 can be set to FLt and connected to upstream protection. |
| PHF | ATV12 | Input phase loss: drive incorrectly supplied or a fuse blown, one phase failed, 3-phase ATV12 on a 1-phase supply, or unbalanced load (only operates with the drive on load) · full fix | Check the power connection and the fuses; use a 3-phase supply. The fault can be disabled with Input Phase loss detection IPL = nO. |
| SCF5 | ATV12 | Load short circuit: short circuit at the drive output (also detected at the run or DC injection order if IGBT test Strt = YES) | Check the cables connecting the drive to the motor, and the motor insulation. |
| SLF1 | ATV12 | Modbus communication: interruption in communication on the Modbus network | Check the bus connections and the time-out (Modbus time out ttO); refer to the Modbus user manual. |
| SLF2 | ATV12 | SoMove communication: communication interruption with SoMove | Check the SoMove connecting cable and the time-out. |
| SLF3 | ATV12 | HMI communication: communication interruption with the external display terminal | Check the terminal connection. |
| SPIF | ATV12 | PI feedback fault: PID feedback below the lower limit | Check the PID function feedback, the PI feedback supervision threshold LPI and time delay tPI. |
| ULF | ATV12 | Process underload: motor current below the underload threshold LUL for the time set in ULt | Check that the process and the drive parameters are in phase. |
| tJF | ATV12 | IGBT overheat: drive overheated; IGBT internal temperature too high for the ambient temperature and load | Check the size of the load/motor/drive; reduce the switching frequency SFr; wait for the drive to cool before restarting. |
| EPF1 | ATV12 | External fault by logic input: event triggered by an external device | Check the device which caused the trip and reset. |
| CFF | ATV12 | Incorrect configuration: HMI block replaced by one configured on a drive with a different rating, or customer parameters inconsistent | Return to factory settings or retrieve the backup configuration, if it is valid. If the fault remains after factory settings, contact your local Schneider Electric representative. |
| CFI | ATV12 | Invalid configuration: the configuration loaded through the bus or network is inconsistent, or the upload was interrupted or not finished | Check the configuration loaded previously; load a compatible configuration. |
| CFI2 | ATV12 | Download invalid configuration: download with Loader or SoMove was interrupted | Check the connection with Loader or SoMove; restart the download or restore the factory setting. |
| USF | ATV12 | Undervoltage: line supply too low, or transient voltage dip · full fix | Check the voltage and the parameters of the Undervoltage/Phase Loss menu USb-. |
| F001 | ATV310 | Precharge: charging relay control fault or charging resistor damaged | Turn the drive off and back on; check the connections and the stability of the main supply. Contact your local Schneider Electric representative. |
| F002 | ATV310 | Unknown drive rating: power card and stored card versions different | Contact your local Schneider Electric representative. |
| F003 | ATV310 | Unknown or incompatible power board: the power card is incompatible with the control card | Contact your local Schneider Electric representative. |
| F004 | ATV310 | Internal serial link fault: communication interruption between the internal cards | Contact your local Schneider Electric representative. |
| F005 | ATV310 | Invalid industrialization zone: internal data inconsistent | Contact your local Schneider Electric representative. |
| F006 | ATV310 | Current measurement circuit fault: current measurement is not correct due to the hardware circuit | Contact your local Schneider Electric representative. |
| F007 | ATV310 | Internal thermal sensor fault: the drive temperature sensor is not operating correctly, or is in short circuit or open | Contact your local Schneider Electric representative. |
| F008 | ATV310 | Internal CPU: internal microprocessor fault | Turn the drive off and back on. Contact your local Schneider Electric representative. |
| F010 | ATV310 | Overcurrent: motor control parameters (menu 300-) not correct, inertia or load too high, or mechanical locking | Check the parameters, the size of the motor/drive/load and the state of the mechanism; connect line motor chokes; reduce the switching frequency range 315; check the ground connection of the drive, the motor cable and the motor insulation. |
| F018 | ATV310 | Motor short-circuit: short circuit or grounding at the drive output | Verify the cables connecting the drive to the motor and the motor insulation; adjust the switching frequency; connect chokes in series with the motor; verify the adjustment of the speed loop. (The ATV310 manual prints F018 and F019 in one shared cell.) |
| F019 | ATV310 | Ground short-circuit: ground fault while running, motor switching while running, or significant current leakage to ground with several motors in parallel | Verify the cables connecting the drive to the motor and the motor insulation; adjust the switching frequency; connect chokes in series with the motor; verify the adjustment of the speed loop. (The ATV310 manual prints F018 and F019 in one shared cell.) |
| F020 | ATV310 | IGBT short circuit: internal power component short circuit detected at power on | Contact your local Schneider Electric representative. |
| F025 | ATV310 | Overspeed: instability, or overspeed linked to the inertia of the application | Check the motor; if overspeed is 10% above Top frequency 308, adjust it if needed; add a braking resistor; check the size of the motor/drive/load and the speed loop parameters (gain and stability). |
| F028 | ATV310 | Autotuning fault: motor not connected, motor phase loss, special motor, or motor rotating (for example driven by the load) | Check that the motor and drive are compatible and that the motor is present and completely stopped; if a downstream output contactor is used, close it during auto-tuning. |
| F036 | ATV310 | Angle setting fault: during the phase-shift angle measurement, a motor phase is disconnected or the motor inductance is too high | Check the motor phases and the maximum current allowed by the drive. |
| F009 | ATV310 | Overbraking: sudden braking or load inertia too high | Increase the deceleration time; install a module unit with a braking resistor if necessary; check that the main supply voltage is under the maximum acceptable. |
| F011 | ATV310 | Drive overheat: drive temperature too high | Check the motor load, the drive ventilation and the ambient temperature. Wait for the drive to cool down before restarting. |
| F012 | ATV310 | Process overload fault | Check that the drive parameters and the application process are compatible. |
| F013 | ATV310 | Motor overload: triggered by excessive motor current | Check the configuration of the motor thermal protection and the motor load. |
| F014 | ATV310 | 1 output phase loss: loss of one phase on the drive output | Check the connections from the drive to the motor; with a downstream contactor, make sure the connection, cable and contactor are right. |
| F015 | ATV310 | 3 output phases loss: motor not connected, motor power below 6% of the rated drive current, output contactor open, or transient instability in the motor current | Check the connections from the drive to the motor. To test without a matching motor, set Output Phase loss detection 605 = 00. Check IR compensation 310, Rated motor voltage 304 and Rated motor current 305, then perform Auto-tuning 318. |
| F016 | ATV310 | Main overvoltage: line voltage too high (10% over the maximum at power on, or 20% over the maximum with no run command) or disturbed mains supply | Turn off the drive; check and adjust the line voltage; power on again once it is back to nominal. If F016 comes and goes, R1 assignment 205.0 can be set to 01 and connected to upstream protection. |
| F017 | ATV310 | Input phase loss: drive incorrectly supplied or a fuse blown, one phase failed, 3-phase ATV310 on a single-phase supply, or unbalanced load (only operates with the drive on load) | Check the power connection and the fuses; use a 3-phase supply. Reporting can be disabled with Input Phase loss detection 606 = 00. |
| F021 | ATV310 | Load short circuit: short circuit at the drive output (also detected at the run or DC injection command if IGBT Test 608 = 01) | Check the cables connecting the drive to the motor and the condition of the motor insulation. |
| F022 | ATV310 | Modbus interruption: interrupted communication on the Modbus network | Check the bus connections and the time-out (Modbus time out 704); refer to the Modbus user manual. |
| F024 | ATV310 | HMI communication: communication interruption with the external display terminal | Check the terminal connection. |
| F026 | ATV310 | PI feedback fault: PID feedback below the lower limit | Verify the PID function feedback, PID feedback supervision 59.25 and time delay 59.23. |
| F027 | ATV310 | IGBT overheat: drive overheated; IGBT internal temperature too high for the ambient temperature and load | Check the size of the load/motor/drive; reduce the switching frequency 315; wait for the drive to cool down before restarting. |
| F029 | ATV310 | Process underload fault: motor current below the underload threshold 211 for longer than the time delay 210 | Check that the drive parameters and the application process are compatible. |
| F033 | ATV310 | AI1 current loss: AI1 is set as a current input, its 0% scaling 204.1 is above 3 mA, and the input current is below 2 mA | Check the terminal connection. |
| F030 | ATV310 | Undervoltage: line supply too low, or transient voltage dip | Check the voltage and the parameters in the Undervoltage phase loss menu 607-. |
| F031 | ATV310 | Incorrect configuration: HMI block replaced by one configured on a drive with a different rating, or customer parameters inconsistent | Return to factory settings or retrieve the backup configuration, if it is valid. If the fault remains after factory settings, contact your local Schneider Electric representative. |
| F032 | ATV310 | Invalid configuration: the configuration loaded through the bus or network is inconsistent, or the upload was interrupted or not finished | Check the configuration loaded previously; load a compatible configuration. |
| F034 | ATV310 | Download invalid configuration: the drive found an invalid configuration while saving parameters or restoring factory settings | Power cycle the drive; restore the factory setting. If the fault remains, contact your local Schneider Electric representative. |
| ANF | ATV320 | Load slipping: the difference between the output frequency and the speed feedback is not correct | Check the motor, gain and stability parameters; add a braking resistor; check the size of the motor/drive/load; check the encoder coupling and wiring; check the parameter settings. |
| ASF | ATV320 | Angle error: during the phase-shift angle measurement, a motor phase is disconnected or the motor inductance is too high | Check the motor phases and the maximum current allowed by the drive. |
| BLF | ATV320 | Brake control error: brake release current not reached; the manual also lists the brake engage frequency threshold BEN (only regulated when brake logic control is assigned) | Check the drive/motor connection and the motor windings; check the IBR and IRD settings; apply the recommended settings for BEN. |
| BRF | ATV320 | Brake feedback error: the brake feedback contact does not match the brake logic, or the brake does not stop the motor quickly enough | Check the feedback circuit and the brake logic control circuit; check the mechanical state of the brake and the brake linings. |
| CFF | ATV320 | Incorrect configuration: option module changed or removed, control block replaced by one from a drive with a different rating, or configuration inconsistent | Check that there are no module errors; return to factory settings (FCS-) or retrieve the backup configuration, if it is valid. |
| CFI | ATV320 | Invalid configuration: the configuration loaded through the bus or network is inconsistent | Check the configuration loaded previously; load a compatible configuration. |
| CFI2 | ATV320 | Configuration transfer error: the configuration loaded through the bus or network is inconsistent | Check the configuration loaded previously; load a compatible configuration. |
| CNF | ATV320 | Fieldbus module communication interruption | Check the environment (electromagnetic compatibility), the wiring and the time-out; replace the option module. Contact Schneider Electric Product Support. |
| COF | ATV320 | CANopen communication interruption | Check the communication bus and the time-out; refer to the CANopen user manual. |
| CRF1 | ATV320 | Precharge capacitor error: charging relay control error or charging resistor damaged | Turn the drive off and on again; check the internal connections. Contact Schneider Electric Product Support. |
| CSF | ATV320 | Channel switching error: switch to channels that are not valid | Check the function parameters. |
| DLF | ATV320 | Dynamic load error: abnormal load variation | Check that the load is not blocked by an obstacle. Removing the run command causes a reset. |
| EEF1 | ATV320 | EEprom control error: internal memory error, control block | Check the environment (electromagnetic compatibility); turn off, reset, return to factory settings. Contact Schneider Electric Product Support. |
| EEF2 | ATV320 | EEprom power error: internal memory error, power board | Check the environment (electromagnetic compatibility); turn off, reset, return to factory settings. Contact Schneider Electric Product Support. |
| EPF1 | ATV320 | External error: event triggered by an external device | Check the device which caused the trip and reset. |
| EPF2 | ATV320 | Fieldbus external error: event triggered by a communication network | Check the cause of the trip and reset. |
| FBE | ATV320 | Function block error | See [FB Error] FBFT for details. |
| FBES | ATV320 | Function block stop error: function blocks were stopped while the motor was running | Check the [FB Motor Stop Type] FBSM configuration. |
| FCF1 | ATV320 | Output contactor closed: the output contactor stays closed although the opening conditions are met | Check the contactor and its wiring, and the feedback circuit. |
| FCF2 | ATV320 | Output contactor opened: the output contactor stays open although the closing conditions are met | Check the contactor and its wiring, and the feedback circuit. |
| HCF | ATV320 | Boards compatibility: Boards pairing (PPI-) is configured and a drive card has been changed | If a card is faulty, reinsert the original card; if the card was changed on purpose, confirm with the Pairing password PPI. |
| HDF | ATV320 | IGBT desaturation: short circuit or grounding at the drive | Check the cables connecting the drive to the motor, and the motor insulation. |
| ILF | ATV320 | Internal link error: communication interruption between the option module and the drive | Check the environment (electromagnetic compatibility) and the connections; replace the option module. Contact Schneider Electric Product Support. |
| INF1 | ATV320 | Internal error 1 (Rating): the power board is different from the board stored | Check the reference of the power board. |
| INF2 | ATV320 | Internal error 2 (Soft): the power board is incompatible with the control block | Check the reference of the power board and its compatibility. |
| INF3 | ATV320 | Internal error 3 (Intern Comm): communication interruption between the internal cards | Check the internal connections. Contact Schneider Electric Product Support. |
| INF4 | ATV320 | Internal error 4 (Manufacturing): internal data inconsistent | Re-calibrate the drive (done by Schneider Electric Product Support). |
| INF6 | ATV320 | Internal error 6 (Option): the option installed in the drive is not recognized | Check the reference and compatibility of the option, and that it is well inserted. |
| INF9 | ATV320 | Internal error 9 (Measure): the current measurements are incorrect | Replace the current sensors or the power board. Contact Schneider Electric Product Support. |
| INFA | ATV320 | Internal error 10 (Mains): the input stage is not operating correctly | Contact Schneider Electric Product Support. |
| INFB | ATV320 | Internal error 11 (Temperature): the drive temperature sensor is not operating correctly | Replace the drive temperature sensor. Contact Schneider Electric Product Support. |
| INFE | ATV320 | Internal error 14 (CPU): internal microprocessor error | Turn off and reset. Contact Schneider Electric Product Support. |
| LCF | ATV320 | Input contactor error: the drive is not turned on even though Mains V. time out LCT has elapsed | Check the contactor and its wiring, the time-out, and the supply mains/contactor/drive connection. |
| LFF3 | ATV320 | AI3 4-20 mA loss: loss of the 4-20 mA reference on analog input AI3 | Check the connection on the analog inputs. |
| OBF | ATV320 | DC bus overvoltage: braking too sudden or driving load, or supply voltage too high · full fix | Increase the deceleration time; install a braking resistor if necessary; activate Dec.Ramp Adapt BRA if compatible with the application; check the supply voltage. |
| OCF | ATV320 | Overcurrent: parameters in the SET- and DRC- menus not correct, inertia or load too high, or mechanical locking · full fix | Check the parameters, the size of the motor/drive/load and the state of the mechanism; decrease Current Limitation CLI; increase the switching frequency. |
| OHF | ATV320 | Drive overheating: drive temperature too high · full fix | Check the motor load, the drive ventilation and the ambient temperature. Wait for the drive to cool down before restarting. |
| OLC | ATV320 | Process overload | Check and remove the cause of the overload; check the parameters of the Process overload OLD- function. |
| OLF | ATV320 | Motor overload: triggered by excessive motor current · full fix | Check the setting of the motor thermal protection and the motor load. Wait for the motor to cool down before restarting. |
| OPF1 | ATV320 | Single output phase loss: loss of one phase at the drive output | Check the connections from the drive to the motor. |
| OPF2 | ATV320 | Output phase loss: motor not connected or motor power too low, output contactor open, or instantaneous instability in the motor current | Check the connections from the drive to the motor. If an output contactor is used, set Output phase loss OPL to OAC. To test without a matching motor, set OPL = NO. Check UFR, UNS and NCR and perform Autotuning TUN. |
| OSF | ATV320 | Supply mains overvoltage: supply voltage too high, or disturbed mains supply | Check the supply voltage. |
| OTFL | ATV320 | DI6=PTC overheat: overheating of the PTC probes detected on input DI6 | Check the motor load, motor size and motor ventilation; wait for the motor to cool before restarting; check the type and state of the PTC probes. |
| PHF | ATV320 | Input phase loss: drive incorrectly supplied or a fuse blown, one phase missing, 3-phase ATV320 on a single-phase supply, or unbalanced load (only operates with the drive on load) · full fix | Check the power connection and the fuses; use a 3-phase supply. The error can be disabled with InPhaseLoss Assign IPL = NO. |
| PTFL | ATV320 | DI6=PTC probe error: the PTC probe on input DI6 is open or short-circuited | Check the PTC probe and the wiring between it and the motor/drive. |
| SAFF | ATV320 | Safety function error: debounce time exceeded, SS1 threshold exceeded, incorrect configuration, or SLS type overspeed | Check the safety functions configuration and the ATV320 Integrated Safety Functions manual. Contact Schneider Electric Product Support. |
| SCF1 | ATV320 | Motor short circuit: short circuit or grounding at the drive output · full fix | Check the cables connecting the drive to the motor, and the motor insulation; connect chokes in series with the motor; check the speed loop and brake adjustment; increase Time to restart TTR. The remedy list gives both reduce and increase the switching frequency. |
| SCF3 | ATV320 | Ground short circuit: significant earth leakage current at the drive output if several motors are connected in parallel | Check the cables connecting the drive to the motor, and the motor insulation; reduce the switching frequency; connect chokes in series with the motor; check the speed loop and brake adjustment; increase Time to restart TTR. |
| SCF4 | ATV320 | IGBT short circuit: power component error | Contact Schneider Electric Product Support. |
| SCF5 | ATV320 | Motor short circuit: short circuit at the drive output | Check the cables connecting the drive to the motor, and the motor insulation. Contact Schneider Electric Product Support. |
| SLF1 | ATV320 | Modbus communication interruption | Check the communication bus and the time-out; refer to the Modbus user manual. |
| SLF2 | ATV320 | PC communication interruption: communication interruption with the PC software | Check the PC software connecting cable and the time-out. |
| SLF3 | ATV320 | HMI communication interruption: with the graphic display terminal or remote display terminal | Check the terminal connection and the time-out. |
| SOF | ATV320 | Motor overspeed: instability or driving load too high, downstream contactor not closed before the Run command, or overspeed threshold (110% of Max Frequency TFR) reached | Check the motor, gain and stability parameters; add a braking resistor; check the size of the motor/drive/load; check the Frequency meter FQF- settings if used; close the motor contacts before the Run command; Schneider recommends TFR at least 110% of High Speed HSP. |
| SPF | ATV320 | Encoder feedback loss: signal on the Pulse input missing (if used for speed measurement), or encoder feedback signal missing | Check the input cable wiring and the detector, the encoder configuration parameters, the wiring between the encoder and the drive, and the encoder. |
| SSF | ATV320 | Torque limitation error: switch to torque or current limitation | Check for mechanical problems; check the parameters of Torque limitation TOL- and Torque or I limit detect TID-. |
| TJF | ATV320 | IGBT overheating: drive overheated | Check the size of the load/motor/drive; reduce the switching frequency. The manual then says: "Wait for the motor to cool before restarting." |
| TNF | ATV320 | Autotuning error: special motor or motor power not suitable for the drive, motor not connected, or motor not stopped | Check that the motor and drive are compatible, that the motor is present and stopped during auto-tuning; if an output contactor is used, close it during auto-tuning. |
| ULF | ATV320 | Process underload | Check and remove the cause of the underload; check the parameters of the Process underload ULD- function. |
| USF | ATV320 | Supply mains undervoltage: supply mains too low, or transient voltage dip · full fix | Check the voltage and the parameters of Undervoltage handling USB-. |
| InIt | ATV12, ATV310, ATV320 | Initializing: the microcontroller is initializing and searching for the communication configuration (not a fault) | — |
| COM.E | ATV12, ATV310, ATV320 | Communication error (flashing): 50 ms time-out. ATV12 and ATV310 manuals: shown after 220 retry attempts; ATV320 manual: after 20 attempts | — |
| A-17 | ATV12, ATV310, ATV320 | Key alarm (flashing): a key held down for more than 10 seconds, keypad (membrane switch) disconnected, or keypad woken up while a key is pressed | — |
| cLr | ATV12, ATV310, ATV320 | Confirm fault reset (flashing): shown when the STOP key is pressed while there is a fault (ATV320: when the remote display terminal is the active command channel) | — |
| dEU.E | ATV12, ATV310, ATV320 | Drive mismatch (flashing): the drive brand does not match the remote display terminal brand | — |
| rOM.E | ATV12, ATV310, ATV320 | ROM abnormality (flashing): the terminal found a ROM problem by checksum calculation | — |
| rAM.E | ATV12, ATV310, ATV320 | RAM abnormality (flashing): the terminal found a RAM problem | — |
| CPU.E | ATV12, ATV310, ATV320 | Other fault (flashing): other detected fault (shown on the remote display terminal) | — |
| nSt | ATV12, ATV320 | Not a fault: freewheel stop. Shown when the Freewheel stop input is not powered, or when control is on Modbus/fieldbus and the bus has not sent a command yet | Normal. Check the logic input assignment (ATV12: COnF/FULL/FUn-/Stt-), or wait for the bus to send a command. |
| FSt | ATV12, ATV320 | Not a fault: fast stop. Shown when the Fast stop input is not powered | Normal. Check the logic input assignment (ATV12: COnF/FULL/FUn-/Stt-). |
| rdY | ATV12 | Not a fault: shown with the Fast stop/Freewheel functions. The ATV12 manual's sentence reads "it will display rdY en freewheel stop"; the ATV310 manual's matching sentence says this code shows at the end of a freewheel stop. | Normal. Check the logic input assignment (COnF/FULL/FUn-/Stt-) and that the run command input is active. |
| 502.1 | ATV310 | Not a fault: freewheel stop. Shown when the Freewheel stop input is not powered, or when control is on Modbus and the bus has not sent a command yet | Normal. Check the logic input assignment in COnF/FULL/500-/502-, or wait for the bus to send a command. |
| --01 | ATV310 | Not a fault: fast stop mode | Normal. Check the logic input assignment in COnF/FULL/500-/502-. |
| --00 | ATV310 | Not a fault: shown at the end of a freewheel stop | Normal. Check that the run command input is active for the selected control mode. |
Good to know
- ATV310 shows numbered codes. The ATV310 manual gives a name for each number (for example F010 Overcurrent, F009 Overbraking, F030 Undervoltage) but does not list a letter code for each one, so the numbers are shown here as printed. Where an ATV12 or ATV320 fault has the same name, the guide pages say so. The ATV310 manual's own text does use USF in the note above F030 and CFI in the footnote to F032.
- ATV12, needs a power cycle: CrF1, InFI, InF2, InF3, InF4, InF9, ----, InFb, InFE, OCF, SCF1, SCF3, SCF4, SOF and tnF. Remove the cause, then turn the drive off and on. SOF and tnF can also be reset by a logic input (Detected fault reset assignment rSF).
- ATV12, cleared by automatic restart once the cause has gone: LFF1, ObF, OHF, OLC, OLF, OPF1, OPF2, OSF, PHF, SCF5, SLF1, SLF2, SLF3, SPIF, ULF, tJF and EPF1. These can also be cleared by turning the drive off and on, or by a logic input (rSF). CFF, CFI, CFI2 and USF clear as soon as the cause disappears (USF can also be cleared by a logic input).
- ATV310, needs a power cycle: ----, F001 to F008, F010, F018, F019, F020, F025, F028 and F036. F025 and F028 can also be reset by a logic input (parameter 601). F007, F025 and F028 can be inhibited and cleared by a logic input (parameter 610).
- ATV310, cleared by automatic restart once the cause has gone: F009, F011 to F017, F021, F022, F024, F026, F027, F029 and F033, also by turning off and on or by a logic input (601). F030, F031, F032 and F034 clear as soon as the cause disappears. Some faults can also be reset with the RUN key (parameter 614).
- ATV320 (summary table p.403), needs a power reset: ANF, ASF, BLF, BRF, CRF1, EEF1, EEF2, FCF1, HDF, ILF, INF1 to INF4, INF6, INF9, INFA, INFB, INFE, SAFF, SOF and SPF (ASF, BRF, SOF, SPF and TNF also by the Fault Reset Assign RSF input). Automatic restart: CNF, COF, EPF1, EPF2, FBES, FCF2, LCF, LFF3, OBF, OHF, OLF, OLC, OPF1, OPF2, OSF, OTFL, PTFL, SCF4, SCF5, SLF1 to SLF3, SSF, TJF, TNF and ULF. Clear when the cause goes: CFF, CFI, CFI2, CSF, DLF, FBE, HCF, PHF and USF. OCF, SCF1 and SCF3 clear by the RSF input only if Extended Fault Reset HRFC = YES; otherwise they need a power reset.
- ATV320: the per-code pages of the manual say ASF, BRF, SOF and SPF can be cleared by Auto Fault Reset ATR, while the summary table on p.403 lists them under power reset. The manual does not say which applies; a power reset is the method the summary table gives. TNF is listed both in the RSF sentence and in the automatic-restart group.
- ATV320 reset methods: switch off until the display goes out completely and switch on again; Auto Fault Reset (ATR-); a logic input or control bit assigned to Fault reset (RST-); or the STOP/RESET key on the graphic display terminal when the HMI is the active command channel.
- CFF after a part change (ATV320): if an option module was changed or removed on purpose, pressing ENT twice restores the factory settings of the parameter groups affected by that module; if the control block was changed on purpose, pressing ENT twice restores all factory settings. ATV12 and ATV310: the fault can be cleared by returning to factory settings.
- The ATV12 manual prints codes in the drive's display lettering (for example ObF, tnF, tJF, InFb); the ATV320 manual writes the same letters in capitals (OBF, TNF, TJF, INFB).
- InFI is printed as InFI in the ATV12 manual. The ATV320 manual's INF1, Internal error 1 (Rating), has the same cause: the power board is different from the board stored.
हिंदी में
Schneider Electric Altivar VFD (ATV12, ATV310, ATV320) के फ़ॉल्ट कोड Schneider के अपने मैनुअल से: OCF मतलब ज़्यादा करंट, OBF/ObF मतलब Overbraking (ATV12) या DC बस ओवरवोल्टेज (ATV320), OHF मतलब ड्राइव गरम, OLF मतलब मोटर ओवरलोड, SCF1 मतलब मोटर शॉर्ट सर्किट, USF मतलब वोल्टेज कम, PHF मतलब इनपुट फ़ेज़ गायब। ATV310 में नंबर वाले कोड (F001 से F036) आते हैं।
- ड्राइव की नेमप्लेट पर मॉडल देखें (ATV12, ATV310 या ATV320)।
- कोड का मतलब नीचे उसी मॉडल की लाइन में देखें।
- nSt, FSt (ATV12/ATV320), rdY (ATV12) या 502.1, --01, --00 (ATV310) फ़ॉल्ट नहीं हैं: स्टॉप इनपुट चालू नहीं है या ड्राइव बस से कमांड का इंतज़ार कर रही है।
- वायरिंग या मोटर का काम सिर्फ़ इलेक्ट्रीशियन करे। Schneider के ATV320 मैनुअल के अनुसार: बाहरी कंट्रोल सप्लाई समेत सारी बिजली बंद करें, स्विच को बंद हालत में लॉक करें, 15 मिनट रुकें (ड्राइव की LED से पता नहीं चलता कि DC बस में करंट नहीं है), और PA/+ व PC/- के बीच DC बस वोल्टेज 42 V DC से कम नापें। वोल्टेज कम न हो तो ड्राइव को न छुएं, न चलाएं; Schneider Electric से संपर्क करें।
- कारण ठीक करने के बाद मैनुअल के अनुसार रीसेट करें (कुछ कोड के लिए बिजली बंद करके फिर चालू करनी पड़ती है)।
Questions people ask
What is OCF fault in a Schneider Altivar drive?
Overcurrent. The ATV12 and ATV320 manuals list wrong motor control parameters, inertia or load too high, and mechanical locking as causes. Check the parameters, the motor/drive/load size and the mechanism. On ATV12 and ATV320 it needs a power reset (on ATV320 the RSF input can clear it if Extended Fault Reset HRFC = YES).
What does OBF or ObF mean on a Schneider VFD?
ATV12 calls ObF Overbraking; ATV320 calls OBF DC bus overvoltage. Causes are braking too sudden or a driving load (ATV320 adds supply voltage too high). The first fix in both manuals is to increase the deceleration time, and to add a braking resistor if necessary.
What is F010 on an ATV310?
The ATV310 manual names F010 Overcurrent: motor control parameters not correct, inertia or load too high, or mechanical locking. It needs a power cycle after the cause is removed.
The drive shows nSt and will not start. Is it faulty?
No. Schneider says nSt (freewheel stop) shows when the Freewheel stop input is not powered, or when the drive is controlled over Modbus or a fieldbus and the bus has not sent a command yet. On ATV310 the same state shows as 502.1.
How do I reset a Schneider Altivar fault?
Remove the cause first. Some codes need the drive switched off and on, some clear by automatic restart or a logic input assigned to fault reset, and some clear on their own once the cause is gone. The groups for each model are listed under Good to know.
Sources
- Schneider Electric Altivar 12 User manual BBV28581 (version 06, 02/2026): Diagnostics and Troubleshooting, pp.111–116
- Schneider Electric Altivar ATV310 User manual EAV94277 (version 12, 05/2026): Diagnostics and Troubleshooting, pp.124–129
- Schneider Electric ATV320 Programming Manual NVE41295 (version 06, 04/2025): Diagnostics and Troubleshooting, pp.402–421
Last checked: